Yaskawa iQpump Controller User Manual User Manual

Browse online or download User Manual for Equipment Yaskawa iQpump Controller User Manual. Yaskawa iQpump Controller User Manual User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 266
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - User Manual

iQpump ControllerUser ManualDocument Number: TM.iQp.06 PRG: 0034 ~ 003X

Page 2

10 YASKAWA TM.

Page 3 - Miscellaneous Items:

Pump Tuning100 YASKAWA TM.iQp.06 iQpump Controller User ManualPump Tuning◆ PI Control Tuning (b5 Group)The built-in PI controller in the iQpump is

Page 4 - Table 1.2 Pump Quick Setup

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 101Figure 5.12 Figure 6. PI Feedback Response CharacteristicsFigure 5.13 Figure 5.1

Page 5

Pump Tuning102 YASKAWA TM.iQp.06 iQpump Controller User ManualTable 5.1 PI Setpoint OptionsIn some situations there are two feedback inputs. The i

Page 6

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 103 b5-08 PI Primary Delay Time ConstantSetting Range: 0.00 ~ 10.00 sFactory Default: 0

Page 7

Pump Tuning104 YASKAWA TM.iQp.06 iQpump Controller User Manual b5-17 PI Accel / Decel TimeSetting Range: 0.0 ~ 25.5 sFactory Default: 0.0 sThis is

Page 8

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 105◆ C1 Accel / Decel C1-01 Acceleration Time 1C1-02 Deceleration Time 1C1-03 Accelerat

Page 9 - Table of Contents

Pump Tuning106 YASKAWA TM.iQp.06 iQpump Controller User Manual d2-03 Master Speed Reference Lower LimitSetting Range: 0.0 ~ 110.0 %Factory Default

Page 10

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 107◆ E1 V/f Pattern E1-01 Input Voltage SettingSetting Range: 155.0 V ~ 255.0 V (208 V

Page 11

Pump Tuning108 YASKAWA TM.iQp.06 iQpump Controller User ManualTable 5.3 Preset V/f PatternsIf one of the custom V/f patterns is selected, then pa

Page 12

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 109 E1-06 Base FrequencySetting Range: 0.0 ~ 200.0 HzFactory Default: 60.0 Hz E1-07 Mi

Page 13 - Warnings and Cautions

YASKAWA TM.iQp.06 iQpump Controller User Manual

Page 14 - ◆ Intended Use

Pump Tuning110 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 5.18 Figure 5.6 Custom V/f Pattern Programming CurveIncreasing the voltage i

Page 15 - Introduction

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 111◆ H3 Analog Inputs H3-02 Terminal A1 Gain SettingSetting Range: 0.0 ~ 1000.0 %Factor

Page 16 - EXAMPLE:

Pump Tuning112 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 5.21 Figure 5.36 Output Frequency with Reduced Bias SettingAs a further exam

Page 17 - Physical Installation

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 113Figure 5.24 Figure 5.39 Connection of a 3-Wire 4~20 mA Feedback Device (H3-08 = 2)T

Page 18 - 208-230 Vac

Pump Tuning114 YASKAWA TM.iQp.06 iQpump Controller User Manual H3-09 Terminal A2 Function SelectionThe A2 analog input can be programmed to perfor

Page 19 - ◆ Nameplate Information

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 115Function: Aux ReferenceSetting: 2In order for the A2 analog input to be used as the m

Page 20 - ◆ Drive Model Numbers

Pump Tuning116 YASKAWA TM.iQp.06 iQpump Controller User Manual H3-11 Terminal A2 Bias SettingSetting Range: –100.0 % ~ +100.0 %Factory Default: 0.

Page 21 - 1.3 Component Names

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 117 L2-02 Momentary Power Loss Ride-Thru TimeSetting Range: 0.0 ~ 25.5 sFactory Default

Page 22 - 1.3 Component Names

Pump Tuning118 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 5.28 Figure 5.45 Automatic Restart Timing DiagramThe auto restart count is r

Page 23 - BOTTOM VIEW

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 119◆ L6 Torque Detection L6-01 Torque Detection Selection 1 L6-02 Torque Detection Lev

Page 24

12 YASKAWA TM.

Page 25 - 5 INCHES TOP AND BOTTOM

Pump Tuning120 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 5.46 Over Torque DetectionFigure 5.29 Figure 5.47 Under Torque Detection◆ L

Page 26 - FOR "A" SIZE SCREWS

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 121 L8-03 Overheat Pre-Alarm Operation SelectionThe iQpump drive is capable of warning

Page 27 - 1.5 Heat Loss Data

Pump Tuning122 YASKAWA TM.iQp.06 iQpump Controller User Manual L8-07 Output Phase Loss Protection <0033>The output phase loss detection circ

Page 28 - ◆ Installation Site

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 123 L8-19 Overheat Frequency Reference Reduction LevelSetting Range: 0.0 ~ 100.0 % of m

Page 29 - Type 1 iQpump drives

Pump Tuning124 YASKAWA TM.iQp.06 iQpump Controller User ManualThe active monitor displayed when the iQpump drive is powered on can be changed to ei

Page 30 - ◆ Removing the Terminal Cover

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 125◆ o2 Key Selections o2-06 Operation Selection when Digital Operator is DisconnectedL

Page 31 - Attaching the Front Cover

Pump Tuning126 YASKAWA TM.iQp.06 iQpump Controller User Manual o3-02 Read Allowed SelectionThe digital operator has parameter COPY capabilities vi

Page 32 - Attaching the Front Cover

Pump TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 127A successful VERIFY of the parameter values will display:If all the parameter values

Page 33 - IMPORTANT

5.2 Pump Basic128 YASKAWA TM.iQp.06 iQpump Controller User Manual5.2 Pump Basic◆ Parameter Overview — P1 GroupTable 5.6 ◆ P1 Pump Minimum Speed and

Page 34

5.2 Pump BasicYASKAWA TM.iQp.06 iQpump Controller User Manual 129Example: 3600 rpm Pump MotorDesired Operation: Minimum Speed is 2400 rpmSolution: P

Page 35 - Electrical Installation

YASKAWA TM.iQp.06 iQpump Controller User Manual 13Warnings and CautionsThis Section provides warnings and cautions pertinent to this product, that if

Page 36

5.2 Pump Basic130 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 5.34 Figure 5.51 Loss of Prime (LOP) FaultNote: Loss of prime function is

Page 37

5.3 Pump ProtectionYASKAWA TM.iQp.06 iQpump Controller User Manual 1315.3 Pump Protection◆ P2 Shutdown Pump System When Running at Low Speed (Sleep)

Page 38

5.3 Pump Protection132 YASKAWA TM.iQp.06 iQpump Controller User Manual Sleep Function Based on Output Frequency (P2-01 = 0) The iQpump drive enters

Page 39

5.3 Pump ProtectionYASKAWA TM.iQp.06 iQpump Controller User Manual 133 Sleep Function Based on Output Current (P2-01 = 1) The iQpump drive enters s

Page 40

5.3 Pump Protection134 YASKAWA TM.iQp.06 iQpump Controller User Manual Sleep Function Based on Feedback Level (P2-01 = 2) The iQpump drive enters s

Page 41

5.4 T1 Auto-TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 1355.4 T1 Auto-Tuning◆ T1-02 Motor Rated PowerSetting Range: 0.00 ~ 650.00 kWFacto

Page 42

5.4 T1 Auto-TuningYASKAWA TM.iQp.06 iQpump Controller User Manual 136THIS PAGE INTENTIONALLY BLANK

Page 43

YASKAWA TM.iQp.06 iQpump Controller User Manual 1376Diagnostics & TroubleshootingThis chapter describes diagnostics and troubleshooting for the iQ

Page 44

6.1 Fault Detection138 YASKAWA TM.iQp.06 iQpump Controller User Manual6.1 Fault DetectionWhen the iQpump drive detects a fault, the fault informatio

Page 45 - Ground Wiring

6.1 Fault DetectionYASKAWA TM.iQp.06 iQpump Controller User Manual 139CPF08WAT- E rrWatchdog Timer Fault(WAT)— Cycle power off and on to the iQpump.

Page 46 - 2.3 Control Wiring

14 YASKAWA TM.iQp.06 iQpump Controller User Manual ◆ Intended UseDrives are intended for installation in electrical systems or machinery.For use in

Page 47 - Wiring Checks

6.1 Fault Detection140 YASKAWA TM.iQp.06 iQpump Controller User ManualLFOutput Phase LossOutput Open-phaseAn open-phase occurred at the iQpump outpu

Page 48 - ◆ DIP Switch S1

6.1 Fault DetectionYASKAWA TM.iQp.06 iQpump Controller User Manual 141oL2Inv OverloadediQpump OverloadDesigned to protect the iQpump.The load is too

Page 49 - ◆ Shunt Connector CN15

6.1 Fault Detection142 YASKAWA TM.iQp.06 iQpump Controller User ManualUv2CTL PS UndervoltControl Power Supply UndervoltageUndervoltage of the contro

Page 50 - ◆ Sinking/Sourcing Mode

6.2 iQpump Keypad MessagesYASKAWA TM.iQp.06 iQpump Controller User Manual 1436.2 iQpump Keypad Messages◆ Pump Fault and Alarm MessagesThe iQpump has

Page 51 - Pump Motor

6.2 iQpump Keypad Messages144 YASKAWA TM.iQp.06 iQpump Controller User ManualPoCPump Over CyclePump Over Cycle Protection VFD Controlled Pump exceed

Page 52

6.3 Alarm DetectionYASKAWA TM.iQp.06 iQpump Controller User Manual 1456.3 Alarm DetectionThe alarms are iQpump drive protection functions that do no

Page 53 - 2.3 Control Wiring

6.3 Alarm Detection146 YASKAWA TM.iQp.06 iQpump Controller User ManualLL3Loss of Load Det 1(Flashing)Loss of Load Detection 1iQpump output current &

Page 54

6.3 Alarm DetectionYASKAWA TM.iQp.06 iQpump Controller User Manual 147◆ Pump Alarm Messages GeneratedDigital Operator DisplayDescription Cause Corre

Page 55 - Feedback Device (3-Wire)

6.4 Operator Programming Errors (oPE)148 YASKAWA TM.iQp.06 iQpump Controller User Manual6.4 Operator Programming Errors (oPE)An Operator Programming

Page 56

6.5 Auto-Tuning FaultsYASKAWA TM.iQp.06 iQpump Controller User Manual 1496.5 Auto-Tuning FaultsAuto-tuning faults are shown below. When the followin

Page 57 - Digital Operator

YASKAWA TM.iQp.06 iQpump Controller User Manual 15IntroductionThis Section describes the applicability of the Manual.The iQpump (P7U) is a Pulse Widt

Page 58 - 3.1 Digital Operator Display

6.6 Digital Operator COPY Function Faults150 YASKAWA TM.iQp.06 iQpump Controller User Manual6.6 Digital Operator COPY Function FaultsThese faults ca

Page 59 - 3.2 Digital Operator Keys

6.7 TroubleshootingYASKAWA TM.iQp.06 iQpump Controller User Manual 1516.7 TroubleshootingDue to problems sucha s parameter setting errors or faulty

Page 60 - 3.3 Drive Mode Indicators

6.7 Troubleshooting152 YASKAWA TM.iQp.06 iQpump Controller User ManualThe Speed Command is too low.If the Speed Command is set below the frequency s

Page 61 - ◆ Stop Indicator

6.7 TroubleshootingYASKAWA TM.iQp.06 iQpump Controller User Manual 153 The withstand voltage between the motor phases is insufficient.When the moto

Page 62 - 3.4 Drive Main Menu

6.7 Troubleshooting154 YASKAWA TM.iQp.06 iQpump Controller User Manual• Increase the parameter b2-04 (DC Injection Braking (initial excitation) Time

Page 63 - 3.4 Drive Main Menu

6.8 Main Circuit Test ProcedureYASKAWA TM.iQp.06 iQpump Controller User Manual 1556.8 Main Circuit Test ProcedureBefore attempting any troubleshooti

Page 64 - U1 Monitor List

6.8 Main Circuit Test Procedure156 YASKAWA TM.iQp.06 iQpump Controller User ManualSoft Charge Resistor Check(R1, R2, 6PCB)The soft charge resistor w

Page 65 - U2 Fault Trace List

6.8 Main Circuit Test ProcedureYASKAWA TM.iQp.06 iQpump Controller User Manual 157Output Transistors(Q1-Q12)(Continued)11. Place the positive (red)

Page 66 - U3 Fault History List

6.9 Drive Date Stamp Information158 YASKAWA TM.iQp.06 iQpump Controller User Manual6.9 Drive Date Stamp InformationThis information is used to deter

Page 67 - Pump Quick Setup

YASKAWA TM.iQp.06 iQpump Controller User Manual 1597MaintenanceThis chapter describes basic maintenance and inspection of the iQpump drive. Please ref

Page 68 - 3.6 Programming Menu (-ADV-)

16 YASKAWA TM.iQp.06 iQpump Controller User Manual ◆ Conventions Used in this Manual Software VersionsYaskawa recognizes the need to continuously im

Page 69 - ◆ Auto-Tuning Menu (-A.TUNE-)

7.1 Periodic Inspection160 YASKAWA TM.iQp.06 iQpump Controller User Manual7.1 Periodic InspectionCheck the following items during periodic maintenan

Page 70 - 3.7 Parameter Editing Example

7.2 Preventive MaintenanceYASKAWA TM.iQp.06 iQpump Controller User Manual 1617.2 Preventive MaintenanceTable 7.3 Preventive MaintenanceIf the iQpum

