YASKAWA VS MINI J7 Instruction Manual Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 138
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
5. Operating the Inverter
33
5. Operating the Inverter
Test Run
The Inverter operates when a frequency (speed) is set.
There are three operating modes for the VS mini:
1. RUN command from the Digital Operator (potentiometer/digital set-
ting)
2. RUN command from the control circuit terminals
3. RUN command from MEMOBUS communications
Prior to shipping, the Inverter is set up to receive the RUN command
and frequency reference from the Operator. Below are instructions for
running the VS mini using the Digital Operator (with potentiometer).
For instructions on operation, refer to page 41.
Operation reference or frequency reference constants can be selected
separately as shown below.
Name Constant
RUN
Command
Selection
n02 = 0 --- Enables run, stop, and reset from Digital Operator.
= 1 --- Enables run and stop from control circuit terminals.
= 2 --- Enables MEMOBUS communications.
Frequency
Reference
Selection
n03 = 0 --- Enables the Digital Operator’s potentiometer setting.
= 1 --- Enables Frequency Reference 1 (constant n21).
= 2 --- Enables a voltage reference (0 to 10 V) of control circuit terminal.
= 3 --- Enables a current reference (4 to 20 mA) of control circuit terminal.
= 4 --- Enables a current reference (0 to 20 mA) of control circuit termi-
nal.
= 6 --- Enables MEMOBUS communications.
Page view 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 137 138

Comments to this Manuals

No comments