Recommended Peripheral Devices
It is recommended that the following peripheral devices should be mounted
between the AC main circuit power supply and VS mini input terminals
R/L1, S/L2, and T/L3.
MCCB (Molded-case circuit breaker)/ fuse :
Be sure to connect it for wiring protection.
Magnetic contactor:
Mount a surge suppressor on the coil (refer to the table shown below.)
When using a magnetic contactor to start and stop the inverter, do not
exceed one start per hour.
Recommended MCCB and magnetic contactor
200V 3-phase
200V single-phase
400V 3-phase
111
VS mini model
J7
*
Z
20P1
J7
*
Z
20P2
J7
*
Z
20P4
J7
*
Z
20P7
J7
*
Z
21P5
J7
*
Z
22P2
J7
*
Z
24P0
0.3 0.6 1.1 1.9 3.0 4.2 6.7
0.8 1.6 3 5 8 11 17.5
5A 5A 5A 10A 20A 20A 30A
HI-7E HI-7E HI-7E HI-7E
HI-10-
2E
HI-10-
2E
HI-20E
Capacity (kVA)
Rated Output Current (A)
5A 5A 5A 10A 20A 20A 30A
Fuse (UL Class RK5)
MCCB type NF30
(MITSUBISHI)
Magnetic contactor type HI
(YASKAWA CONTROL)
VS mini model
J7
*
Z
B0P1
J7
*
Z
B0P2
J7
*
Z
B0P4
J7
*
Z
B0P7
J7
*
Z
B1P5
0.3 0.6 1.1 1.9 3.0
0.8 1.5 3 5 8
5A 5A 10A 20A 20A
HI-7E HI-7E HI-7E HI-15E
HI-10-
2E
Capacity (kVA)
Rated Output Current (A)
5A 5A 10A 20A 20A
Fuse (UL Class RK5)
MCCB type NF30, NF50
(MITSUBISHI)
Magnetic contactor type HI
(YASKAWA CONTROL)
VS mini model
J7
*
Z
40P2
J7
*
Z
40P4
J7
*
Z
40P7
J7
*
Z
41P5
J7
*
Z
42P2
J7
*
Z
44P0
0.9 1.4 2.6 3.7 4.2 7.0
1.2 1.8 3.4 4.8 5.5 9.2
5A 5A 5A 10A 10A 20A
HI-7E HI-7E HI-7E
HI-10-
2E
HI-10-
2E
HI-10-
2E
Capacity (kVA)
Rated Output Current (A)
5A 5A 5A 10A 10A
J7
*
Z
43P0
5.5
7.2
20A
HI-10-
2E
20A 20A
Fuse (UL Class RK5)
MCCB type NF30, NF50
(MITSUBISHI)
Magnetic contactor type HI
(YASKAWA CONTROL)