Page 71 - Auto: Setpoint Ref

7.3 Heatsink Cooling Fan Replacement162 YASKAWA TM.iQp.06 iQpump Controller User Manual7.3 Heatsink Cooling Fan Replacement◆ Models CIMR-P7U20P4 thr

Page 72

7.3 Heatsink Cooling Fan ReplacementYASKAWA TM.iQp.06 iQpump Controller User Manual 163◆ Models CIMR-P7U2022 thru 2110 (30 HP to 150 HP @ 208 V / 2

Page 73 - Start-Up

7.4 Removing and Mounting the Terminal Card164 YASKAWA TM.iQp.06 iQpump Controller User Manual7.4 Removing and Mounting the Terminal CardThe termina

Page 74 - 4.1 Start-Up

YASKAWA TM.iQp.06 iQpump Controller User Manual 165Appendix: AParametersThis appendix lists all the parameter numbers and names, along with a descript

Page 75

166 YASKAWA TM.iQp.06 iQpump Controller User Manual Parameter ListTable 1 Parameter ListParameter No.Addr. HexParameter NameDigital Operator Display

Page 76

YASKAWA TM.iQp.06 iQpump Controller User Manual 167b2-02 018ADC Injection BrakingCurrentDCInj CurrentSelects the DC injection braking current as a p

Page 77 - Removing the Terminal Cover

168 YASKAWA TM.iQp.06 iQpump Controller User Manual b5-0701ABPI Offset AdjustmentPI OffsetSets the amount of offset of the output of the PI controll

Page 78 - Attaching the Terminal Cover

YASKAWA TM.iQp.06 iQpump Controller User Manual 169C1-09 0208Fast Stop TimeFast Stop TimeSets the time to decelerate from maximum frequency to zero

Page 79 - NOT USED

YASKAWATM.iQp.06 iQpump Controller User Manual 171Physical InstallationThis chapter describes the requirements for receiving and installing the iQpump

Page 80 - ◆ Step # 3 - Control Wiring

170 YASKAWA TM.iQp.06 iQpump Controller User Manual Preset Referenced1-010280Set-point Reference 1Set-point 1Digital preset setpoint reference 1. U

Page 81 - Figure 4.7 Digital Operator

YASKAWA TM.iQp.06 iQpump Controller User Manual 171E1-04 0303Maximum Output FrequencyMax FrequencyTo set V/f characteristics in a straight line, set

Page 82

172 YASKAWA TM.iQp.06 iQpump Controller User Manual F6-05 03A6Current Monitor Display Unit SelectionCurrent Unit Sel0: A Display1: 100 % / 8192 (Dri

Page 83 - Figure 4.11)

YASKAWA TM.iQp.06 iQpump Controller User Manual 173H1-04(continued on next page)0403Terminal S6 Function SelectionTerminal S6 Sel20: External Pump F

Page 84 - Figure 4.9

174 YASKAWA TM.iQp.06 iQpump Controller User Manual H1-04 040381: Disable Sleep ModeFunction Active in Auto Mode.Closed: Disables sleep function, Fee

Page 85 - HAND MODE OPERATION

YASKAWA TM.iQp.06 iQpump Controller User Manual 175Parameter No.Addr. HexParameter NameDigital Operator DisplayDescriptionSetting RangeFactory Setti

Page 86

176 YASKAWA TM.iQp.06 iQpump Controller User Manual H2-02(continued)040CTerminal M3-M4 Function SelectionTerm M3-M4 Sel42: Pump FaultFunction Active

Page 87 - Set System Setpoint

YASKAWA TM.iQp.06 iQpump Controller User Manual 177H2-02(continued)040CTerminal M3- M4 Function SelectionTerm M3-M4 Sel55: Lube Pump <0034> Cl

Page 88 - ◆ Simplex Pump Setup Complete

178 YASKAWA TM.iQp.06 iQpump Controller User Manual H4-02041ETerminal FM Gain SettingTerminal FM GainSets Terminal FM output voltage (in percent of

Page 89 - Basic Programming

YASKAWA TM.iQp.06 iQpump Controller User Manual 179H5-06 042ADrive Transmit Wait TimeTransmit WaitTimSets the time from when the drive receives data

Page 90 - ◆ A1 Initialization

1.1 iQpump Model Number and Enclosure Style18 YASKAWA TM.iQp.06 iQpump Controller User Manual1.1 iQpump Model Number and Enclosure StyleTable 1.1 i

Page 91 - ◆ b1 Sequence

180 YASKAWA TM.iQp.06 iQpump Controller User Manual Stall PreventionL3-01 048FStall Prevention Selection During AccelStallP Accel Sel0: Disabled (Mo

Page 92 - Potentiometer

YASKAWA TM.iQp.06 iQpump Controller User Manual 181 Torque DetectionL6-01 04A1Torque Detection Selection 1Load DetectionDetermines the drive's

Page 93 - A1 0 to +/- 10 Vdc, 20 kΩΩ*

182 YASKAWA TM.iQp.06 iQpump Controller User Manual L8-12 04B8Ambient Temperature SettingAmbient TempWhen the drive is installed in an ambient temper

Page 94

YASKAWA TM.iQp.06 iQpump Controller User Manual 183o1-07 0518Second Line User Monitor Selection2nd Monitor SelSets the “U1” monitor always displayed

Page 95 - Feedback Device

184 YASKAWA TM.iQp.06 iQpump Controller User Manual o3-02 0516Read Allowed Selection Read AllowableEnables and disables all digital operator copy fun

Page 96

YASKAWA TM.iQp.06 iQpump Controller User Manual 185P1-090608High Feedback LevelHigh FB LevelThe drive will display a “High Feedback Level (HFB)” al

Page 97 - Time BrakeInjection DC

186 YASKAWA TM.iQp.06 iQpump Controller User Manual P2-02060BSleep LevelSleep LevelSleep activates when selected level (P2-01) reaches programmed sl

Page 98 - ◆ b2 DC Braking

YASKAWA TM.iQp.06 iQpump Controller User Manual 187P2-15 010FNo-Flow Delta Feedback LevelNF FB LevelNo-flow feedback (PID-Error: setpoint minus feed

Page 99 - Figure 5.11

188 YASKAWA TM.iQp.06 iQpump Controller User Manual P3-020615Drive Multi / Maximum LevelMax-Multi LevelSets the maximum level used for multiplex pum

Page 100 - Pump Tuning

YASKAWA TM.iQp.06 iQpump Controller User Manual 189P3-09061CPump 2 Frequency Shutdown LevelP2 Freq Shd LvlSets the level used for multiplex pumping

Page 101 - PI Feedback

1.2 Confirmations Upon DeliveryYASKAWA TM.iQp.06 iQpump Controller User Manual 191.2 Confirmations Upon Delivery◆ Receiving ChecksCheck the followin

Page 102 - Setpoint

190 YASKAWA TM.iQp.06 iQpump Controller User Manual Pump AdvancedP4-010115Pre-charge LevelPre-charge LevelSets the level when the drive will run at

