Yaskawa G7 Drive User Manual Page 1

Browse online or download User Manual for Equipment Yaskawa G7 Drive. Yaskawa G7 Drive User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 454
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews

Summary of Contents

Page 1 - Technical Manual

G7 DriveTechnical ManualModels: CIMR-G7U Document Number: TM.G7.01

Page 2 - Warnings and Cautions

ix5 User Parameters ... 5-1User Parameter Descriptions ...

Page 3 -  Intended Use

Trial Operation Procedures4-11Precautions for Rotational and Stationary AutotuningLower the base voltage based on Fig 4.4 to prevent saturation of th

Page 4 - Safety Precautions

4-12 Parameter Settings for AutotuningThe following parameters must be set before autotuning. Table 4.3 Parameter Settings before AutotuningParamete

Page 5 - Warning Information

Trial Operation Procedures4-13* 1. Not normally displayed. Displayed only when a motor switch command is set for a multi-function digital input (one o

Page 6

4-14 Application SettingsUser parameters are set as required in advanced programming mode (“ADV” will be displayed on the LCDscreen). All the paramet

Page 7 - Registered Trademarks

Trial Operation Procedures4-15 Loaded OperationConnect the machine to the motor and then start operation as described for no-load operation (i.e., fr

Page 8 - Contents

4-16 Check and Recording User ParametersUse verify mode (“VERIFY” will be displayed on the LCD screen) to check user parameters that have beenchanged

Page 9

Adjustment Suggestions4-17Adjustment SuggestionsIf hunting, vibration, or other problems originating in the control system occur during trial operatio

Page 10

4-18Open-loop vector control (A1-02 = 2)Speed feedback detection control (AFR) gain(N2-01)• Increasing torque and speed response• Controlling hunting

Page 11

Adjustment Suggestions4-19Flux vector control (A1-02 = 3)ASR proportional gain 1 (C5-01) and ASR proportional gain 2 (C5-03)• Torque and speed respons

Page 12

4-20* The setting is given for 200-240 V Class Drives. Double the voltage for 380-480V Class Drives.• Do not change the Torque Compensation Gain (C4-0

Page 13

xSpeed Limit (Frequency Reference Limit Function) ... 6-30Limiting Maximum Output Frequency...

Page 14 - Handling Drives

Adjustment Suggestions4-21Table 4.5 Parameters Indirectly Affecting Control and ApplicationsName (Parameter Number) ApplicationDwell function (b6-01

Page 16 - Confirmations upon Delivery

User ParametersThis chapter describes all user parameters that can be set in the Drive. User Parameter Descriptions...

Page 17 - Drive Specifications

5-2User Parameter DescriptionsThis section describes the contents of the user parameter tables. Description of User Parameter TablesUser parameter ta

Page 18 -  Component Names

Digital Operator Display Functions and Levels5-35-3Digital Operator Display Functions and LevelsThe following figure shows the Digital Operator displ

Page 19 - Fig 1.6 Drive Appearance

5-4 User Parameters Settable in Quick Programming ModeThe minimum user parameters required for Drive operation can be monitored and set in quick prog

Page 20 -  Open Chassis Drives (IP00)

Digital Operator Display Functions and Levels5-5C6-02Carrier Frequency SelectionSelects the number of pulses per second of the output voltage waveform

Page 21 -  NEMA Type 1 Drives (IP 20)

5-6E1-01Input Voltage SettingSet to the nominal voltage of the incoming line. Sets the maximum and base voltage used by preset V/F patterns (E1-03 = 0

Page 22

Digital Operator Display Functions and Levels5-7E1-04Max. Output Frequency (FMAX)These parameters are only applicable when V/f Pattern Selection is se

Page 23 -  Installation Site

5-8H4-02Terminal FM Gain SettingSets terminal FM output level when selected monitor is at 100%.In order to adjust the meter, 100% of the appropriate o

Page 24

xiMonitor Parameterss ...6-79Using the Analog Monitor Parameters...

Page 25 -  Removing the Terminal Cover

Digital Operator Display Functions and Levels5-9* 1. The setting ranges for acceleration/deceleration times depends on the setting of C1-10 (Accelerat

Page 26 - Attaching the Terminal Cover

5-10User Parameter Tables A: Setup SettingsThe following settings are made with the environment parameters (A parameters): Language displayed on theD

Page 27 - Front Cover

User Parameter Tables5-11User-set Parameters: A2The parameters set by the user are listed in the following table.A1-03Initialize ParametersUsed to re

Page 28 - Mounting the Front Cover

5-12 Application Parameters: bThe following settings are made with the application parameters (B parameters): Operation method selection,DC injection

Page 29

User Parameter Tables5-13* The setting range is 1 or 2 for flux vector control and open-loop vector control 2.b1-05Minimum Output Frequency (E1-09) or

Page 30 -  Attaching the Front Cover

5-14DC Injection Braking: b2User parameters for injection braking are shown in the following table.Parameter NumberNameDescriptionSetting RangeFactor

Page 31

User Parameter Tables5-15Speed Search: b3User parameters for the speed search are shown in the following table.Parameter NumberNameDescriptionSetting

