Yaskawa J7 Drive User Manual

Browse online or download User Manual for Equipment Yaskawa J7 Drive. Yaskawa J7 Drive User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Technical Manual

J7 DriveTechnical ManualModels: JD and CIMR-J7AM Document Number: TM.J7.01

Page 2

Sequence and Reference Explained Sequence – refers to how the Drive is started, stopped, and told which direction to run. When the sequence comes fr

Page 3

QUICK REFERENCE FOR PARAMETERS ...Inside CoverCURRENT RATINGS AND HORSEPOWER RANGE ... iWARNINGS

Page 4

5.20 Reset Codes: 2-Wire, 3-Wire Initialization ... 5-305.21 Slip Compensation ...

Page 5 - INSTALLATION

1-1The J7 drive is a pulse width modulated general purpose AC drive which generates an adjustablevoltage/frequency, three phase output for speed contr

Page 6

1-2Figure 1-1. Component Identification (Sheet 1 of 2)Ground TerminalMain Circuit Output Terminal BlockControl Circuit BlockSW8 Analog InputCurrent/Vo

Page 7

1-3Figure 1-1. Component Identification (Sheet 2 of 2)Ground TerminalMain Circuit Output Terminal BlockControl Circuit BlockSW8 Analog Input Current/V

Page 8

1-4The Drive leaves the factory with all parameters set for 2-Wire external reference control. Figure 1-5must be used for all external connections.To

Page 9

1-5B. Control Circuit All basic control circuit (signal) interconnections are shown in the appropriate diagram:• Interconnections for external two

Page 10 - - viii

1-6DATA FUNCTION DESCRIPTION*S1 Input 1 Factory setting is " Forward Run/Stop " (1).(Forward run when closed, stop when open)S2 Multi-Functi

Page 11

1-7Continued1.4 ELECTRICAL INSTALLATIOND. Auxiliary Input and Output Power Option DevicesFigure 1-3 is a factory guideline for proper wiring pract

Page 12

Note 1: Factory setting differs depending on drive capacity. See Appendix 3-1.QUICK REFERENCE – J7 PARAMETERSPARA- FACTORY USERMETERS SETTING SETTIN

Page 13

E. Conformance to European EMC DirectiveIn order to conform to EMC standards, the following methods are required for line filter application,cable s

Page 14 - 1.3 PHYSICAL INSTALLATION

1-9Continued1.4 ELECTRICAL INSTALLATIONFigure 1-4. Installation of Line Filter and Drive

Page 15

1-10NOTES FOR FIGURE 1-5✱ – Indicates components not supplied.– Main circuit terminal.– Indicates control circuit terminal.( ) – Indicates altern

Page 16

1-11Continued1.4 ELECTRICAL INSTALLATIONL1 ( R )L2 ( S )L3 ( T )FREQUENCYSETTING POWER SUPPLY (+12V, 20mA) (See Note 2)REFERENCEFREQUENCYSETTIN

Page 17

1-12NOTES FOR FIGURE 1-6✱ – Indicates components not supplied.– Main circuit terminal.– Indicates control circuit terminal.( ) – Indicates altern

Page 18 - 1.4 ELECTRICAL INSTALLATION

1-13Continued1.4 ELECTRICAL INSTALLATIONL1 ( R )L2 ( S )L3 ( T )FREQUENCYSETTING POWER SUPPLY (+12V, 20mA) (See Note 2)REFERENCEFREQUENCYSETTIN

Page 19 - T1, T2, T3

2-1• Verify wires are properly connected and no erroneous grounds exist.• Remove all debris from the enclosure, such as loose wire clippings, metal

Page 20

2-2IMPORTANT: 2-wire or 3-wire sequence selection must be made prior to any other adjustments(Parameter n01).2.2 STARTUP PROCEDUREDIGITAL OPERATOR

Page 21

2-3DIGITAL OPERATOR DESCRIPTION KEY SEQUENCE DISPLAYTable 2-1. Startup Procedure - ContinuedSet Parameter n10-Voltage Max.(460 V)Press then .DATAENTE

Page 22 - NOTES FOR FIGURE 1-5

2-4DIGITAL OPERATOR DESCRIPTION KEY SEQUENCE DISPLAYTable 2-1. Startup Procedure - ContinuedSet Parameter n13-Voltage - Midpoint(80 V)Press then .DAT

Page 23 - FIG. 1-5 (305)

- i -CURRENT RATINGS & HORSEPOWER RANGERATED CURRENT NOMINAL OLD DRIVENEW DRIVEINPUT RATING (AMPS) HORSEPOWER MODEL NO.MODEL NO.CIMR-J7AM0.8 1/8 J