Page 103 - Setting Description

YASKAWA TM.iQp.06 iQpump Controller User Manual 191P4-08<0032>011CProtection Fault Auto Restart EnableProt Flt RestrtSetting to enable / disab

Page 104 - ◆ b8 Energy Savings

192 YASKAWA TM.iQp.06 iQpump Controller User Manual P4-21<0034> 834Low City Pressure Input SelectLow City In SelSelects the type of pressure swi

Page 105 - ◆ C1 Accel / Decel

YASKAWA TM.iQp.06 iQpump Controller User Manual 193P6-07<0034> 846Low Flow SelectLow Flow SelSets the behavior of the drive when a “Low Flow”

Page 106 - ◆ d3 Jump Frequencies

194 YASKAWA TM.iQp.06 iQpump Controller User Manual P7-08<0034> 856De-Scale Acceleration TimeDe-Scale AccelSets the amount of time it will tak

Page 107 - ◆ E1 V/f Pattern

YASKAWA TM.iQp.06 iQpump Controller User Manual 195P9-04<0034> 0883Alternation ModeAlternation ModeDetermines how alternation is performed:0:

Page 108 - E1-05 Maximum Output Voltage

196 YASKAWA TM.iQp.06 iQpump Controller User Manual P9-17<0034> 0890Setpoint ModifierSet-pt ModifierSystem Set-point is incremented with this

Page 109

YASKAWA TM.iQp.06 iQpump Controller User Manual 197Monitor ListTable 2 Monitor ListParameter No.Addr. HexParameter Name Digital Operator DisplayDes

Page 110 - E1-09 E1-07

198 YASKAWA TM.iQp.06 iQpump Controller User Manual U1-16 004FTerminal A2 Input Voltage Term A2 lev elDisplays the input current (or voltage) on Term

Page 111 - ◆ H3 Analog Inputs

YASKAWA TM.iQp.06 iQpump Controller User Manual 199U1-92 0722Pump StatusPump StatusDisplay pump running status.U1-93 723Total Set-point Compensation

Page 112

2 YASKAWA TM.iQp.06 iQpump Controller User Manual

Page 113 - DIP Switch S1-1 located on

1.2 Confirmations Upon Delivery20 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Drive Model NumbersThe model number on the nameplate indicates th

Page 114 - Setting: 0

200 YASKAWA TM.iQp.06 iQpump Controller User Manual Fault Trace ListTable 3 Fault Trace ListParameter No.Addr. HexFault TraceU2-01 0080Current Fault

Page 115 - (H3-09 = D) applied

YASKAWA TM.iQp.06 iQpump Controller User Manual 201Fault History ListTable 4 Fault History ListParameter No.Addr.HexFault HistoryU3-01 0090Most Rec

Page 116

202 YASKAWA TM.iQp.06 iQpump Controller User Manual Table 5 Decimal to Hex ConversionDecimal Hex Decimal Hex1 1 51 332 2 52 343 3 53 354 4 54 365 5

Page 117 - ◆ L5 Fault Restart

YASKAWA TM.iQp.06 iQpump Controller User Manual 203Appendix: BCapacity Related ParametersThis appendix lists the parameters affected by the Drive Cap

Page 118 - Figure 5.28

204 YASKAWA TM.iQp.06 iQpump Controller User Manual B.1 Drive CapacityB.1 Drive CapacityParameter o2-04 sets the iQpump drive capacity according to

Page 119 - ◆ L6 Torque Detection

B.2 Parameters Affected by o2-04YASKAWA TM.iQp.06 iQpump Controller User Manual 205B.2 Parameters Affected by o2-04The factory setting of the follow

Page 120 - ◆ L8 Hardware Protection

206 YASKAWA TM.iQp.06 iQpump Controller User Manual B.3 Capacity Related Parameter ValuesB.3 Capacity Related Parameter ValuesThe following tables d

Page 121

B.3 Capacity Related Parameter ValuesYASKAWA TM.iQp.06 iQpump Controller User Manual 207Table B.4 480 Vac iQpump DrivesDrive ModelCIMR-P7U-107Nomi

Page 122

208 YASKAWA TM.iQp.06 iQpump Controller User Manual B.3 Capacity Related Parameter ValuesCC arrier F requenc y P arameter F ac tory Defaults : 208V

Page 123 - ◆ o1 Monitor Configuration

YASKAWA TM.iQp.06 iQpump Controller User Manual 209Appendix: CSpecificationsThis appendix details the standard iQpump drive specifications. C.1 Stand

Page 124 - U1-03= 10.05A

1.3 Component NamesYASKAWA TM.iQp.06 iQpump Controller User Manual 211.3 Component Names◆ Models CIMR-P7U20P4 through 2018 (25 HP @ 208 V / 240 V)

Page 125 - ◆ o2 Key Selections

210 YASKAWA TM.iQp.06 iQpump Controller User Manual C.1 Standard iQpump Drive SpecificationsC.1 Standard iQpump Drive SpecificationsThe standard iQp

Page 126 - READ COMPLETE

C.1 Standard iQpump Drive SpecificationsYASKAWA TM.iQp.06 iQpump Controller User Manual 211◆ 480 VacTable C.2 480 Vac iQpump Drive SpecificationsTa

Page 127 - VERIFY ERROR

212 YASKAWA TM.iQp.06 iQpump Controller User Manual C.1 Standard iQpump Drive SpecificationsTable C.3 Common iQpump (P7U) Drive SpecificationsModel

Page 128 - 5.2 Pump Basic

YASKAWA TM.iQp.06 iQpump Controller User Manual 213Appendix: DCommunicationThis appendix details the specifications, connections, and programming of

Page 129 - Operation

214 YASKAWA TM.iQp.06 iQpump Controller User Manual D.1 Using Modbus CommunicationD.1 Using Modbus CommunicationSerial communication can be performe

Page 130 - 5.2 Pump Basic

D.1 Using Modbus CommunicationYASKAWA TM.iQp.06 iQpump Controller User Manual 215Figure D.2 Communication Connection Terminals and Terminating Resi

Page 131 - 5.3 Pump Protection

216 YASKAWA TM.iQp.06 iQpump Controller User Manual D.1 Using Modbus Communication Related ParametersTable D.2 Serial Communication Related Parame

Page 132 - Sleep Delay Time

D.1 Using Modbus CommunicationYASKAWA TM.iQp.06 iQpump Controller User Manual 217 Message FormatIn Modbus communication, the master sends commands

Page 133 - 5.3 Pump Protection

218 YASKAWA TM.iQp.06 iQpump Controller User Manual D.2 Modbus Function Code DetailsD.2 Modbus Function Code Details◆ Reading / Holding Register Con

Page 134

D.2 Modbus Function Code DetailsYASKAWA TM.iQp.06 iQpump Controller User Manual 219◆ Loopback Test (08H)The loopback test returns the command messag