Page 32

5-16* Factory settings will change when the control method is changed. (Open-loop vector 1 factory settings are given.) Set to “3” in V/f w/PG.** Fact

Page 33 - Connection Diagram

User Parameter Tables5-17Timer Function: b4User parameters for timer functions are shown in the following table.PID Control: b5User parameters for P

Page 34 - Connection Diagram

5-18b5-06PID Output LimitSets the maximum output possible from the entire PID controller. Set as a percentage (%) of maximum frequency.0.0 to 100.0100

Page 35 - Terminal Block Configuration

xii If Motor Deceleration is Slow... 7-23 If the Motor Overheat

Page 36 - Wiring Main Circuit Terminals

User Parameter Tables5-19b5-13PID Feedback Loss Detection LevelSets the PID feedback loss detection level as a percentage (%) of maximum frequency (E1

Page 37

5-20Dwell Functions: b6User parameters for dwell functions are shown in the following table.DROOP Control: b7User parameters for droop functions are

Page 38

User Parameter Tables5-21Energy Saving: b8User parameters for energy-saving control functions are shown in the following table.* 1. The factory setti

Page 39

5-22 Autotuning Parameters: CThe following settings are made with the autotuning parameters (C parameters): Acceleration/deceleration times, s-curve

Page 40

User Parameter Tables5-23* The setting range for accel/decel time will differ depending on C1-10 (Accel/Decel Time Units). If C1-10 is set to "0&

Page 41

5-24Motor Slip Compensation: C3User parameters for slip compensation are shown in the following table.* The display shows the factory settings for Op

Page 42 - Wire Size * Terminal Screw

User Parameter Tables5-25Torque Compensation: C4User parameters for are torque compensation shown in the following table.* The display shows the fac

Page 43

5-26Speed Control (ASR): C5User parameters for speed control are shown in the following table.* 1. Factory settings will change depending on the cont

Page 44

User Parameter Tables5-27Carrier Frequency: C6User parameters for the carrier frequency are shown in the following table.* 1. The setting range depen

Page 45 -  Main Circuit Configurations

5-28 Reference Parameters: dThe following settings are made with the reference parameters (d parameters): Frequency references.Preset Reference: d1U

Page 46 - Standard Connection Diagrams

Handling DrivesThis chapter describes the checks required upon receiving or installing an Drive. Varispeed G7 Introduction ...

Page 47 -  Wiring the Main Circuits

User Parameter Tables5-29Note The unit is set in o1-03 (frequency units of reference setting and monitor). The default for o1-03 is 0 (increments of 0

Page 48

5-30Reference Limits: d2User parameters for frequency reference limits are shown in the following table.Jump Frequencies: d3User parameters for jump

Page 49

User Parameter Tables5-31Reference Frequency Hold: d4User parameters for the reference frequency hold function are shown in the following table.Torq

Page 50 - Inductive

5-32* Factory setting will change according to the control mode (factory settings for Flux Vector Control are shown here).d5-03Speed Limit SelectionSe

Page 51 - Ground Wiring

User Parameter Tables5-33Field Control: d6User parameters for the field weakening command are shown in the following table.Parameter NumberNameDescri

Page 52

5-34 Motor Setup Parameters: EThe following settings are made with the motor setup parameters (E parameters): V/f characteristics andmotor setup para

Page 53

User Parameter Tables5-35E1-04Maximum Output FrequencyThese parameters are only applicable when V/f Pattern Selection is set to Custom (E1-03 = F or F

Page 54 - Digital

5-36* 2. The factory setting will change when the control method is changed. (Open-loop vector 1 factory settings are given.)* 3. E1-11 and E1-12 are

Page 55

User Parameter Tables5-37User parameters for motor 1 are shown in the following table. * 1. The factory setting depends upon the Drive capacity. The v

Page 56

5-38* 1. These are values for a 200-240V class Drive. Values for a 380-480V class Drive are double.* 2. The factory setting will change when the contr

Page 57

1-2Varispeed G7 Introduction Varispeed G7 ModelsThe Varispeed-G7 Series of Drives included two Drives in two voltage classes: 200-240V and 380-480V.

Page 58

User Parameter Tables5-39Motor 2 Setup: E4User parameters for motor 2 are shown in the following table.Parameter NumberNameDescriptionSetting RangeFa

Page 59 -  Sinking/Sourcing Mode

5-40* 1. The factory setting depends upon the Drive capacity. The value for a 200-240V class Drive of 0.4 kW is given.* 2. The setting range is 10% to

Page 60

User Parameter Tables5-41 Option Parameters: FThe following settings are made with the option parameters (F parameters): Settings for Option Cards.P

Page 61 -  Wiring Checks

5-42F1-05PG Rotation Selection0: Fwd=C.C.W. - Phase A leads with forward run command. (Phase B leads with reverse run command.)1: Fwd=C.W. - Phase B l

Page 62

User Parameter Tables5-43* The factory setting will change when the control method is changed. (Flux vector control factory settings are given.)*1 Def

Page 63

5-44Analog Reference Card: F2User parameters for the Analog Reference Card are shown in the following table.Parameter NumberNameDescriptionSetting Ra

Page 64

User Parameter Tables5-45Digital Reference Card: F3User parameters for the Digital Reference Card are shown in the following table.Analog Monitor Ca

Page 65

5-46F4-04AO-08/AO-12 Channel 2 GainSets the channel 2 gain. In order to adjust the meter, 100% of the appropriate output is multiplied for the gain se

Page 66

User Parameter Tables5-47Digital Output Card (DO-02 and DO-08): F5User parameters for the Digital Output Card are shown in the following table.Parame

Page 67 -  Wiring

5-48Communications Option Cards: F6User parameters for a Communications Option Card are shown in the following table.F5-08DO-08 Channel 8 Output Sele

Page 68

Confirmations upon Delivery1-3Confirmations upon Delivery ChecksCheck the following items as soon as the Drive is delivered. If you find any irregula

Page 69 -  Wiring the PG-B2

User Parameter Tables5-49F6-04Trace Sampling from Communication Option BoardSets the sample trace for the CP-916 option board. 0 to 600000NoAAAAA3A5HT

Page 70 - Wiring the PG-X2

5-50 Terminal Function Parameters: HThe following settings are made with the terminal function parameters (H parameters): Settings for externaltermin

Page 71 -  Wiring Terminal Blocks

User Parameter Tables5-51* Number in parenthesis indicates the initial value when using a 3-wire sequence.Multi-function Contact Input FunctionsH1-07M

Page 72 - Capacitor for momentary

5-52C Multi-function analog input selection (ON: Enable) Yes Yes Yes Yes YesD No V/f control with PG (ON: Speed feedback control disabled,) (normal V/

Page 73

User Parameter Tables5-53 Multi-function Contact Outputs: H2User parameters for multi-function outputs are shown in the following tables.71 Speed/tor

Page 74 - Digital Operator and Modes

5-54 Multi-function Contact Output FunctionsSetting ValueFunctionControl MethodsV/f V/f with PGOpenLoopVector1FluxVectorOpenLoopVector20 During run (O

Page 75 - Digital Operator

User Parameter Tables5-55Analog Inputs: H3User parameters for analog inputs are shown in the following table.1FMotor overload (OL1, including OH3) pr

Page 76 -  Digital Operator Keys

5-56H3-06Terminal A3 Gain SettingSets the output level when 10V is input.0.0 to 1000.0100.0% Yes A A A A A 415HTerminal A3 GainH3-07Terminal A3 Bias S

Page 77 - Drive Mode Indicators

User Parameter Tables5-57H3-05,H3-09 SettingsSetting ValueFunction Contents (100%)Control MethodsV/f V/f with PGOpenLoopVector1FluxVectorOpenLoopVecto

Page 78 -  Drive Modes

5-58Multi-function Analog Outputs: H4User parameters for multi-function analog outputs are shown in the following table.* In order to adjust the mete

Page 79

1-4Drive Model NumbersThe model number of the Drive on the nameplate indicates the specification, voltage class, and maximummotor capacity of the Dri

Page 80 -  Drive Mode

User Parameter Tables5-59MODBUS Communications: H5User parameters for MODBUS communications are shown in the following table.* If H5-01 is set to zer

Page 81

5-60Pulse Train I/O: H6User parameters for pulse I/O are shown in the following table.Parameter NumberNameDescriptionSetting RangeFactory SettingChan

Page 82 -  Quick Programming Mode

User Parameter Tables5-61 Protection Function Parameters: LThe following settings are made with the protection function parameters (L parameters): Mo

Page 83 -  Advanced Programming Mode

5-62Power Loss Ridethrough: L2User parameters for power loss ridethroughs are shown in the following table.Parameter NumberNameDescriptionSetting Ran

Page 84 - Entry Accepted

User Parameter Tables5-63* 1. Factory settings will vary based on drive capacity (values given here are for 208-240Vac, 0.4kW).* 2. Setting value for

Page 85

5-64L3-02Stall Prevention Level During AccelerationThis function is enabled when L3-01 is "1" or "2".Drive rated current is 100%.

Page 86 -  Verify Mode

User Parameter Tables5-65* In Flux Vector or in Open Loop Vector 2, the setting range becomes 0 to 2.* *1 Values shown here are for 208-240V drives. D

Page 87 -  Autotuning Mode

5-66Reference Detection: L4User parameters for the reference detection function are shown in the following table.Parameter NumberNameDescriptionSetti

Page 88

User Parameter Tables5-67Fault Restart: L5User parameters for restarting faults are shown in the following table.L4-06Frequency Reference at Referenc

Page 89

5-68Torque Detection: L6User parameters for the torque detection function are shown in the following table.Parameter NumberNameDescriptionSetting Ran

Page 90 - Trial Operation

Confirmations upon Delivery1-5 Component Names Models CIMR-G7U20P4 thru 2015 and 40P4 thru 4015The external appearance and component names of the Dr

Page 91 - Trial Operation Procedure

User Parameter Tables5-69L6-02Torque Detection Level 1Sets the Overtorque/Undertorque detection level as a percentage of Drive rated current or torque

Page 92 - Trial Operation Procedures

5-70L6-04Torque Detection Selection 2Determines the Drive's response to an Overtorque/Undertorque condition. Overtorque and Undertorque are deter

Page 93 -  Checking the Display Status

User Parameter Tables5-71Torque Limits: L7User parameters for torque limits are shown in the following table.Parameter NumberName DescriptionSetting

Page 94 -  Basic Settings

5-72Hardware Protection: L8User parameters for hardware protection functions are shown in the following table.Parameter NumberNameDescriptionSetting

Page 95

User Parameter Tables5-73* Factory settings will vary based on drive capacity.L8-10Heatsink Cooling Fan Operation SelectionControls the heatsink cooli

Page 96 - Overview of Settings

5-74 n: Special AdjustmentsThe following settings are made with the special adjustments parameters (n parameters): Hunting preventionand speed feedba

Page 97 - Setting the Control Method

User Parameter Tables5-75Speed Feedback Protection Control Functions: n2User parameters for speed feedback protection control functions are shown in

Page 98 -  Autotuning

5-76Speed Estimation: n4User parameters for speed estimation are shown in the following table.n3-03High Slip Braking Dwell Time at StopSets the amoun

Page 99

User Parameter Tables5-77n4-17Torque Adjustment GainSets the torque adjustment gain for low-speed power.0.0 to 5.01.0 No No No No No A 5A4HTRQ adjust

Page 100 - IMPORTANT

5-78n4-35U1-48 Gain Reduction CoefficientSetting this parameter to a low value can improve operation when acceleration during low speeds or regenerati

Page 101

1-6 Models CIMR-G7U2018 thru 2110 and 4018 thru 4300The external appearance and component names of the Drive are shown in Fig 1.6. The Drive with the

Page 102

User Parameter Tables5-79Feed Forward: n5User parameters for the feed forward control are shown in the following table.* 1. Initial values differ bas

Page 103 -  No-load Operation

5-80 Digital Operator Parameters: oThe following settings are made with the Digital Operator parameters (o parameters): Multi-function selections and

Page 104 -  Loaded Operation

User Parameter Tables5-81Multi-function Selections: o2User parameters for Digital Operator key functions are shown in the following table.o1-04Settin

Page 105 - Password (A1-04 and A1-05)

5-82o2-04Drive/kVA SelectionSets the kVA of the Drive. Enter the number based on Drive model number. Use the last four digits of the model number. CIM

Page 106 - Adjustment Suggestions

User Parameter Tables5-83* Factory settings will vary based on drive capacity (values given here are for 208-240Vac, 0.4kW). Copy Function: o3User pa

Page 107 - Recommended

5-84 T: Motor AutotuningThe following settings are made with the motor autotuning parameters (T parameters): Settings for autotuning.Parameter Number

Page 108

User Parameter Tables5-85* 1. Set T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 is possible for V/f control or V/f control with PG.* 2. Se

Page 109

5-86 U: Monitor Parameters The following settings are made with the monitor parameters (U parameters): Setting parameters for monitoring indrive mode

Page 110

User Parameter Tables5-87* The unit is set in o1-03 (frequency units of reference setting and monitor).U1-09Torque ReferenceTorque reference10V: Motor

Page 111

5-88U1-13Cumulative Operation TimeTotal operating or power-on time of the Drive.No output possible.1hrAA A A A 4CHElapsed TimeU1-14Software NumberLast

Page 112 - User Parameters

iWarnings and CautionsThis Section provides warnings and cautions pertinent to this product, that if not heeded, may result in personal injury, fatali

Page 113 - User Parameter Descriptions

Exterior and Mounting Dimensions1-7Exterior and Mounting Dimensions Open Chassis Drives (IP00)Exterior diagrams of the Open Chassis Drives are shown

Page 114

User Parameter Tables5-89U1-24PI Feedback Va lu eFeedback signal level when PID control is used.10V: Maximum Frequency(possible for -10V thru +10V)0.0

Page 115 - Control Methods

5-90U1-34First Parameter Causing an OPEParameter number causing an "OPE" fault.No output possible.-AAA A A 61HOPE DetectedU1-35Zero Servo Pu

Page 116

User Parameter Tables5-91U1-44ASR Output without FilterOutput from the speed control loop (ASR) before the ASR primary delay filter (C5-06). 100% is d

Page 117

5-92 Fault Trace: U2User parameters for error tracing are shown in the following table.Parameter NumberNameDescriptionOutput Signal Level During Mult

Page 118

User Parameter Tables5-93Note The following errors are not included in the error trace: CPF00, 01, 02, 03, UV1, and UV2.U2-10Torque Reference at Previ

Page 119

5-94Fault History: U3User parameters for the error log are shown in the following table.Parameter NumberNameDescriptionOutput Signal Level During Mul

Page 120

User Parameter Tables5-95Note The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.U3-117th Most Recent FaultShows

Page 121 - User Parameter Tables

5-96 Factory Settings that Change with the Control Method (A1-02)The factory settings of the following user parameters will change if the control met

Page 122 - User-set Parameters: A2

User Parameter Tables5-97* 1. The settings will be 0.05 (Flux vector)/2.00 (Open-loop vector) for drives of 55kW or larger.* 2. The settings shown are