Page 24

2-5DIGITAL OPERATOR DESCRIPTION KEY SEQUENCE DISPLAYTable 2-1. Startup Procedure - ContinuedTest run the drive from theDigital OperatorWARNING:The ne

Page 25 - FIG. 1-6 (305)

3-1After completing the start-up, and programming of constants, turn off the AC main circuit power.Make additional wiring connections required for the

Page 26 - Section 2. INITIAL START-UP

4-1All functions of the Drive are accessed using the Digital Operator. In addition to controlling motoroperation, the operator can enter information i

Page 27 - Table 2-1. Startup Procedure

4-2ContinuedB. Description of Function LEDsBy pressing the DSPL key on the Digital Operator, the operator can step to each of the sevenFunction LEDs a

Page 28

4-3There are two indicator LEDs on the front of the Drive. The Drive status is indicated by variouscombinations of ON, Blinking, and OFF conditions of

Page 29

4-4Fault record displayWhen U-09 is selected, a three-digit box is displayed.• Example ... 3-digit numbers :Fault description“---” is displa

Page 30

5-1This section describes features of the Drive which are defined by programmed settings in the variousparameters in memory. Since most features use m

Page 31 - Section 3. OPERATION AT LOAD

5-2A.n16: Accel Time 1 Factory setting (each): 10.0secondsn17: Decel Time 1Range (each): 0.0 to 999 secondsn18: Accel Time 2 Factory setting (each):

Page 32 - Section 4. DIGITAL OPERATOR

5-3n020 : S-Curve SelectionFactory setting: 0Range: 0 to 3Setting of this parameterdetermines the S-curve(starting) characteristics of the acceleratio

Page 33 - F/R LO/RE

5-4A. n48 : Number of Auto-Restart Attempts Factory setting: 0Range: 0 to 10When a fault occurs during operation, the Drive can be programmed for an a

Page 34 - IIIIII

- ii -CAUTIONParameter n10 must be set to proper motor voltage.CAUTIONAlways ground the drive using its ground terminal ( ) (near the maincircuit

Page 35

5-5n46CARRIER FREQUENCY(kHz) SLOPE OUTPUT FREQUENCY(Hz)MODESETTING Maximum(FcMAX) Minimum(FcMIN)(=Fc)FoF1 F21 2.5 2.5 0 NA NA CONSTANT2 5.0 5.0 0 NA N

Page 36

5-6A. n49 : Prohibited Frequency 1 Factory setting (each): 0.0n50 : Prohibited Frequency 2Range (each): 0.0 to 400 HzThese parameters allow programmin

Page 37

5-7n14 : Minimum Frequency Range: 0.1 to 10.0 Hzn52 : DC Injection Braking Current Factory setting: 50 %(% of Drive Rated Current)Range: 0 to 100 %n5

Page 38 - ACCELERATION

5-8ADJUSTMENT PROCEDURE:1. With no input, adjust Bias (n42 setting) until an output of 0.0 Hz is obtained.2. With full scale input, adjust Gain (n41 s

Page 39

5-9n30 : Frequency Reference Upper Limit Factory setting: 100 %Range: 0 to 110 %n31 : Frequency Reference Lower Limit Factory setting: 0 %Range: 0 to

Page 40 - MAX) Minimum(FcMIN)

5-10The Drive allows selection of up to eleven frequency references. One is an analog input (terminalFR), eight are digital presets (selected with mul

Page 41

5-11ContinuedExample 2 - Eight preset referencesProgramming: n37 = 6, n38 = 7 and n39 = 8DIGITAL PRESET S5 S4 S3Selectable Reference (2)Open Open Open

Page 42

5-12n29 : Jog Reference Factory setting: 6.0 HzRange: 0.0 to 400``````````` Hzn36 thru n39 : Multi-function Inputs Data 10 : Jog Selection(Term. S1 -

Page 43

5-13The Drive has the ability to have either a local or a remote reference and sequence selection.Local - Run and stop functions are controlled by the

Page 44

5-14Continuedn07 : Reference Selection - Digital Operator Factory setting: 0Range: 0 or 1This parameter is only effective when the Drive is in the loc

Page 45

J7 Simplified Startup Procedure This procedure is a simplified step by step guide to installing, programming, and using the

Page 46

5-15The Drive can perform serial communication by using a programmable controller (PLC), MODBUSprotocol, and by installing an optional RS-232 or RS-4

Page 47

5-16ContinuedC. Sending/Receiving DataData that can be sent and received are run/stop commands, frequency reference, fault reset, Drivestatus, and set

Page 48

5-17Continuedn69: Modbus Frequency Resolution Factory setting: 0Range: 0 to 3The frequency resolution from the PLC and in the frequency reference a

