2. With 400-V Inverters, the values for the upper limit of setting ranges and
the default settings will be twice those given in the above table.
Set the rated motor input frequency to the maximum voltage frequency
(FMAX) while the rated motor input voltage is set to the maximum output
voltage (VMAX).
The vertical-axis load or the load with high viscous friction may require
high torque at low speed. If the torque is insufficient at low speed,
increase the voltage in the low-speed range by 1 V, provided that no
overload (OL1 or OL2) is detected. If an overload is detected, decrease
the set values or consider the use of an Inverter model with a higher
capacity.
The required torque of fan or pump control increases in proportion to the
square of the speed. By setting a quadratic V/f pattern to increase the
voltage in the low-speed range, the power consumption of the system will
increase.
Frequency (Hz)
Output voltage
(V)
n10(VMAX)
n13(VC)
n15(VMIN)
0 n14
(FMIN
n12
(FB)
n11
(FA)
n09
(FMA
Frequency (Hz)
Note 1. Set the parameters so that the
following condition will be satisfied.
n14 n12 < n11 n09
Note 2. The value set in n13 will be ignored if
parameters n14 and n12 are the same
in value.