Property
Object Type
Device
Analog
Input
Analog
Output
Analog
Value
Binary
Input
Binary
Output
Binary
Value
ADPU_Timeout Yes – – – – – –
Number_Of_ADPU_Retries Yes – – – – – –
Max_Masters Yes – – – – – –
Max_Info_Frames Yes – – – – – –
Device_Address_Binding Yes – – – – – –
Database_Revision Yes – – – – – –
Present_Value – Yes Yes Yes Yes Yes Yes
Status_Flags – Yes Yes Yes Yes Yes Yes
Event_State – Yes Yes Yes Yes Yes Yes
Reliability – Yes Yes Yes Yes Yes Yes
Out_Of_Service – Yes Yes Yes Yes Yes Yes
Units – Yes Yes Yes – – –
Priority_Array – –
Yes
<1>
Yes
<1>
– Yes Yes
Relinquish_Default – –
Yes
<1>
Yes
<1>
– Yes Yes
Polarity – – – – Yes Yes –
Inactive_Text – – – – Yes Yes Yes
Active_Text – – – – Yes Yes Yes
<1> For Commandable Object Instances only.
u
Analog Input Objects
Table 12 Analog Input Objects
Object ID Object Name
Modbus
Address
Precision Range Units PV Access
AI1 Analog Input 1 Level 004EH XXXX.X – % R
AI2 Analog Input 2 Level 004FH XXXX.X – % R
AI3 Not Used AI3 – – – – –
AI4 Not Used AI4 – – – – –
AI5 Not Used AI5 – – – – –
AI6 Display Format o1-03 0502H XXXXX – – R
AI7 Scale Format b5-20 01E2H XXXXX – – R
AI8 Inverter Model o2-04 0508F XXXXX – – R
AI9 Rated Current n9-01 05D0H XXXX.X – Amps R
10 BACnet Objects Supported
34
YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual