74
Using MEMOBUS (MODBUS) Communications
Serial communication is available with VS mini using programmable
controller (MEMOCON series) and MEMOBUS. In order to perform serial
communications, RS-485/422 interface card (optional) must be installed.
Refer to MEMOBUS Instruction Manual (Manual No.: TOEZ-C736-70.1)
for details of communications.
MEMOBUS (MODBUS) communications
MEMOBUS system is composed of a single master (PLC) and slaves (1
to 31 VS-mini units).
Communication between master and slave (serial communication) is
controlled according to the master program with the master initiating
communication and the slave responding.
The master sends a signal to one slave at a time. Each slave has a pre-
registered address No., and the master specifies the number and conduct
signal communications. The slave receives the communication to carry
out designated functions and reply to the master.
○ Communications specifications
Interface
Synchronization
Communication
parameters
Communication
protocol
Max. number of
inverters that can be
connected
RS-422, RS-485
Asynchronous (Start-stop synchronization)
Baud rate : Selected from 2400/4800/9600/19200 bps
Data length : 8 bits fixed
Parity : Selected from even/odd/none
Stop bits : 1 bit fixed
MEMOBUS (MODBUS) (RTU mode only)
31 units (When using RS-485)