Page 49

5-18Continuedn68 : Modbus Time Out Detection Factory setting: 1Range: 0 to 4If time between Modbus messages exceeds 2.0 seconds, the Drive will resp

Page 50 - S- S+ SG R- R+

5-19n47 : Momentary Power Loss Ride-thru 0 = Disabled (Factory setting)Protection 1 = Enabled – 2 sec. power loss ride-thru2 = Enabled – indefi

Page 51

5-20The multi-function input terminals can be activated in one of two ways:The multi-function inputs are configured using rotary switch SW7, which is

Page 52

5-21Continued5.17 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S5)DATA FUNCTION DESCRIPTION*FWD/REV selection (for MUST BE SET ONLY IN n37 . Redefines t

Page 53

5-22Continued5.17 MULTI-FUNCTION INPUT TERMINALS (Term. S1-S5)A. Data 17 : Remote/LocalThe use of a Remote/Local command input allows switching betw

Page 54 - + –

5-23ContinuedC. Data 13 : External Base Block by N.C. ContactBase block operation is the same as described above, except that the Base Block contact m

Page 55

5-24ContinuedE. Data 34 : Up/Down FunctionProgramming data " 34 " for n39 (multi-function input terminal) allows the S4 / S5 inputs to be us

Page 56

5. Digital Operator The DSPL button cycles through all of the quick start LEDs. To access a parameter, press the DSPL button until the PRGM LED

Page 57

5-25ContinuedFWD RUN(S4) UPCOMMAND(S5) DOWNCOMMANDUPPERLIMIT SPEEDLOWERLIMIT SPEEDOUTPUT FREQUENCY*"SPEED AT SETFREQUENCY"SIGNAL* U = UP

Page 58

5-26Table 5-3. Multi-function Output TerminalsSetDescriptionValue ConditionSignal Level0 Fault Closed = Drive fault has occurred (except CPF0, CPF1)1

Page 59

5-27Continuedn58 : Speed Coincidence Frequency / Frequency Factory setting: 0.0 HzDetection LevelRange: 0.0 to 400 HzSpeed coincidence is used to con

Page 60 - OUTPUT SPEED

Overtorque detection is used to compare Drive rated output current/torque with the overtorquedetection level. When the output current is equal to or g

Page 61

5-29ContinuedE. n40 : Multi-function Output 1 Data 6 or 7 :Overtorque (terminals MA, MB & MC) DetectionThe Form-C contact, or an open collector o

Page 62 - C. Frequency Detection – High

5-30n01 : Parameter Selection / Initialization Factory setting: 1Range: 0 to 9The following table shows which parameters can be programmed (displayed

Page 63

5-31n65 : Motor No-Load Current Factory setting: See Table A3-1 Range: 0 to 99%Motor no-load current (n65 ) is set as a percentage of motor full-load

Page 64

A. n55 : Stall Prevention During Deceleration Factory setting: 0Range: 0 to 1Setting Function0 Stall prevention during deceleration enabled1 Stall pre

Page 65 - ———— S1 = Forward Run = Start

5-33n04 : Stopping Method Factory setting: 0Range: 0 to 1Selects the stopping method suitable for the application.Setting Description0 Deceleration (r

Page 66

5-34n32 : Motor Rated Current Factory setting: See Table A3-1Range: see descriptionThis parameter should be set, in increments of 0.1 A, to the rated

Page 67 - Setting Function

Example 1: Sequence & Reference From The Digital Operator When the Drive is set up with the sequence and the reference coming from the digital

Page 68 - 1 Coast to stop

5-35n63 : Torque Compensation Gain (KT)Factory setting: 1.0Range: 0.0 to 2.5 Torque Compensation Gain (n63) adjusts howmuch the output voltage is boos

Page 69 - OPERATION FREQUENCY (Hz)

5-365.26 V/f PATTERNThe V/f pattern can be tailored to suit your specific application and load characteristics by adjustingparameters n09 to n15 (s

Page 70 - T)Factory setting: 1.0

5-37Continuedn09 : Frequency – Max. (Fmax)n10 : Voltage – Max. (Vmax)n11 : Frequency – Max. Voltage point (FA)n12 : Frequency – Midpoint (FB)n13 : Vol

Page 71

5-38The optional Remote Digital Operator can be used to store (upload) parameters from a drive, whichcan then be copied (downloaded) to another drive.

Page 72

6-1This section describes the alarm and fault displays, explanations for fault conditions and correctiveactions to be taken if the Drive malfunctions.

