Yaskawa BACnet MS/TP User Manual Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
Property
Object Type
Device
Analog
Input
Analog
Output
Analog
Value
Binary
Input
Binary
Output
Binary
Value
ADPU_Timeout Yes
Number_Of_ADPU_Retries Yes
Max_Masters Yes
Max_Info_Frames Yes
Device_Address_Binding Yes
Database_Revision Yes
Present_Value Yes Yes Yes Yes Yes Yes
Status_Flags Yes Yes Yes Yes Yes Yes
Event_State Yes Yes Yes Yes Yes Yes
Reliability Yes Yes Yes Yes Yes Yes
Out_Of_Service Yes Yes Yes Yes Yes Yes
Units Yes Yes Yes
Priority_Array
Yes
<1>
Yes
<1>
Yes Yes
Relinquish_Default
Yes
<1>
Yes
<1>
Yes Yes
Polarity Yes Yes
Inactive_Text Yes Yes Yes
Active_Text Yes Yes Yes
<1> For Commandable Object Instances only.
u
Analog Input Objects
Table 12 Analog Input Objects
Object ID Object Name
Modbus
Address
Precision Range Units PV Access
AI1 Analog Input 1 Level 004EH XXXX.X % R
AI2 Analog Input 2 Level 004FH XXXX.X % R
AI3 Not Used AI3
AI4 Not Used AI4
AI5 Not Used AI5
AI6 Display Format o1-03 0502H XXXXX R
AI7 Scale Format b5-20 01E2H XXXXX R
AI8 Inverter Model o2-04 0508F XXXXX R
AI9 Rated Current n9-01 05D0H XXXX.X Amps R
10 BACnet Objects Supported
34
YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual