CONSTANT INCRE- SETTING FACTORY USER PARA.
NUMBER DATA NAME MENT RANGE SETTING SETTING REF.
Cn-14 Frequency Command 1 % 0 - 109 100 2.14
Upper Limit
Cn-15 Frequency Command 1 % 0 - 109 0 2.14
Lower Limit
Cn-16 Prohibit Frequency 1 0.1 Hz 0.0 - 400.0 0.0 2.7A
Cn-17 Prohibit Frequency 2 0.1 Hz 0.0 - 400.0 0.0 2.7A
Cn-18 Prohibit Frequency 3 0.1 Hz 0.0 - 400.0 0.0 2.7A
Cn-19 Prohibit Frequency Deadband 0.1 Hz 0.0 - 25.5 1.0 2.7B
Cn-20 Operator Display Mode 1 0 - 39999 0 2.9
Reference and Indication
Cn-21 Speed Coincidence Frequency 0.1 Hz 0.0 - 400.0 0.0 2.23, 2.21
Cn-22 Speed Coincidence Bandwidth 0.1 Hz 0.0 - 25.5 2.0 2.23, 2.21
Cn-23 Carrier Frequency Upper Limit 0.1kHz 0.4 - 15.0
See Note 3 2.36
Cn-24 Carrier Frequency Lower Limit 0.1kHz 0.4 - 15.0
See Note 3 2.36
Cn-25 Frequency Proportion Gain 1 0 - 99 0 2.36
Cn-26 Overtorque Detection Level 1 % 30 - 200 160 2.18, 2.22
Cn-27 Overtorque Detection Time 0.1 s 0.0 - 25.5 0.1 2.22
Cn-28 Stall Prevention Level During 1 % 30 - 200 170 2.29
Accel (Constant Torque Region)
Cn-29 Stall Prevention Limit During 1 % 30 - 200 50 2.29
Accel (Constant HP Region)
Cn-30 Stall Prevention Level at Set 1 % 30 - 200 160 2.29
Frequency
Cn-31 Motor-to-Motor Cable 0.001 1 0.000 - 65.535
See Note 3 – –
Resistance
Cn-32 Torque Compensation Iron 1 W 0 - 65535
See Note 3 – –
Loss
Cn-33 Torque Compensation Limiter 1 V 0 - 50
(230V) See Note 3 – –
0 - 100
(460V)
Cn-34 Motor No-load Current 1 % 0 - 99 30 2.35
See Note 2
Cn-35 Slip Compensation Primary 0.1 s 0.0 - 25.5 2.0 2.35
Delay Time
Cn-36 No. of Auto-Restart Attempts 1 0 - 10 0 2.5A
Table A1-4. Control Constants (Cn-XX) - Continued
CONSTANT INCRE- SETTING FACTORY USER PARA.
NUMBER DATA NAME MENT RANGE SETTING SETTING REF.
A1-12