YASKAWA VS MINI J7 Instruction Manual Page 55

  • Download
  • Add to my manuals
  • Print
  • Page
    / 138
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 54
54
• To operate the Inverter with a frequency reference of 50% to
100% at an input voltage of 0 to 10 V
Adjusitng Frequency Upper and Lower Limits
• Frequency Reference Upper Limit (n30)
Sets the upper limit of the frequency refer-
ence in units of 1%.
(n09: Max. Output Frequency = 100%)
Factory setting: 100%
• Frequency Reference Lower Limit (n31)
Sets the lower limit of the frequency refer-
ence in units of 1%.
(n09: Max. Output Frequency = 100%)
When operating at a frequency reference of
0, operation is continued at the frequency
reference lower limit.
However, if the frequency reference lower
limit is set to less than the Minimum Output
Frequency (n14), operation is not performed.
Factory setting: 0%
Max. frequency (100 %)
Gain n41 = 100
Bias n42 = 50
0 V 10 V
Internal
frequency
reference
Frequency
Upper Limit
(n30)
Frequency
Lower Limit
(n31)
Set frequency reference
Page view 54