Page 135 - 5.4 T1 Auto-Tuning

1.3 Component Names22 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Models CIMR-P7U2022 through 2110 (30 HP and above @ 208 V / 240 V) and 4030

Page 136 - THIS PAGE INTENTIONALLY BLANK

220 YASKAWA TM.iQp.06 iQpump Controller User Manual D.3 Modbus Data TablesD.3 Modbus Data TablesThe data tables are shown below. The types of data a

Page 137

D.3 Modbus Data TablesYASKAWA TM.iQp.06 iQpump Controller User Manual 221Monitor DataThe following table shows the monitor data. Monitor data can on

Page 138 - 6.1 Fault Detection

222 YASKAWA TM.iQp.06 iQpump Controller User Manual D.3 Modbus Data Tables002BSequence input statusBit 0 Input terminal S1 1: ON 0: OFFBit 1 Input t

Page 139 - 6.1 Fault Detection

D.3 Modbus Data TablesYASKAWA TM.iQp.06 iQpump Controller User Manual 223Broadcast DataThe following table shows the broadcast data. Broadcast data

Page 140

224 YASKAWA TM.iQp.06 iQpump Controller User Manual D.3 Modbus Data TablesError CodesThe following table shows Modbus communication error codes.Tabl

Page 141

D.4 Modbus Self-DiagnosisYASKAWA TM.iQp.06 iQpump Controller User Manual 225D.4 Modbus Self-DiagnosisThe iQpump drive has a built-in function for se

Page 142

226 YASKAWA TM.iQp.06 iQpump Controller User Manual D.4 Modbus Self-DiagnosisTHIS PAGE INTENTIONALLY BLANK.

Page 143 - 6.2 iQpump Keypad Messages

YASKAWA TM.iQp.06 iQpump Controller User Manual 227Appendix: EPeripheral DevicesThis appendix describes recommended branch short circuit protection a

Page 144 - 6.2 iQpump Keypad Messages

228 YASKAWA TM.iQp.06 iQpump Controller User Manual E.1 Branch Circuit Short Circuit ProtectionE.1 Branch Circuit Short Circuit ProtectionThe follow

Page 145 - <0032>

E.1 Branch Circuit Short Circuit ProtectionYASKAWA TM.iQp.06 iQpump Controller User Manual 229Table E.2 Recommended Fuse and Circuit Breaker Rating

Page 146 - 6.3 Alarm Detection

1.4 Exterior and Mounting DimensionsYASKAWA TM.iQp.06 iQpump Controller User Manual 231.4 Exterior and Mounting DimensionsDimensions: iQpump (P7U) (

Page 147

230 YASKAWA TM.iQp.06 iQpump Controller User Manual E.2 Branch Circuit Overload ProtectionTable E.4 Semiconductor Fuses for drive I2t Protection an

Page 148 - Appendix B

E.4 Third Party Serial Communication Converters RS232-RS485 / USB - RS485 ConvertersYASKAWA TM.iQp.06 iQpump Controller User Manual 231◆ AC and DC R

Page 149 - 6.5 Auto-Tuning Faults

232 YASKAWA TM.iQp.06 iQpump Controller User Manual E.4 Third Party Serial Communication Converters RS232-RS485 / USB - RS485 ConvertersIC485AI Modu

Page 150

E.5 SCADA Software for iQpump Drive (SW.iQp.01)YASKAWA TM.iQp.06 iQpump Controller User Manual 233Manufacturer: NudamModel: ND-6530Website: www.indu

Page 151 - 6.7 Troubleshooting

234 YASKAWA TM.iQp.06 iQpump Controller User Manual E.7 iQpump Drive Harmonics Estimator (SW.HE.04)THIS PAGE INTENTIONALLY BLANK

Page 152 - ◆ If the Motor Overheats

YASKAWA TM.iQp.06 iQpump Controller User Manual 235Appendix: FElectromagnetic CompatibilityThis section describes the measures necessary to comply wi

Page 153

236 YASKAWA TM.iQp.06 iQpump Controller User Manual F.1 Electromagnetic CompatibilityF.1 Electromagnetic Compatibility◆ IntroductionThis section des

Page 154

F.1 Electromagnetic CompatibilityYASKAWA TM.iQp.06 iQpump Controller User Manual 237Figure F.1 Grounding Surface LayoutThe grounding surfaces must

Page 155

238 YASKAWA TM.iQp.06 iQpump Controller User Manual F.1 Electromagnetic CompatibilityFigure F.2 EMC Filter LayoutMetal plateGroundingRemove varnish

Page 156

YASKAWA TM.iQp.06 iQpump Controller User Manual 239Appendix: GQuick Setup ProceduresThis appendix provides quick setup procedures or application exam

Page 157

1.4 Exterior and Mounting Dimensions24 YASKAWA TM.iQp.06 iQpump Controller User ManualDimensions: iQpump (P7U) (NEMA 1) 208 V / 240 V (88.0–115 AMPS

Page 158 - Example: July 22, 2000

240 YASKAWA TM.iQp.06 iQpump Controller User Manual G.2 Set-up Procedures Included in this AppendixG.2 Set-up Procedures Included in this AppendixThe

Page 159 - Maintenance

G.3 Well Draw Down FunctionYASKAWA TM.iQp.06 iQpump Controller User Manual 241G.3 Well Draw Down FunctionThe Well Draw Down function in parameter P8

Page 160 - 7.1 Periodic Inspection

242 YASKAWA TM.iQp.06 iQpump Controller User Manual G.3 Well Draw Down Function 3. Connect Level Transducer to the iQpump DriveMost depth level tra

Page 161 - 7.2 Preventive Maintenance

G.3 Well Draw Down FunctionYASKAWA TM.iQp.06 iQpump Controller User Manual 243Figure G.1 Figure G.3 Terminal Connections with Schematic 4. Connec

Page 162 - Connector

244 YASKAWA TM.iQp.06 iQpump Controller User Manual G.3 Well Draw Down Function 10. Set Wake-Up Level in Parameter P8-05When the water level reache

Page 163 - (40 HP to 500 HP @ 480 V)

G.4 Sleep/Sleep Boost FunctionYASKAWA TM.iQp.06 iQpump Controller User Manual 245G.4 Sleep/Sleep Boost FunctionThe following is a summary of a set-u

Page 164 - ◆ Mounting the Terminal Card

246 YASKAWA TM.iQp.06 iQpump Controller User Manual G.4 Sleep/Sleep Boost FunctionTable G.3 Related Parameters <0034>◆ TroubleshootingIf the

Page 165 - Appendix: A

G.5 Utility Delayed Start FunctionYASKAWA TM.iQp.06 iQpump Controller User Manual 247G.5 Utility Delayed Start FunctionThe following is a summary of

Page 166 - Parameter List

248 YASKAWA TM.iQp.06 iQpump Controller User Manual G.6 Start Level FunctionG.6 Start Level FunctionThe following is a summary of a set-up procedure

