VS mini J7
PROGRAMMING FEATURES (Cont’d)
24
The set value displayed in is factory setting.
Terminal function at 3-wire sequence selection
RUN COMMAND
(Run when closed)
STOP COMMAND
(Stop when open)
FWD/REV RUN SELECTION
FWD run when open
REV run when closed
STOP SW
(NC CONTACT)
RUN SW
(NO CONTACT)
S1
S2
S3
SC
( )
Control circuit terminal S4 (UP command)
Control circuit terminal S5 (DOWN command)
Operation status
Closed
Open
Accel
Closed
Closed
Hold
Closed
Open
Decel
Open
Open
Hold
LOCAL/REMOTE select (setting : 17)
Select operation reference by the digital operator or by
the control circuit terminal.
LOCAL/REMOTE select is valid only during stop.
Open : Run by setting at run command selection (n02)
and frequency reference selection (n03).
Closed : Run by frequency reference and run command
from digital operator.
e.g. :
When the digital operator/control circuit terminal
selection setting is n02 = 1 and n03 = 2, 3 or 4
Open : Receives frequency reference (terminal FR,
RP) and run command (terminals S1 to S5 )
from control circuit terminal
Closed : Receives frequency reference (setting at n07)
and run command from digital operator.
Communication/control circuit terminal selection
(setting : 18)
Selects operation reference by communication or by
control circuit terminal. Communication/control circuit
terminal selection is valid only during stop.
Open : Run according to the setting at n02 and n03
(operation method selection).
Closed : Run by frequency reference and run command
from communication.
e.g. : When used for communication/control circuit
terminal selection, set n02 = 1 and n03 = 2, 3
or 4
Open : Receives frequency reference (terminal FR)
and run command (terminals S1 to S5 ) from
control circuit terminal
Closed: Receives frequency reference and run
command from communication
UP/DOWN command (setting : n39 = 34)
With the FWD (REV) run command entered,
accel/decel is enabled by inputting the UP or DOWN
signals to control circuit terminals S4 and S5 without
changing the frequency reference, so that operation can
be perfomed at the desired speed. When UP/DOWN
commands are specified by n39, any function set to
n38 becomes disabled; terminal S4 becomes an input
terminal for UP command and terminal S5 for DOWN
command.
* : Effective only when with option unit.
D1H D1 D1 D1UU UHH H H H HDD D
FWD RUN
UP COMMAND S4
DOWN COMMAND S5
UPPER LIMIT SPEED
LOWER LIMIT SPEED
OUTPUT FREQUENCY
FREQUENCY AGREED
SIGNAL
Time chart at UP/DOWN command input
U = UP (accelerating) status
D = DOWN (decelerating) status
H = HOLD (constant speed) status
U1 = UP status, clamping at upper limit speed
D1 = DOWN status, clamping at lower limit speed
Notes : When UP/DOWN command is selected, the
upper limit speed is set regardless of
frequency reference.
Upper limit speed = Max. output frequency
(n09) × Frequency
reference upper limit
(n30) /100
The lower limit speed is the largest value
among min. output frequency (n14) and
frequency reference lower limit (n31).
When the FWD (REV) run command is input,
operation starts at the lower limit speed
without UP/DOWN command.
When the jog command is input while running
by the UP/DOWN command, the jog
command has priority. The UP/DOWN
command can not be input together with
multi-step speed reference.
By setting hold output frequency memory
selection (n62) to 1, the output frequency
during hold can be saved.
Setting at n62
Description
0 Output frequency during hold is not saved.
1
After 5 sec. of hold state, the output frequency
during hold is saved and the operation will
restart with the saved output frequency