3 Digital I/O Specifications
3.1.2 200-VAC 16-point Input Module
3-8
3) The following diagram shows an example of terminal connections.
Connect power supplies of the same phase to the Common 1 and Common 2.
If power supplies of different phases are connected, overheating or fire may
occur.
Note: (1) Crimp Terminals
Use M3 terminal for crimping to the terminal block.
(2) Recommended Wires
Use wires of 1.3 mm
2
(AWG16) to 0.5mm
2
(AWG20) to connect to the terminal
block.
(3) Terminal 10 and terminal 20 are not connected.
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Common 1
Not connected.
Input 9
Input 10
Input 11
Input 12
Input 13
Input 14
Input 15
Input 16
Common 2
Not connected.200 VAC
Terminals
EXAMPLE