Page 167 - PI Control

G.6 Start Level FunctionYASKAWA TM.iQp.06 iQpump Controller User Manual 249P1-04 can be programmed using a negative (-) psi value that will represen

Page 168 - Accel/Decel

1.4 Exterior and Mounting DimensionsYASKAWA TM.iQp.06 iQpump Controller User Manual 25Dimensions: iQpump (P7U) (Protected Chassis) 208–230 V (162–41

Page 169 - Carrier Frequency

250 YASKAWA TM.iQp.06 iQpump Controller User Manual G.7 Low City Pressure or Low Suction Inlet PressureG.7 Low City Pressure or Low Suction Inlet Pr

Page 170 - V/f Pattern

G.8 Lube Pump Digital Output for Deep Well IrrigationYASKAWA TM.iQp.06 iQpump Controller User Manual 251G.8 Lube Pump Digital Output for Deep Well I

Page 171 - Communication Option Setup

252 YASKAWA TM.iQp.06 iQpump Controller User Manual G.9 iQpump Software Multiplexing Set-upG.9 iQpump Software Multiplexing Set-upThe following is a

Page 172 - Digital Inputs

G.9 iQpump Software Multiplexing Set-upYASKAWA TM.iQp.06 iQpump Controller User Manual 2532. Use shielded communication cable for steps 3 and 4 to c

Page 173 - <0034>

254 YASKAWA TM.iQp.06 iQpump Controller User Manual G.9 iQpump Software Multiplexing Set-upAn iQpump drive displays U1-67 = 0 <->:•Check physi

Page 174

G.9 iQpump Software Multiplexing Set-upYASKAWA TM.iQp.06 iQpump Controller User Manual 255◆ Multiplex Status DisplayFigure G.12 Figure G.14 Multip

Page 175 - Digital Outputs

256 YASKAWA TM.iQp.06 iQpump Controller User Manual G.9 iQpump Software Multiplexing Set-up◆ MEMOBUS Networking Quick Start GuideTable G.8 Related

Page 176

G.9 iQpump Software Multiplexing Set-upYASKAWA TM.iQp.06 iQpump Controller User Manual 257P9-13088CRemove Freq LevelRemove Freq LvlWhen P9-12 = 0 a

Page 177 - Analog Outputs

258 YASKAWA TM.iQp.06 iQpump Controller User Manual G.9 iQpump Software Multiplexing Set-up◆ Application Examples Simple Duplex SystemA customer re

Page 178 - Serial Communication Setup

G.9 iQpump Software Multiplexing Set-upYASKAWA TM.iQp.06 iQpump Controller User Manual 259 Duplex System with Fine TuningThe customer would like to

Page 179 - Power Loss Ridethru

1.4 Exterior and Mounting Dimensions26 YASKAWA TM.iQp.06 iQpump Controller User ManualDimensions: iQpump (P7U) (Protected Chassis)Figure 1.11 Exter

Page 180 - Fault Restart

260 YASKAWA TM.iQp.06 iQpump Controller User Manual G.9 iQpump Software Multiplexing Set-up Duplex System with Jockey PumpA customer requires a pum

Page 181 - Hardware Protection

G.9 iQpump Software Multiplexing Set-upYASKAWA TM.iQp.06 iQpump Controller User Manual 261 Triplex SystemA customer who currently runs a duplex sys

Page 182 - Monitor Select

262 YASKAWA TM.iQp.06 iQpump Controller User Manual G.10 First In First Out (FIFO) DescriptionG.10 First In First Out (FIFO) Description The followi

Page 183 - Copy Function

G.11 Anti-No Flow Simplified SetupYASKAWA TM.iQp.06 iQpump Controller User Manual 263G.11 Anti-No Flow Simplified Setup◆ Sleep and Anti-No-Flow Dete

Page 184 - Pump Basic

264 YASKAWA TM.iQp.06 iQpump Controller User Manual G.11 Anti-No Flow Simplified SetupTHIS PAGE INTENTIONALLY BLANK

Page 186

YASKAWA TM.iQp.02 iQpump Drive Programming Manual iQpump Controller Data subject to change without notice. Yaskawa Electric America, Inc.YEA

Page 187 - Pump Multiplex

1.5 Heat Loss DataYASKAWA TM.iQp.06 iQpump Controller User Manual 271.5 Heat Loss DataTable 1.3 200V Class Heat Loss DataTable 1.4 400V Class Heat

Page 188

1.6 Checking and Controlling the Installation Site28 YASKAWA TM.iQp.06 iQpump Controller User Manual1.6 Checking and Controlling the Installation Si

Page 189

1.7 Installation Orientation and ClearancesYASKAWA TM.iQp.06 iQpump Controller User Manual 291.7 Installation Orientation and ClearancesInstall the

Page 190 - Pump Advanced

YASKAWA TM.iQp.06 iQpump Controller User Manual 3iQpump Software ChangesTable 1.1 Modified iQpump Default Settings Miscellaneous Items:• In the pre

Page 191

1.8 Removing and Attaching the Terminal Cover30 YASKAWA TM.iQp.06 iQpump Controller User Manual1.8 Removing and Attaching the Terminal CoverRemove t

Page 192 - Flow Meter Setup

1.9 Removing/Attaching the Digital Operator and Front CoverYASKAWA TM.iQp.06 iQpump Controller User Manual 311.9 Removing/Attaching the Digital Oper

Page 193 - Anti-Jam/De-Scale

1.9 Removing/Attaching the Digital Operator and Front Cover32 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Models CIMR-P7U2022 through 2110 (30

Page 194 - Network Options

1.9 Removing/Attaching the Digital Operator and Front CoverYASKAWA TM.iQp.06 iQpump Controller User Manual 33IMPORTANT• Do not remove or attach the

Page 195

1.9 Removing/Attaching the Digital Operator and Front Cover34 YASKAWA TM.iQp.06 iQpump Controller User ManualTHIS PAGE INTENTIONALLY BLANK.

