Yaskawa SI-EN3D User Manual

Browse online or download User Manual for Equipment Yaskawa SI-EN3D. Yaskawa SI-EN3D User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - EtherNet/IP

EtherNet/IPYASKAWA AC Drive 1000-Series OptionTechnical ManualMANUAL NO. SIEP YAICOM 16ATo properly use the product, read this manual thoroughly and

Page 2

uOption LED DisplayThe option has four LEDs.Bi-color Status LEDs:• Module status (MS) red/green• Network status (NS) red/greenEthernet LEDs:• Network

Page 3 - Table of Contents

5 Installation ProcedureuSection Safety DANGERElectrical Shock HazardDo not connect or disconnect wiring while the power is on.Failure to comply will

Page 4 - 1 Preface and Safety

NOTICEProperly connect all pins and connectors.Failure to comply may prevent proper operation and possibly damage equipment.Check wiring to ensure tha

Page 5 - General Safety

uInstalling the OptionRemove the front covers of the drive before installing the option. Refer to the drive Quick Start Guide for directions onremovin

Page 6

NS MSKLFMTX RXFigure 5 Insert the Option4.Connect the ground wire (I) to the ground terminal (K) using one of the remaining provided screw

Page 7 - 2 Product Overview

ABA – Route wires through the openingsprovided on the left side of the frontcover. <1>B – Use the open space providedinside the drive to route

Page 8 - 3 Receiving

DriveMU/T1V/T2W/T3R/L1S/L2T/L3SI-EN3DEtherNet/IP OptionFE<1>EtherNet/IP CableMotorPowerEtherNet/IP CableFigure 9 Option Connection Diagram7.Use

Page 9 - 1 2 3 4 5 6 7 8

6 Related Drive ParametersThe following parameters are used to set up the drive for operation with the option. Parameter setting instructions can be f

Page 10 - Option LED Display

No.(Addr.Hex)Name Description ValuesF7-09(03ED)Gateway Address 1 Sets the most significant octet of network Gateway address.Default: 192Range: 0 to 25

Page 11 - 5 Installation Procedure

<3> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines whether the value is read as theTorqu

Page 12

Copyright © 2014 YASKAWA AMERICA, INC. All rights reserved.No part of this publication may be reproduced, stored in a retrieval system, or transmitte

Page 13 - Installing the Option

7 Configuring MessagingThis section provides information on methods used to control the drive with the option installed.uDrive Polled ConfigurationThe

Page 14

8 Output Assemblies (Drive Consumes)Note: The convention in this manual is from the PLC perspective. As such, an assembly is called an “Output Assembl

Page 15

uSpeed and Torque Control Output - 22 (0x16)Output Instance Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 02200 – – – – – Fault Reset – Run

Page 16 - EDS Files

Name DescriptionTorque Reference/TorqueLimitTorque Reference/Torque LimitSets the Torque Reference/Torque Limit in units of 0.1%.Sets the Torque Refer

Page 17 - 6 Related Drive Parameters

Name DescriptionMulti-Function Input 4Terminal S4 Function Input0: Terminal S4 Function (H1-04) OFF1: Terminal S4 Function (H1-04) ONMulti-Function In

Page 18

uExtended Speed/Torque Control Output (Vendor Specific Yaskawa Electric (YE) Assy)- 115 (0x73)Output Instance Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3

Page 19

Name DescriptionMulti-FunctionPhotocoupler 1Terminal P10: P1 OFF1: P1 ONThis function is enabled only when H2-02 is set to F.Multi-FunctionPhotocouple

Page 20 - 7 Configuring Messaging

Output Instance Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0116714 Analog Output 2 (Low Byte)15 Analog Output 2 (High Byte)816 Digital Ou

Page 21

Name DescriptionExternal FaultExternal Fault EF00: No External Fault (EF0)1: External Fault (EF0)Fault ResetFault Reset0: No Fault Reset1: Fault Reset

Page 22

9 Input Assemblies (Drive Produces)Note: The convention in this manual is from the PLC perspective. An “Input Assembly” is outputted from this node an

Page 23 - 100 (0x64)

Table of Contents1 PREFACE AND SAFETY...42 PRODUCT OVERVIEW...

