When the frequency reference is output by analog input
of control circuit terminals FR and FC, the relation
between analog voltage and frequency reference can be
set.
Frequency reference gain (n41)
The analog input voltage
value for the maximum
output frequency (n09) can
be set in units of 1%.
Factory setting : 100%
Frequency reference bias (n42)
The frequency reference
provided when analog input
is 0V (4mA or 0mA) can be
set in units of 1%.
[n09 : Maximum output frequency = 100%]
Factory setting : 0%
Gain : Outputs % (ratio to max. output frequency n09)
at 10V.
a
n41 = %
Bias : Outputs % (ratio to max. output frequency n09)
at 0V.
a
n42 = %
B
B
A
A
FREQUENCY REF.
0V
(4mA)
10VGAIN
(20mA)
MAX. OUTPUT
FREQUENCY
GAIN
100
MAX. OUTPUT
FREQUENCY
BIAS
100
( ) indicates when current
reference input is selected.
Typical Settings
At 0 to 5V input
To operate the inverter
with frequency reference
of 50% to 100% at 0 to
10V input
0V
Gain:
Bias:
Constant n41=100
Constant n42=50
10V
MAX. OUTPUT
FREQUENCY
(100%)
50%
0V
Gain:
Bias:
Constant n41=200
Constant n42=0
10V5V
MAX. OUTPUT
FREQUENCY
(100%)
50%
0%
By inputting a jog command and then a forward
(reverse) run command, operation is enabled at the jog
frequency set in n29. When multi-step speed references
1, 2, or 3 are input simultaneously with the jog
command, the jog command has priority.
Name Constant no.
Jog frequency reference
Jog command
n29
n36 to n39
Setting
Factory setting : 6.0Hz
Set to 10 for any constant.
Frequency reference upper
limit (n30)
Sets the upper limit of the
frequency reference in units of
1%.
[n09 : Maximum output frequency
= 100%]
Factory setting : 100%
Frequency reference lower
limit (n31)
Sets the lower limit of the frequency reference in units of 1%.
[n09 : Maximum output frequency = 100%]
When operating at frequency reference 0, operation continues
at the frequency reference lower limit.
However, when frequency reference lower limit is set to less
than the minimum output frequency (n14), operation is
disabled.
Factory setting : 0%
INTERNAL FREQUENCY
REF.
FREQUENCY
UPPER LIMIT
(n033)
FREQUENCY
LOWER LIMIT
(n034)
SET FREQUENCY
REF.
By setting input terminal function selection (one of n36
to n39) to 11 (accel/decel time select), accel/decel time
is selected by turning ON/OFF the accel/decel time
select (one terminal of S2 to S5).
At OFF : n16 (accel time 1)
n17 (decel time 1)
At ON : n18 (accel time 2)
n19 (decel time 2)
OUTPUT
FREQUENCY
ACCEL
TIME 1
(n16)
DECEL TIME 1
(n17)
DECEL TIME 2
(n18)
DECEL TIME 2*
(n19)
DECEL TIME 1*
(n17)
TIME
ON
ON
ON
FWD (REV) RUN COMMAND
MULTI-STEP SPEED REF.
ACCEL/DECEL
TIME SELECTION
(TERMINAL S2 TO S5)
*
When deceleration to a stop is selected (n04=0).
No.
n16
n17
n18
n19
Unit*
0.1s
0.1s
0.1s
0.1s
Setting range
0.0 to 999s
0.0 to 999s
0.0 to 999s
0.0 to 999s
Initial setting
10.0s
10.0s
10.0s
10.0s
Name
Accel time 1
Decel time 1
Accel time 2
Decel time 2
* Setting unit is 1s when 100s or more.
• Accel time
Set the time needed for output frequency to reach 100%
from 0%.
• Decel time
Set the time needed for output frequency to reach 0%
from 100%.
Adjusting frequency setting signal
Frequency reference gain
Frequency reference bias
N42
N41
Operating at low speed
Jog frequency reference
Jog command selection to
N39N36
N29
FREF
Adjusting frequency upper and lower limits
Frequency reference upper limit
Frequency reference lower limit
N31
N30
Using two accel/decel times
Accel time 1, 2
Decel time 1, 2
Input terminal function selection to
N39N36
N19N17
N18N16