Page 196 - Auto-Tuning

YASKAWA TM.iQp.06 iQpump Controller User Manual 352Electrical InstallationThis chapter describes wiring terminals, main circuit terminal connections,

Page 197 - Monitor List

2.1 Terminal Block Configuration36 YASKAWA TM.iQp.06 iQpump Controller User Manual2.1 Terminal Block ConfigurationThe wiring terminals are shown in

Page 198

2.2 Wiring Main Circuit TerminalsYASKAWA TM.iQp.06 iQpump Controller User Manual 372.2 Wiring Main Circuit Terminals◆ Applicable Wire Sizes and Clos

Page 199 - Not used. Always 0

2.2 Wiring Main Circuit Terminals38 YASKAWA TM.iQp.06 iQpump Controller User Manual2037 50R/L1, S/L2, T/L3, , 1 U/T1, V/T2, W/T3, R1/L11, S1/L21,

Page 200 - Fault Trace List

2.2 Wiring Main Circuit TerminalsYASKAWA TM.iQp.06 iQpump Controller User Manual 39Table 2.2 480 Vac Wire Sizes and Connector SpecificationsDrive M

Page 201 - Fault History List

4 YASKAWA TM.iQp.06 iQpump Controller User ManualTable 1.2 Pump Quick SetupOriginal Quick Start MenuPRG: 0033(VSP130033 and below)New Quick Start

Page 202

2.2 Wiring Main Circuit Terminals40 YASKAWA TM.iQp.06 iQpump Controller User Manual4055 100R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/T3, R1/L11, S1/L21

Page 203 - Appendix: B

2.2 Wiring Main Circuit TerminalsYASKAWA TM.iQp.06 iQpump Controller User Manual 414185 300 / 350R/L1, S/L2, T/L3, , 1 M888.5(10.0)300 X 2P(152 X

Page 204 - B.1 Drive Capacity

2.2 Wiring Main Circuit Terminals42 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Main Circuit Terminal FunctionsMain circuit terminal functions

Page 205

2.2 Wiring Main Circuit TerminalsYASKAWA TM.iQp.06 iQpump Controller User Manual 43◆ Main Circuit Configurations 208-240 Vac The 208-240 Vac main ci

Page 206

2.2 Wiring Main Circuit Terminals44 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Main Circuit Configurations 480 VacThe 480 Vac main circuit con

Page 207

2.2 Wiring Main Circuit TerminalsYASKAWA TM.iQp.06 iQpump Controller User Manual 45 Cable Length Between iQpump Drive and MotorThe iQpump drive sho

Page 208

2.3 Control Wiring46 YASKAWA TM.iQp.06 iQpump Controller User Manual2.3 Control Wiring◆ Control Circuit Wire SizesThe auto mode setpoint (speed comm

Page 209 - Appendix: C

2.3 Control WiringYASKAWA TM.iQp.06 iQpump Controller User Manual 47 Wiring ChecksAfter all wiring is completed, perform the following checks: 1. I

Page 210 - ◆ 208-240 Vac

2.3 Control Wiring48 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ DIP Switch S1 DIP Switch S1 is described in this section. The functions of DIP

Page 211 - ◆ 480 Vac

2.3 Control WiringYASKAWA TM.iQp.06 iQpump Controller User Manual 49◆ Shunt Connector CN15The shunt connector CN15 is described in this section. The

Page 212

YASKAWA TM.iQp.06 iQpump Controller User Manual 5P4-03Pre-charge TimePre-charge TimeREMOVED FROM QUICK START MENUP4-04Thrust Bearing Acceleration Tim

Page 213 - Appendix: D

2.3 Control Wiring50 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Sinking/Sourcing ModeThe input terminal logic can be switched between sinking

Page 214

2.3 Control WiringYASKAWA TM.iQp.06 iQpump Controller User Manual 51◆ Control Circuit Terminal Connections iQpump Drive Factory DefaultConnections

Page 215 - Figure D.3 below

2.3 Control Wiring52 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Control Circuit Wiring PrecautionsObserve the following precautions when wirin

Page 216 - Related Parameters

2.3 Control WiringYASKAWA TM.iQp.06 iQpump Controller User Manual 53 Duplex Pump System WiringConnections to the Multi-function Digital Outputs for

Page 217 - Error Check

2.3 Control Wiring54 YASKAWA TM.iQp.06 iQpump Controller User Manual Duplex Pump System with Motor Starter WiringConnections to the Multi-function

Page 218

2.3 Control WiringYASKAWA TM.iQp.06 iQpump Controller User Manual 55 Feedback Device (3-Wire)Connection of a 3-Wire 0 ~ 10 Vdc Feedback Device (H3-

Page 219 - ◆ Loopback Test (08H)

2.3 Control Wiring56 YASKAWA TM.iQp.06 iQpump Controller User ManualTHIS PAGE INTENTIONALLY BLANK.

Page 220 - D.3 Modbus Data Tables

YASKAWA TM.iQp.06 iQpump Controller User Manual 573Digital OperatorThis chapter describes the displays and functions of the Digital Operator.3.1 Digit

Page 221 - Monitor Data

3.1 Digital Operator Display58 YASKAWA TM.iQp.06 iQpump Controller User Manual3.1 Digital Operator DisplayThe digital operator is used for programmi

Page 222 - D.3 Modbus Data Tables

3.2 Digital Operator KeysYASKAWA TM.iQp.06 iQpump Controller User Manual 593.2 Digital Operator KeysThe names and functions of the digital operator

Page 223 - Enter Command

6 YASKAWA TM.iQp.06 iQpump Controller User ManualTHIS PAGE INTENTIONALLY BLANK.

Page 224 - Slave Not Responding

3.3 Drive Mode Indicators60 YASKAWA TM.iQp.06 iQpump Controller User Manual3.3 Drive Mode IndicatorsThe definitions of the iQpump drive mode indicat

Page 225 - D.4 Modbus Self-Diagnosis

3.3 Drive Mode IndicatorsYASKAWA TM.iQp.06 iQpump Controller User Manual 61◆ Stop IndicatorThe status of the “STOP” indicator is shown in Table 3.6

Page 226 - D.4 Modbus Self-Diagnosis

3.4 Drive Main Menu62 YASKAWA TM.iQp.06 iQpump Controller User Manual3.4 Drive Main MenuThe iQpump drive’s parameters and monitoring functions are o

Page 227 - Appendix: E

3.4 Drive Main MenuYASKAWA TM.iQp.06 iQpump Controller User Manual 63◆ Pump Quick Setup Main Menu StructureThe menu selection display will appear wh

Page 228

3.4 Drive Main Menu64 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Operation Menu (-DRIVE-) This menu is used for setting a speed command or mon

Page 229

3.4 Drive Main MenuYASKAWA TM.iQp.06 iQpump Controller User Manual 65 U2 Fault Trace ListAfter viewing the “Monitor” parameter list, in order to vi

Page 230 - E.3 Peripheral Devices

3.4 Drive Main Menu66 YASKAWA TM.iQp.06 iQpump Controller User Manual U3 Fault History ListAfter viewing the “Fault Trace” parameter list, in order

Page 231 - ◆ Noise filter

3.5 Pump Quick Setup Menu (-QUICK-) HYASKAWA TM.iQp.06 iQpump Controller User Manual 673.5 Pump Quick Setup Menu (-QUICK-) H This menu is used to

Page 232

3.6 Programming Menu (-ADV-)68 YASKAWA TM.iQp.06 iQpump Controller User Manual3.6 Programming Menu (-ADV-) This menu is used to set / read every par

Page 233 - Calculation Sotware

3.6 Programming Menu (-ADV-)YASKAWA TM.iQp.06 iQpump Controller User Manual 69◆ Auto-Tuning Menu (-A.TUNE-)This menu is used to auto-tune the iQpump

Page 234

YASKAWA TM.iQp.06 iQpump Controller User Manual 7◆ Quick Reference for iQpump (P7U) <0034>Parameter NumberFactory SettingUser SettingParameter

Page 235 - Appendix: F

3.7 Parameter Editing Example70 YASKAWA TM.iQp.06 iQpump Controller User Manual3.7 Parameter Editing ExampleTable 3.14 provides an example of how to

Page 236 - ◆ Recommended EMC Filters

3.7 Parameter Editing ExampleYASKAWA TM.iQp.06 iQpump Controller User Manual 7111 Press the SHIFT/RESET key to move the flashing digit to the right.