Page 24

Name DescriptionDrive State Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.Speed ActualActual Drive SpeedMonitors

Page 25 - - 115 (0x73)

Name DescriptionRunning 2 (REV)Reverse Running0: Stop or Forward Running1: Reverse RunningReadyDrive Ready0: Not Ready1: ReadyCtrl from NetStatus of R

Page 26

Error Code Description0x22Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done.Writing

Page 27

Name DescriptionMulti-Function DigitalOutputTerminal M1/M20: M1/M2 OFF1: M1/M2 ONThis function is enabled only when H2-01 is set to F.Multi-FunctionPh

Page 28

Output Instance Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 01551020 <1>Parameter F7-33Default: Alarm Code (Low Byte)21 <1>Par

Page 29

Name DescriptionMulti-Function DigitalOutputTerminal M1/M20: M1/M2 OFF1: M1/M2 ONThis function is enabled only when H2-01 is set to F.Multi-FunctionPh

Page 30

uHigh Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 166(0xA6)If an error occurs while trying to read from the dynamic param

Page 31

Output Instance Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 01661122 <1>Parameter F7-34Default: Output Power (Low Byte)23 <1>P

Page 32

Name DescriptionFault ResetFault Reset command from Network0: Fault Reset command is not from network1: Fault Reset command is from networkSpeed Agree

Page 33 - 155 (0x9B)

Name DescriptionF7-38 PG Count Value(CH 2)Programmable: MEMOBUS/Modbus (0xF1)Serial interface Control ResponseF7-39 NetRef (Status)Status of reference

Page 34

1 Preface and SafetyYaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection andapplicati

Page 35

10 General Class ObjectsuIdentity Object 1 (Class 0x01)nServices SupportedService Code No. (Hex) Service Name01 Get Attribute All05 Reset0E Get Attrib

Page 36 - <1>

InstanceIDAttribute Name Description Get Set Size Range Default23 3 DataSame function as the Extended Speedand Torque Control(Output Assembly)O O Arra

Page 37

nAttributes SupportedInstanceIDAttribute Name Description Get Set Size Range Default0 1Object SoftwareRevisionMotor Data Object software revision. O –

Page 38

InstanceIDAttribute Name Description Get Set Size Range Default1 11 WarningWarning0: No Warning1: WarningO – Byte – 01 12 Fault ResetFault Reset0: No

Page 39

Drive Fault Code (Hex)(MEMOBUS/Modbus 0080 Hex)Option Fault Code (Hex) Description29 5210 Motor Overheat 1 (PTC Input) (oH3)30 5300 Operator Disconnec

Page 40 - 10 General Class Objects

InstanceIDAttribute Name Description Get Set Size Range Default1 6 Drive ModeDrive control mode.0: OLV, OLV for PM (Read only),Advanced OLV for PM (Re

Page 41 - Services Supported

InstanceIDAttribute Name Description Get Set Size Range Default1 27Voltage Scale(-15 to 15)Setting for F7-21, scale of units forvoltage related data.O

Page 42 - Attributes Supported

InstanceIDAttribute Name Description Get Set Size Range Default1 10ActiveSupervisorAddressStruct of:Supervisor IP Address = LongSupervisor MAC Address

Page 43

InstanceIDAttribute Name Description Get Set Size Range Default1 2ConfigurationCapabilityBit 0 = BOOTP ClientBit 1 = DNS ClientBit 2 = DHCP ClientBit

Page 44

InstanceIDAttribute Name Description Get Set Size Range Default1 2 Interface FlagsBit 0 = Link StatusBit 1 = Duplex (0: Half/1: Full)Bits 2-4 = Negoti

Page 45

WARNINGIndicates a hazardous situation, which, if not avoided, could result in death or serious injury.WARNING! may also be indicated by a bold key w

