16 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
8 Switches
8Switches
The CPU Module has the following two types of switches.
DIP switches: Mode switches
STOP/SAVE switch
DIP Switches: Mode Switches
The SW1 and SW2 switches are checked at start-up, and their behavior is described in the following tables:
Table 3 SW1 Switches
Table 4 SW2 Switches
E-INIT and - switches can override the Ethernet configuration according to Table 5.
Table 5 Operation of E-INIT, E-PM0 and E-PM1 for Configuring Ethernet
On start-up, the controller will automatically load firmware or user projects based on the LOAD and MNT switches. The
USB thumb drive is available in any other circumstances.
Table 6 Operation of LOAD and MNT for USB Thumb Drive
SW Description
STOP When ON, prevents PLC from running.
E-INIT When ON, overrides Ethernet configuration according to Table 5.
INIT When ON, the controller uses the fixed, default configuration
CNFG When ON, the controller creates Axes and I/O for all connected devices. (Auto-configuration)
SW Description
LOAD When ON, load either the user project or firmware from the USB thumb drive. See Table 6 for details.
TEST When ON, the IP address is scrolled across the seven segment display.
MNT
When ON, controller starts up in supervisor mode. In this mode MECHATROLINK III, PLC, Modbus/TCP and Ethernet/IP
do not start. The controller firmware can be updated, and clearing DOS FS alarms will repair the DOS FS.
-- / DHCP DHCP Selection when E-INIT is ON.
E-INIT -- / DHCP
Static Configuration OFF N/A
192.168.1.1 ON OFF
DHCP ON ON
E-INIT -- / DHCP
Load user project from USB thumb drive ON OFF
Install firmware and user project from USB
thumb drive
ON ON