2.34 UP/DOWN FREQUENCY SETTING
Sn-15 thru Sn-18: Multi-function Input Data
10
: UP function
Terminals (Term. 5-8) Data
11
: DOWN function
Programming data
10
and
11
for two of the four multi-function input terminals allows the
inputs to be used for UP/DOWN frequency setting.
NOTES:
1.
oPE03
fault will occur if UP function and DOWN function data settings are
not used together.
2. JOG has priority over UP/DOWN.
3. UP/DOWN has priority over Multi-step Speed inputs.
4. UP/DOWN is ineffective when operation is from the Digital Operator.
5. Upper and lower limit speeds set by Cn-02, Cn-14 and Cn-15.
EXAMPLE:
Sn-17 Data
10
: UP function
Sn-18 Data
11
: DOWN function
2-50
GPD 503
7
UP
8
DOWN
11
0V
UP
o o
DOWN
o o
INPUT SIGNAL
FUNCTION
UP DOWN
Open Open HOLD
Closed Open UP (Frequency command approaches frequency
command upper limit)
Open Closed DOWN (Frequency command approaches minimum
output frequency or frequency command lower limit,
whichever is larger)
Closed Closed HOLD