Page 46 - DLR Object 71 (Class 0x47)

11 Vendor-Specific (Yaskawa) Class ObjectsuYaskawa Drive Parameters Object 100 (Class 0x64)nServices SupportedService Code No. (Hex) Service Name0E Ge

Page 47 - QoS Object 72 (Class 0x48)

InstanceIDAttribute Name Description Get Set Size Range Default... ... ... ... ... O Word – –255 YYMEMOBUS/ModbusRegisters0xFF00 to0xFFFFMEMOBUS/Modbu

Page 48

12 Web InterfaceThe option contains a series of web pages that allow for viewing of status and diagnostic information through a standard webbrowser.Th

Page 49

uHTML Home PageThe HTML home page provides basic drive and option data and a link to an enhanced web page.VST800340CIMR-AU2A0004Figure 11 HTML Home Pa

Page 50 - Storing Changed Parameters

uDrive Status TabThe Drive Status tab shows basic I/O information and drive state information.Figure 13 Drive Status Tab ViewuNetwork TabThe Network t

Page 51

Network Monitor ExplanationCurrent Connections Current number of open connections.Control Connection DeltaTimeThe time between the last two writes to

Page 52 - 12 Web Interface

uParameter Access TabThe Parameter Access tab allows the user to read and write parameters from the drive. Write access is restricted until a validpas

Page 53 - CIMR-AU2A0004

uConfiguration TabThe Configuration tab sets web page behavior parameters. Access is restricted unless a valid password is entered.Figure 17 Configura

Page 54 - Network Tab

nGeneral SettingsClick “Save Options Card Parameters” to save the Applet Refresh Rate and the Parameter Security settings to the option.uCustom TabThe

Page 55 - Conditional Email Set-up

13 TroubleshootinguDrive-Side Error CodesDrive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are

Page 56 - Parameter Access Tab

NOTICEDo not expose the drive to halogen group disinfectants.Failure to comply may cause damage to the electrical components in the drive.Do not pack

Page 57 - Configuration Tab

Digital Operator Display Fault Name to oFA03 to oFA06Option Card Error Occurred at Option Port CN5-A, oFA10, oFA11 to oFA12 to oFA17 Option Card Conne

Page 58 - Custom Tab

nMinor Faults and AlarmsDigital Operator Display Minor Fault NameCALLSerial Communication Transmission ErrorCommunication has not yet been established

Page 59 - 13 Troubleshooting

ErrorCode(Hex)Description Cause Possible Solution20 Invalid parameterAttempted to change to a data value outside the settingrange.Specify a data value

Page 60

14 SpecificationsTable 17 Option SpecificationsItem SpecificationModel SI-EN3DSupported MessagesExplicit: Explicit Class 3, UnconnectedI/O: Class 1, L

Page 61 - Minor Faults and Alarms

14 SpecificationsThis Page Intentionally Blank64YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual

Page 62 - Option Compatibility

This Page Intentionally BlankYASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual65

Page 63 - 14 Specifications

Revision HistoryThe revision dates and the numbers of the revised manuals appear on the bottom of the back cover.MANUAL NO.Example: SIEP YAICOM 16Publ

Page 65

YASKAWA AMERICA, INC.2121 Norman Drive South, Waukegan, IL 60085, U.S.A.Phone: 1-800-YASKAWA (927-5292) or 1-847-887-7000 Fax: 1-847-887-7310http://

Page 66 - Revision History

2 Product OverviewuAbout this ProductThe option provides a communications connection between the drive and an ODVA EtherNet/IP network. The option con

Page 67

3 ReceivingPlease perform the following tasks upon receipt of the option:• Inspect the option for damage. Contact the shipper immediately if the optio

Page 68

4 Option ComponentsuSI-EN3D Dual-Port EtherNet/IP OptionMAIHGEBDFCJKLUndersideA – Ground terminal and installationhole <1>B –Port 2 LED (10/100)