• 200 V Single-phase
• 400 A 3-phase
VS mini Model J7*A
B0P1
J7*A
B0P2
J7*A
B0P4
J7*A
B0P7
J7*A
B1P5
Capacity (kVA) 0.3 0.6 1.1 1.9 3.0
Rated Output Current (A) 0.8 1.5 3 5 8
MCCB type NF30, NF50 (MIT-
SUBISHI)
5 A 5 A 10 A 20 A 30 A
Magnetic contactor
(Fuji Electric FA Com-
ponents & Systems)
Without
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N2
(35A)
With
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-N1
(26A)
Fuse (UL Class RK5) 5 A 5 A 10 A 20 A 20 A
VS mini Model J7*A
40P2
J7*A
40P4
J7*A
40P7
J7*A
41P5
J7*A
42P2
J7*A
43P0
J7*A
43P7
Capacity (kVA) 0.9 1.4 2.6 3.7 4.2 5.5 6.6
Rated Output Current (A) 1.2 1.8 3.4 4.8 5.5 7.2 8.6
MCCB type NF30, NF50
(MITSUBISHI)
5 A 5 A 5 A 10 A 15 A 20 A 20 A
Magnetic con-
tactor (Fuji Elec-
tric FA
Components &
Systems)
Without
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
SC-4-0
(18A)
SC-N1
(26A)
With
reactor
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-03
(11A)
SC-4-0
(18A)
Fuse (UL Class RK5) 5 A 5 A 5 A 10 A 10 A 20 A 20 A