Page 73

6-2Alarm DisplayDigital RUN (Green)DriveExplanationCauses andOperator ALARM (Red)Status Corrective ActionsOP (Parameter setting Check the setting val

Page 74

6-3Alarm DisplayDigital RUN (Green)DriveExplanationCauses andOperator ALARM (Red)Status Corrective ActionsBB (External baseblock) Check the external c

Page 75 - - Continued

6-4Fault DisplayDigital RUN (Green)DriveExplanationCauses andOperator ALARM (Red)Status Corrective ActionsOC (Overcurrent) • Short circuit orDrive out

Page 76

6-5Fault DisplayDigital RUN (Green)DriveExplanationCauses andOperator ALARM (Red)Status Corrective ActionsUV2 (Control power Cycle power.supply fault)

Page 77

6-6Fault DisplayDigital RUN (Green)DriveExplanationCauses andOperator ALARM (Red)Status Corrective ActionsEF Check the external circuit(External faul

Page 78

Example 2: Remote Sequence (2-Wire) & Remote Reference (4 – 20 mA) This configuration is used when the start & stop sign

Page 79

6-7Fault DisplayDigital RUN (Green)DriveExplanationCauses andOperator ALARM (Red)Status Corrective ActionsCPF-05 Cycle power.A/D converter fault is If

Page 80

6-8ConstantNo.Name DescriptionU-01Frequency referenceHzFrequency reference can be monitored.(FREF) (Same as FREF)U-02Output frequencyHzOutput frequenc

Page 81

A1-1The Drive control circuits use various parameters to select functions and characteristics of the Drive.Changing of parameter settings must be done

Page 82 - Table A1-1. J7 Parameters

A1-2Table A1-1. J7 Parameters - ContinuedPARAM- SETTING RANGE SETTING FACTORY USER PARA.ETER NAME (AND UNITS) INCREMENT SETTING SETTING REF.n21 Freque

Page 83

PARAM- SETTING RANGE SETTING FACTORY USER PARA.ETER NAME (AND UNITS) INCREMENT SETTING SETTING REF.n41Analog Frequency Reference0 to 255 1 (%) 100Gain

Page 84

A1-4Table A1-1. J7 Parameters - ContinuedPARAM- SETTING RANGE SETTING FACTORY USER PARA.ETER NAME (AND UNITS) INCREMENT SETTING SETTING REF.0: 2400 b

Page 85

A2-1(table continued on next page)Appendix 2. SPECIFICATIONSSee notes at end of table.SECTION A.Model No. Related SpecificationsOld Model No. JDA001 J

Page 86 - Appendix 2. SPECIFICATIONS

A2-2NOTES:(1)Based on an N.E.C. standard 4-pole motor for max. applicable motor output.(2)Shows deceleration torque for an uncoupled motor deceleratin

Page 87 - All Models (Continued)

A3-1The factory setting of certain parameters change with drive rating and control method selected. Thefollowing two tables list the parameters and ho

Page 88

230 V Old Drive Model No. JDA001 JDA002 JDA003 JDA005 JDA008 JDA011 JDA017New Drive Model No. CIMR-J7AM 20P10 20P20 20P40 20P70 21P50 22P20 23P70Capac

Page 89

Example 3: Remote Sequence (3-Wire) & Speed Potentiometer This configuration is best when a person rather than an external controller (PLC, rel

Page 90 - Appendix 5. J7 DIMENSIONS

A5-1Appendix 5. J7 DIMENSIONSW10.200.33H1HW DMIN MAXFREF FOUT IOUT MNTRF/R LO/RE PRGMRUNRUN ALARMDSPLDATAENTERSTOPRESETWeightLbs.Old DriveModel No.Dim

Page 91 - RUN ALARM

A5-2W1H1HW D0.200.33MIN MAXFREF FOUT IOUT MNTRF/R LO/RE PRGMRUNRUN ALARMDSPLDATAENTERSTOPRESETOld DriveModel No.Dimensions in InchesHorse-Power23535JD

Page 92

I-1- A -Acceleration :Accel time 1 ... 5-2Accel time 2 ... 5-2Hold ...

Page 93 - INDEX (Continued)

I-2INDEX (Continued) - J -Jog reference ... 5-12- K -Keypad — see Digital Operator- L -LEDs :Function ...

Page 94

I-3Slip compensation ... 5-31Soft start — see S-curveSpecifications ... A2-1Spee

Page 95 - Product Training

It is important to Yaskawa thatusers of our products have atotally satisfying ownershipexperience.Training is one of the mosteffective ways to ensure

Page 96

J7 Drive Technical Manual6/1/2003 TM.J7.01Document Number: TM.J7.01 (Supercedes TM 4305 and YEA-TOA-S606-12.1) 4/1/07

Comments to this Manuals

No comments