Page 123 -  Application Parameters: b

5-98208-240Vac and 380-480Vac Drives of 0.4 to 1.5 kW208-240Vac and 380-480Vac Drives of 0.4 to 1.5 kWTable 5.1 V/F Pattern for Drive Capacities G7U

Page 124

1-8 NEMA Type 1 Drives (IP 20)Exterior diagrams of the Enclosed Wall-mounted Drives (NEMA1 Type 1) are shown below.WW13H1H2DH0D1H34 H4-dt1Models CIMR

Page 125 - DC Injection Braking: b2

User Parameter Tables5-99208-240Vac and 380-480Vac Drives of 2.2 to 45 kW Table 5.4 V/F Pattern for Drive Capacity G7U22P2 - 2045 for 208-240V ClassPa

Page 126 - Speed Search: b3

5-100208-240Vac Drives of 55 to 110 kW and 380-480Vac Drives of 55 to 300 kWTable 5.5 V/F Pattern for Drive Capacity G7U2055 and higher for 208-240V

Page 127

User Parameter Tables5-101Table 5.6 lists the factory settings of V/F patterns when open loop vector or flux vector control method is selected (A1-02

Page 128 - PID Control: b5

5-102 Factory Settings that Change with the Drive Capacity (o2-04)The factory settings of the following user parameters will change if the Drive capa

Page 129

User Parameter Tables5-103Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is

Page 130

5-104380-480Vac DrivesParameter NumberName Unit Factory Setting- Drive Capacity kW 0.4 0.75 1.5 2.2 3.7 4.0 5.5 7.5 11 15o2-04 kVA selection - 20 21

Page 131 - DROOP Control: b7

User Parameter Tables5-105Parameter NumberName Unit Factory Setting- Drive Capacity kW 18.5 22 30 37 45o2-04 kVA selection - 2A 2B 2C 2D 2Eb8-03Energy

Page 132 - Zero Servo: b9

5-106Note Drives with a capacity of 185 kW or more are under development.* 1. The initial settings for C6-02 are as follows: 1: 2.0 kHz, 2: 5.0 kHz, 3

Page 133 -  Autotuning Parameters: C

Parameter Settings byFunction Frequency Reference ...6-2 Run Command...

Page 134

6-2Frequency ReferenceThis section explains how to input the frequency reference. Selecting the Frequency Reference SourceSet parameter b1-01 to sele

Page 135 - Motor Slip Compensation: C3

Exterior and Mounting Dimensions1-9* Same for Open Chassis and Enclosed Wall-mounted DrivesTable 1.3 Drive Dimensions (mm) and Masses (kg)Voltage Clas

Page 136 - Torque Compensation: C4

Frequency Reference6-3Inputting the Frequency Reference Using Voltage (Analog Setting)When b1-01 is set to 1, you can input the frequency reference f

Page 137 - Speed Control (ASR): C5

6-4Switch between 2 Step Speeds: Master/Auxiliary SpeedsWhen switching between the master and auxiliary speeds, connect the master speed frequency ref

Page 138 - Carrier Frequency: C6

Frequency Reference6-5 Using Multi-Step Speed OperationWith Varispeed-G7 series Drives, you can change the speed to a maximum of 17 steps, using 16 f

Page 139 -  Reference Parameters: d

6-6Setting PrecautionsWhen setting analog inputs to step 1 to step 3, observe the following precautions.• When setting terminal A1's analog input

Page 140

Run Command6-7Run CommandThis section explains input methods for the run command. Selecting the Run Command SourceSet parameter b1-02 to select the s

Page 141 - Jump Frequencies: d3

6-8Performing Operations Using a 3-wire SequenceWhen any parameter from H1-01 to H1-10 (multi-function contact input terminals S3 to S12) is set to 0,

Page 142 - Torque Control: d5

Stopping Methods6-9Stopping MethodsThis section explains methods of stopping the Drive. Selecting the Stopping Method when a Stop Command is SentTher

Page 143

6-10* The setting range is 0 or 1 for flux vector control and open-loop vector control 2.Deceleration to StopIf the stop command is input (i.e., the

Page 144 - Field Control: d6

Stopping Methods6-11The operation after stopping depends on the setting of b1-05 when flux vector control is selected (A1-02 = 3).Fig 6.12 Decelerati

Page 145 -  Motor Setup Parameters: E

6-12DC Braking StopIf the stop command is input (i.e., the run command is turned OFF) when b1-03 is set to 2, a wait is made forthe time set in L2-03

Page 146 - Parameter

1-10Checking and Controlling the Installation SiteInstall the Drive in the installation site described below and maintain optimum conditions.  Instal

Page 147 - Motor Setup: E2

Stopping Methods6-13 Using the DC Injection BrakeSet parameter b2-03 to apply the DC injection brake voltage to the motor while it is coasting to a s

Page 148 -  Motor 2 V/f Pattern: E3

6-14Changing the DC Injection Brake Current Using an Analog InputIf you set H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-

Page 149

Acceleration and Deceleration Characteristics6-15Acceleration and Deceleration CharacteristicsThis section explains the acceleration and deceleration

Page 150 - Motor 2 Setup: E4

6-16* The setting range for accel/decel time will differ depending on C1-10 (Accel/Decel Time Units). If C1-10 is set to "0", then the sett

Page 151

Acceleration and Deceleration Characteristics6-17Switching Acceleration and Deceleration Time Using Multi-Function Input Terminal CommandsUsing the D

Page 152 -  Option Parameters: F

6-18Fig 6.19 Acceleration/Deceleration Time Gain Using an Analog InputEntering S-curve Characteristics in the Acceleration and Deceleration TimeBy

Page 153

Acceleration and Deceleration Characteristics6-19 Accelerating and Decelerating Heavy Loads (Dwell Function)The dwell function stores the output freq

Page 154

6-20 Preventing the Motor from Stalling During Acceleration (Stall Prevention During Acceleration Function)The Stall Prevention During Acceleration f

Page 155 - Analog Reference Card: F2

Acceleration and Deceleration Characteristics6-21Time ChartThe following figure shows the frequency characteristics when L3-01 is set to 1.Fig 6.21

Page 156 - Analog Monitor Cards: F4

6-22 Preventing Overvoltage During Deceleration (Stall Prevention During Deceleration Function)The Stall Prevention During Deceleration function make

Page 157

Installation Orientation and Space1-11Installation Orientation and SpaceInstall the Drive vertically so as not to reduce the cooling effect. When inst

Page 158

Acceleration and Deceleration Characteristics6-23Setting ExampleAn example of stall prevention during deceleration when L3-04 is set to 1 as shown be

Page 159

6-24Adjusting Frequency ReferencesThis section explains methods of adjusting frequency references. Adjusting Analog Frequency ReferencesGain and bias

Page 160

Adjusting Frequency References6-25Adjusting Analog Frequency Reference Using ParametersThe frequency reference is input from the control circuit term

Page 161

6-26Adjusting Frequency Gain Using an Analog InputWhen H3-09 or H3-05 is set to 1 (frequency gain), you can adjust the frequency gain using the analo

Page 162

Adjusting Frequency References6-27For example, if H3-02 is 100%, H3-03 is 0%, and terminal A2 is set to 1 V, the frequency reference fromterminal A1 w

Page 163 - Function

6-28Fig 6.27 Jump FrequencySetting Jump Frequency Reference Using an Analog InputWhen parameter H3-09 (Multi-function Analog Input Terminal A2 Funct

Page 164

Adjusting Frequency References6-29 Adjusting Frequency Reference Using Pulse Train InputsThe frequency reference can be adjusted when b1-01 (Referenc

Page 165

6-30Speed Limit (Frequency Reference Limit Function)This section explains how to limit the motor speed. Limiting Maximum Output FrequencyIf you do no

Page 166 - Analog Inputs: H3

Speed Limit (Frequency Reference Limit Function)6-31 Limiting Minimum FrequencyIf you do not want the motor to rotate at below a given frequency, use

Page 167

6-32Improved Operating EfficiencyThis section explains functions for improving motor operating efficiency. Reducing Motor Speed Fluctuation (Slip Com

Page 168 - H3-05,H3-09 Settings

1-12Removing and Attaching the Terminal CoverRemove the terminal cover to wire cables to the control circuit and main circuit terminals.  Removing th

Page 169

Improved Operating Efficiency6-33Adjusting Slip Compensation GainYou can switch the C3-01 parameter settings as shown below by changing the control m

Page 170 - MODBUS Communications: H5

6-34Fig 6.31 Slip Compensation LimitSelecting Slip Compensation Function During RegenerationSet whether to enable or disable the slip compensation f

Page 171 - Pulse Train I/O: H6

Improved Operating Efficiency6-35 Compensating for Insufficient Torque at Startup and Low-speed Opera-tion (Torque Compensation)The torque compensati

Page 172 - Motor Overload: L1

6-36Adjusting Torque Compensation GainNormally, there is no need to make this adjustment. Do not adjust the torque compensation gain when usingopen-l

Page 173 - Power Loss Ridethrough: L2

Improved Operating Efficiency6-37 Hunting-prevention FunctionThe hunting-prevention function suppresses hunting when the motor is operating with a li

Page 174 - Stall Prevention: L3

6-38 Stabilizing Speed (Speed Feedback Detection Function)The speed feedback detection control (AFR) function measures the stability of the speed whe

Page 175

Machine Protection6-39Machine ProtectionThis section explains functions for protecting the machine. Reducing Noise and Leakage CurrentThe switching f

Page 176

6-40Control Mode and Carrier Frequency SettingsCarrier frequency settings are restricted as listed in the following table according to the control mo

Page 177 - Reference Detection: L4

Machine Protection6-41• With vector control, the carrier frequency is fixed to the Carrier Frequency Upper Limit in C6-03 if user-set or by the carrie

Page 178 - Fault Restart: L5

6-42 Limiting Motor Torque (Torque Limit Function)The motor torque limit function is enabled only with open-loop torque control.In the open-loop vect

Page 179 - Torque Detection: L6

Removing and Attaching the Terminal Cover1-13 Attaching the Terminal CoverAfter wiring the terminal block, attach the terminal cover by reversing the

Page 180

Machine Protection6-43Setting the Torque Limit in ParametersUsing L7-01 to L7-04, you can set individually four torque limits in the following direct

Page 181

6-44Setting Precautions• When the torque limit function is operating, control and compensation of the motor speed is disabledbecause torque control i

Page 182 - Torque Limits: L7

Machine Protection6-45 Changing Stall Prevention Level during Operation Using an Analog InputIf you set H3-09 (Multi-function Analog Input Terminal A

Page 183 - Hardware Protection: L8

6-46Related ParametersParameter NumberNameDescriptionSetting RangeFactory SettingChange during OperationControl MethodsDisplayV/f V/f with PGOpenLoop

Page 184

Machine Protection6-47L6-03Torque Detection Time 1Sets the length of time an Overtorque/Undertorque condition must exist before Torque Detection 1 is

Page 185 -  n: Special Adjustments

6-48Multi-function Output (H2-01 to H2-05)L6-01 and L6-04 Set Values and LCD IndicationsThe relationship between alarms displayed by the Digital Oper

Page 186 - High-slip Braking: n3

Machine Protection6-49Setting ExampleThe following diagram shows the time chart for overtorque and undertorque detection.• Overtorque Detection• Unde

Page 187 - Speed Estimation: n4

6-50 Changing Overtorque and Undertorque Detection Levels Using an Ana-log InputIf you set parameter H3-09 (Multi-function Analog Input Terminal A2 F

Page 188

Machine Protection6-51 Motor Overload ProtectionYou can protect the motor from overload using the Drive's built-in electronic thermal overload r

Page 189

6-52Setting Motor Rated CurrentSet the rated current value on the motor nameplate in parameters E2-01 (for motor 1) and E4-01 (for motor 2).This set

Page 190 - Feed Forward: n5

1-14Removing/Attaching the Digital Operator and Front CoverThe methods of removing and attaching the Digital Operator and Front Cover are described in

Page 191

Machine Protection6-53 Setting Motor Protection Operation TimeSet the motor protection operation time in L1-02.If, after operating the motor continuo

Page 192

6-54 Motor Overheating Protection Using PTC Thermistor InputsPerform motor overheating protection using the thermistor temperature resistance charact

Page 193

Machine Protection6-55PTC Thermistor CharacteristicsThe following diagram shows the characteristics of the PTC thermistor temperature to the resistan

Page 194 -  Copy Function: o3

6-56Fig 6.41 Mutual Connections During Motor Overheating Protection Limiting Motor Rotation DirectionIf you set motor reverse rotation prohibited, a

Page 195 -  T: Motor Autotuning

Continuing Operation6-57Continuing OperationThis section explains functions for continuing or automatically restarting Drive operation even if an erro

Page 196

6-58Related Parameters*1 In order for a restart to occur, the run command must be maintained throughout the ride thru period.*2 Factory settings

Page 197 -  U: Monitor Parameters

Continuing Operation6-59 Speed SearchThe speed search function finds the actual speed of the motor that is rotating using inertia, and then startssmo

Page 198

6-60* 1. The factory setting will change when the control method is changed (Open-loop vector control 1 factory settings are given). * 2. The fact

Page 199

Continuing Operation6-61Setting Precautions• When both external search commands 1 and 2 are set for the multi-function contact terminals, an OPE03(in

Page 200

6-62Speed Search SelectionSet whether to enable or disable speed search at startup, and set the type of speed search (estimated speed orcurrent detec

Page 201 - U1-40= 00000000

Removing/Attaching the Digital Operator and Front Cover1-15Removing the Front CoverPress the left and right sides of the front cover in the direction

Page 202

Continuing Operation6-63Speed Search after Short Baseblock (during Power Loss Recovery, etc.)• Loss Time Shorter Than the Minimum Baseblock Time (L2-0

Page 203 -  Fault Trace: U2

6-64Fig 6.45 Speed Search at Startup (Using Current Detection)Speed Search after Short Baseblock (during Power Loss Recovery, etc.)• Loss Time Short

Page 204

Continuing Operation6-65 Continuing Operation at Constant Speed When Frequency Reference Is LostThe frequency reference loss detection function conti

Page 205 - Fault History: U3

6-66 Restarting Operation After Transient Error (Auto Restart Function)If a Drive error occurs during operation, the Drive will perform self-diagnosi

Page 206

Drive Protection6-67Drive ProtectionThis section explains the functions for protecting the Drive and the braking resistor. Performing Overheating Pro

Page 207 - Factory Setting

6-68 Reducing Drive Overheating Pre-Alarm Warning LevelsThe Drive detects the temperature of the cooling fins using the thermistor, and protects the

Page 208

Input Terminal Functions6-69Input Terminal FunctionsThis section explains input terminal functions, which set operating methods by switching functions

Page 209

6-70 Blocking Drive Outputs (Baseblock Commands)Set 8 or 9 (Baseblock command NO/NC) in one of the parameters H1-01 to H1-10 (multi-function contacti

Page 210

Input Terminal Functions6-71 Stopping Acceleration and Deceleration (Acceleration/Deceleration Ramp Hold)The acceleration/deceleration ramp hold func

