10-18
UL Markings
The G7 is UL listed to UL Standard 508C, UL FILE No.: E13145.
Conformance to UL Standard
To comply with UL standard, follow the appropriate installation instructions.
Installation Site
Install the Inverter in a pollution degree 2 environment or equivalent.
Specification of Closed-Loop Connector
The closed-loop connectors must be installed on conductors before installing to terminal blocks.
Use UL Listed closed-loop connectors shown in Tab le 10.5 below.
Table 10.5 JST Closed-Loop Connector Model
Inverter
Model CIMR-G7
JST Kit P/N
Input
Wire Size
Input
JST Kit P/N
Output
Wire Size
Output
JST Kit P/N
2015 2 AWG 38-8 4 AWG 22-8
2018 2 AWG 38-8 2 AWG 38-8
2022 1/0 AWG 60-8 1/0 AWG 60-8
2030 3/0 AWG 80-10 3/0 AWG 80-10
2037 4/0 AWG 100-10 4/0 AWG 100-10
2045 1/0 AWG 60-10 (2 per Ph) 1/0 AWG 60-10 (2 per Ph)
2055 3/0 AWG 80-10 (2 per Ph) 3/0 AWG 80-10 (2 per Ph)
2075 250 kcmil 150-12 (2 per Ph) 4/0 AWG 100-12 (2 per Ph)
2090 400 kcmil 200-12 (2 per Ph) 250 kcmil 150-12 (2 per Ph)
2110 400 kcmil 200-12 (2 per Ph) 300 kcmil 150-12 (2 per Ph)
4018 6 AWG 14-6 6 AWG 14-6
4022 4 AWG 22-6 4 AWG 22-6
4030 2 AWG 38-8 4 AWG 22-8
4037 2 AWG 38-8 2 AWG 38-8
4045 1/0 AWG 60-8 1/0 AWG 60-8
4055 3/0 AWG 80-10 3/0 AWG 80-10
4075 4/0 AWG 100-10 4/0 AWG 100-10
4090 1/0 AWG 60-10 (2 per Ph) 1/0 AWG 60-10 (2 per Ph)
4110 3/0 AWG 80-10 (2 per Ph) 3/0 AWG 80-10 (2 per Ph)
4132 3/0 AWG 80-12 (2 per Ph) 3/0 AWG 80-12 (2 per Ph)
4160 4/0 AWG 100-12 (2 per Ph) 4/0 AWG 100-12 (2 per Ph)
4185 250 kcmil 150-16 (2 per Ph) 250 kcmil 150-16 (2 per Ph)
4220 400 kcmil 200-16 (2 per Ph) 300 kcmil 150-16 (2 per Ph)
4300 650 kcmil 325-16 (2 per Ph) 650 kcmil 325-16 (2 per Ph)