Yaskawa JVOP-180 LCD User Manual Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
54 YASKAWA ELECTRIC TOBP C730600 29G 1000-Series Option JVOP-180 Installation Manual
8 Option Fault Diagnostics
8 Option Fault Diagnostics
Error Code and Connection Messages
Fault/Error code text will appear on the option display to indicate a specific fault. The fault
codes in Table 14 are displayed on the LED operator and/or the option displays. For
information on the fault codes not listed in Table 14, refer to the unit manual.
When an option fault occurs, ensure that the communication cable is properly connected to
the option and it is not loose.
Contact your nearest Yaskawa representative or sales department if the cable appears to be
connect properly but still no message appears to indicate the error.
Note: If A1000, D1000, or R1000 is used, the fault codes are displayed on the option only.
Table 14 Fault/Error Code Displays
LCD Operator
LED Operator
(V1000)
Description
<1>
Option is connected
This is not an error message.
. . . . .
This is not an error message. Occurs when the option is connected
to the unit.
LCD Operator
LED Operator
(V1000)
Description
CPF00
COM-ERR (OP&INV)
<1>
LCD Operator Option Communication Error 1
Occurs when the unit cannot communicate with the option within
5 seconds after the power is switched on.
Cause Possible Solution
Communication cable between the option and
the unit is not properly connected.
Remove and reconnect the option.
Problem with the option. Replace the option.
Problem with the control circuit in the unit.
Cycle power to the unit.
Replace the unit.
LCD Operator
LED Operator
(V1000)
Description
CPF01
COM-ERR (OP&INV)
<1>
LCD Operator Option Communication Error 2
Occurs when the unit does not respond to the option for longer
than 2 seconds.
Cause Possible Solution
Connector on the option cable is loose or
damaged.
Remove and reconnect the option.
Problem with the option. Replace the option.
Problem with the control circuit in the unit.
Cycle power to the unit.
Replace the unit.
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58

Comments to this Manuals

No comments