YASKAWA VS MINI J7 User Manual Page 69

  • Download
  • Add to my manuals
  • Print
  • Page
    / 123
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 68
69
Preventing Motor from Stalling (Current Limit)
Automatically adjusts the output frequency and output current according to
the load to continue operation without stalling the motor.
Stall prevention (current limit) level during acceleration (n56)
Sets the stall prevention (current limit) level during acceleration in units of
1% (Inverter rated current = 100%).
Factory setting: 170%
A setting of 200% disables the stall prevention (current limit) during
acceleration. During acceleration, if the output current exceeds the value set
for n56, acceleration stops and frequency is maintained. When the output
current goes down to the value set for n56, acceleration starts.
*Stops the acceleration to prevent the motor from
stalling.
Release width (hysteresis) of stall prevention
during accel is approx. 5% of inverter rated
current.
In the constant output area [output frequency > max. voltage output
frequency (n11)], following equation automatically decreases the stall
prevention (current limit) level during acceleration.
*
MOTOR CURRENT
n56
OUTPUT
FREQUENCY
TIME
TIME
Stall prevention (current limit)
level during accel (n56)
Max. voltage output frequency (n11)
=
Stall prevention (current limit) level
during accel in constant output area
Output frequency
Max. voltage
output frequency
n11
Output frequency
Stall prevention during accel
(n56)
Stall prevention limit during accel
(40% of n56)
Stall prevention level
during acceleration
Page view 68
1 2 ... 64 65 66 67 68 69 70 71 72 73 74 ... 122 123

Comments to this Manuals

No comments