6-40
Control Mode and Carrier Frequency Settings
Carrier frequency settings are restricted as listed in the following table according to the control mode selec-
tion.
* The upper limit of the carrier frequency depends on the Drive capacity.
Carrier Frequency Setting Precautions
When selecting the carrier frequency, observe the following precautions.
Adjust the carrier frequency according to the cases shown below.
If the wiring distance between Drive and motor is long: Set the carrier frequency low. (Use the following
values as guidelines.)
If speed and torque are inconsistent at low speeds: Set the carrier frequency low.
If leakage current from the Drive is large: Set the carrier frequency low.
If metallic noise from the motor is large: Set the carrier frequency high.
When using V/f control or V/f control with PG, you can vary the carrier frequency according to the output
frequency, as shown in the following diagram, by setting C6-03 (Carrier Frequency Upper Limit), C6-04
(Carrier Frequency Lower Limit), and C6-05 (Carrier Frequency Proportional Gain).
Fig 6.32
Control Mode Carrier Frequency
V/f control with or without a PG
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
F: Any setting*
Detailed settings are available in C6-03, C6-04, and C6-05.
Open-loop vector control 1 or
Flux vector control
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
F: Any setting*
The upper limit of the carrier frequency is determined by C6-03.
Open-loop vector control 2
1: 2.0 kHz
2: 4.0 kHz
3: 6.0 kHz
4: 8.0 kHz
Wiring Length 50 m or less 100 m or less Over 100 m
C6-02 (carrier frequency
selection) setting
1 to 6 (15 kHz) 1 to 4 (10 kHz) 1 to 2 (5 kHz)
C6-03
C6-04
Output frequency
Output frequency × C6-05
× K*
E1-04
Max. Output Frequency
Carrier Frequency
K is the coefficient determined by the set
value in C6-03.
C6-03 10.0 kHz: K=3
10.0 kHz > C6-03 5.0 kHz: K=2
5.0 kHz > C6-03: K=1
*