Page 237 - Ground clip Ground plate

3.7 Parameter Editing Example72 YASKAWA TM.iQp.06 iQpump Controller User ManualTHIS PAGE INTENTIONALLY BLANK.

Page 238 - Figure F.2 EMC Filter Layout

YASKAWA TM.iQp.06 iQpump Controller User Manual 734Start-UpThis chapter describes the procedures to prepare the iQpump drive for start up and the proc

Page 239 - Appendix: G

4.1 Start-Up74 YASKAWA TM.iQp.06 iQpump Controller User Manual4.1 Start-UpIn order to provide the most reliable iQpump drive available and to avoid

Page 240

4.1 Start-UpYASKAWA TM.iQp.06 iQpump Controller User Manual 75 9. Never allow wire leads to touch metal surfaces. Short-circuit may result. 10. Ne

Page 241 - G.3 Well Draw Down Function

4.1 Start-Up76 YASKAWA TM.iQp.06 iQpump Controller User ManualTHIS COMPLETES THE iQpump DRIVE START UP PREPARATION.  25. Wire all necessary control

Page 242 - Figure G.3

4.2 iQpump Drive Quick Start-Up ProceduresYASKAWA TM.iQp.06 iQpump Controller User Manual 774.2 iQpump Drive Quick Start-Up ProceduresThe following

Page 243 - Figure G.1

4.2 iQpump Drive Quick Start-Up Procedures78 YASKAWA TM.iQp.06 iQpump Controller User ManualCover Removal for Models CIMR-P7U2022 through 2110 (30 H

Page 244 - Parameter P8-09

4.2 iQpump Drive Quick Start-Up ProceduresYASKAWA TM.iQp.06 iQpump Controller User Manual 79Figure 4.3 Input Power and Output Motor Electrical Conn

Page 245 - TRANSDUCER

8 YASKAWA TM.iQp.06 iQpump Controller User Manual* Factory Setting changes to “B” when b5-01 = 1.** Factory Setting changes to “B” when b5-01 = 1 as

Page 246 - ◆ Troubleshooting

4.2 iQpump Drive Quick Start-Up Procedures80 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Step # 3 - Control WiringThis step shows how to connec

Page 247 - ◆ Related Parameters

4.2 iQpump Drive Quick Start-Up ProceduresYASKAWA TM.iQp.06 iQpump Controller User Manual 81◆ Step # 4 - Pump Quick Set-upIn this step, the iQpump d

Page 248 - G.6 Start Level Function

4.2 iQpump Drive Quick Start-Up Procedures82 YASKAWA TM.iQp.06 iQpump Controller User Manual◆ Step # 5 - iQpump Drive Quick Setup Parameter Overview

Page 249 - Negative Sign

4.2 iQpump Drive Quick Start-Up ProceduresYASKAWA TM.iQp.06 iQpump Controller User Manual 83Figure 4.8 b5-14 2.0 sPI Feedback Loss Detection TimeDe

Page 250 - ◆ Required Parameter Changes

4.2 iQpump Drive Quick Start-Up Procedures84 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 4.9 START LEVELStart Pump SystemStartDelay200 PS

Page 251

4.2 iQpump Drive Quick Start-Up ProceduresYASKAWA TM.iQp.06 iQpump Controller User Manual 85Figure 4.10 Figure 4.11 HAND MODE OPERATION4Hand Mode

Page 252 - R+ S+R- S

4.2 iQpump Drive Quick Start-Up Procedures86 YASKAWA TM.iQp.06 iQpump Controller User Manual Auto Operation - Power Down StorageAllows iQpump to au

Page 253 - P1-01 = 3 P1-01 = 3 P1-01 = 3

4.2 iQpump Drive Quick Start-Up ProceduresYASKAWA TM.iQp.06 iQpump Controller User Manual 87 Feedback Signal CheckVerify the feedback signal level

Page 254 - ◆ iQpump Drive Run Order

4.2 iQpump Drive Quick Start-Up Procedures88 YASKAWA TM.iQp.06 iQpump Controller User ManualiQpump automatically starts in Auto Mode when the feedba

Page 255 - ◆ PI Feedback via Network

YASKAWA TM.iQp.06 iQpump Controller User Manual 895Basic ProgrammingThis Manual contains descriptions of all user accessible parameters contained in t

Page 256 - Table G.8 Related Parameters

YASKAWA TM.iQp.06 iQpump Controller User Manual

Page 257

5.1 iQpump Drive Basic Programming Parameters90 YASKAWA TM.iQp.06 iQpump Controller User Manual5.1 iQpump Drive Basic Programming ParametersThe init

Page 258 - ◆ Application Examples

5.1 iQpump Drive Basic Programming ParametersYASKAWA TM.iQp.06 iQpump Controller User Manual 91Important: Some parameters are unaffected by either t

Page 259 - Description Drive A Drive B

5.1 iQpump Drive Basic Programming Parameters92 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 5.2 Figure 5.2 Digital Operator Auto Setpoin

Page 260 - Figure G.14

5.1 iQpump Drive Basic Programming ParametersYASKAWA TM.iQp.06 iQpump Controller User Manual 93Figure 5. 3 Figure 5.4 External Analog Signal Setpo

Page 261 - Triplex System

5.1 iQpump Drive Basic Programming Parameters94 YASKAWA TM.iQp.06 iQpump Controller User ManualImportant: If b1-01 = “3: Option PCB” but a network c

Page 262 - Definitions

5.1 iQpump Drive Basic Programming ParametersYASKAWA TM.iQp.06 iQpump Controller User Manual 953. Initiate a Start / Stop commandiQpump command regi

Page 263

5.1 iQpump Drive Basic Programming Parameters96 YASKAWA TM.iQp.06 iQpump Controller User Manualdrive. When the Forward / Reverse input is open the i

Page 264

5.1 iQpump Drive Basic Programming ParametersYASKAWA TM.iQp.06 iQpump Controller User Manual 97Figure 5. 7 Figure 5.9 Deceleration to StopThe actu

Page 265

5.1 iQpump Drive Basic Programming Parameters98 YASKAWA TM.iQp.06 iQpump Controller User ManualFigure 5.11 DC Injection Braking to StopImportant: I

Page 266

5.1 iQpump Drive Basic Programming ParametersYASKAWA TM.iQp.06 iQpump Controller User Manual 99Figure 5.10 Figure 5.13 DC Injection Braking During