2.15 JOG REFERENCE Continued
EXAMPLES: (Continued)
JOG2 – 3-WIRE CONFIGURATION
Sn-04 =
0000
(Remote Control)
2-20.1
NOTES:
1. Use of external Jog input is selected by setting data
06 , 12 ,
or
13
in one of the constants Sn-15 thru Sn-18.
The factory configuration for 2-wire control is Sn-17 =
06
,
for JOG1 input at terminal 7.
The factory configuration for 3-wire control is Sn-18 =
06
,
for JOG1 input at terminal 8.
To select JOG2 - FWD, set data
12
into one of these constants.
To select JOG2 - REV, set data
13
into one of these constants.
JOG2 does not require an active RUN command to allow Jog
operation.
2. JOG2 (FWD or REV) has priority over FWD and REV Run
in 2-wire control configuration, and priority over RUN, STOP, and
FWD/REV commands in 3-wire control configuration.
3. JOG2 - FWD and JOG2 - REV can be selected independently.
4. Sn-05 =
XX1X
(Reverse Run disabled) will override JOG2 - REV.
Also see descriptions of MULTI-FUNCTION INPUT TERMINALS and RESET CODES.
RUN *
COMMAND
(EXTERNAL)
JOG2
(FWD OR REV)
FREQ. CMD
An-09 JOG
REF.
0
**
* Momentary contact.
** When JOG2 command is released, a STOP command
is issued.