7 PROFINET Messaging
YAS K AWA SIEP YEACOM 07A 1000-Series Option PROFINET SI-EP3 Technical Manual 25
Yaskawa Vendor-Specific Control and Status Words
The Control Word and the Status Word
The contents of the Control Word and the Status Word are detailed in Table 10.
Frequency Reference
Frequency Reference is a 16-bit word containing the desired output frequency.
Output Frequency
Output Frequency is a 16-bit word containing the current output frequency of the drive.
Table 10 Yaskawa-Specific Control Word and Status Word
Yaskawa-Specific Control Word Yaskawa-Specific Status Word
Bit Description Bit Description
0 Run bit 0 Running
1 Reverse run bit 1 Zero Speed
2EF0 2 Reverse Operation
3Fault Reset 3 Reset Signal Input Active
4ComFref 4At Speed
5ComCtrl 5Ready
6DI3 6Alarm
7DI4 7Fault
8DI5 8 oPE Fault
9DI6 9Uv Return
10 DI7 10 2nd Motor
11 DI8 <1>
<1> Not available in V1000-series drives.
<2> Not available in A1000-series drives.
11 ZSV
12 DI9 <1> <2> 12 (Unused)
13 DI10 <1> <2> 13 (Unused)
14 DI11 <1> <2> 14 Net Reference
15 DI12 <1> <2> 15 Net Control