Page 211

6-72Application Precautions• When d4-01 is set to 1, the output frequency on hold is stored even after the power supply is turned OFF. Ifperforming o

Page 212 - Voltage

1-16Mounting the Digital OperatorAfter attaching the front cover, mount the Digital Operator onto theDrive using the following procedure.1. Hook the

Page 213 - 208-240Vac Drives

Input Terminal Functions6-73PrecautionsWhen setting and using UP and DOWN commands, observe the following precautions.Setting PrecautionsIf multi-fun

Page 214 - Name Unit Factory Setting

6-74Fig 6.51 UP/DOWN Commands Time ChartOutput frequencyUpper limitAccelerates tolower limitSame frequencyLower limitForward operation/stopUP command

Page 215 - 380-480Vac Drives

Input Terminal Functions6-75 Accelerating and Decelerating Constant Frequencies in the Analog Refer-ences (+/- Speed)The +/- speed function increment

Page 216

6-76 Hold Analog Frequency Using User-set TimingWhen one of H1-01 to H1-10 (multi-function contact input terminal S3 to S12 function selection) is se

Page 217

Input Terminal Functions6-77Setting PrecautionsTo switch command inputs between the Communications Option Card and the control circuit terminals, set

Page 218 - Parameter Settings by

6-78 Stopping the Drive by Notifying Programming Device Errors to the Drive (External Fault Function)The external fault function performs the error c

Page 219 - Frequency Reference

Monitor Parameters6-79Monitor ParametersThis section explains the analog monitor and pulse monitor parameters. Using the Analog Monitor ParametersThi

Page 220

6-80*1 In order to adjust the meter, 100% of the appropriate output is multiplied for the gain setting, the bias amount is added and then output.See

Page 221 - 3.5 to 13.2 V

Monitor Parameters6-81Selecting Analog Monitor ItemsThe digital operator monitor items (U1- [status monitor]) are output from multi-function analog

Page 222 - Related Parameters

6-82 Using Pulse Train Monitor ContentsThis section explains pulse monitor parameters.Related ParametersSelecting Pulse Monitor ItemsOutput digital

Page 223

ii• To avoid unnecessary fault displays caused by contactors or output switches placed between Drive and motor, auxil-iary contacts must be properly

Page 224 - Run Command

Removing/Attaching the Digital Operator and Front Cover1-17 Models CIMR-G7U2018 thru 2110 and 4018 thru 4300For Drive models CIMR-G7U2018 thru 2110 a

Page 225

Monitor Parameters6-83Using a Sinking InputExternal Power Supply (V)12 VDC±10%,15 VDC±10%Sink Current (mA) 16mA MaxLoad impedanceSinking currentExtern

Page 226 - Stopping Methods

6-84Individual FunctionsThis section explains the individual functions used in special applications. Using MODBUS CommunicationsYou can perform seria

Page 227 - C1-01= 0 010.0Sec

Individual Functions6-85Communications Connection TerminalMODBUS communications use the following terminals: S+, S-, R+, and R-. Set the terminating

Page 228 - Run command

6-86Related ParametersParameter NumberNameDescriptionSetting RangeFactory SettingChange during OperationControl MethodsDisplayV/fV/f with PGOpenLoopV

Page 229 - Coast to Stop with Timer

Individual Functions6-87* If H5-01 is set to zero, then the drive will be unable to respond to Modbus communication.H5-05Communication Fault Detection

Page 230 - Using the DC Injection Brake

6-88MODBUS communications can perform the following operations regardless of the settings in b1-01 and b1-02.• Monitoring operation status from the PL

Page 231 -  Using an Emergency Stop

Individual Functions6-89Error CheckErrors are detected during communications using CRC-16. Perform calculations using the following method.1. The fact

Page 232

6-90Loopback TestThe loopback test returns command messages directly as response messages without changing the contents tocheck the communications bet

Page 233

Individual Functions6-91Data TablesThe data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcastdata

Page 234 - Commands

6-92Note Write 0 to all unused bits. Also, do not write data to reserved registers.Monitor DataThe following table shows the monitor data. Monitor dat

Page 236

Individual Functions6-930029H Not used002AH Not used002BHSequence input statusBit 0 1: Control circuit terminal S1 ONBit 1 1: Control circuit terminal

Page 237 - During Acceleration Function)

6-94Note Communications error details are stored until an fault reset is input (you can also reset while the Unit is operating).Broadcast DataThe foll

Page 238 - Setting Precautions

Individual Functions6-95Error CodesThe following table shows MODBUS communications error codes.Slave Not RespondingIn the following cases, the slave

Page 239 - Deceleration Function)

6-96Self-DiagnosisThe Drive has a built-in function for self-diagnosing the operations of serial communications interface cir-cuits. This function is

Page 240 - Setting Example

Individual Functions6-97 Using the Timer FunctionMulti-function contact input terminals S3 to S7 can be designated as timer function input terminals,

Page 241

6-98 Using PID ControlPID control is a method of making the feedback value (detection value) match the set target value. By combin-ing proportional c

Page 242

Individual Functions6-99Related ParametersParameter NumberNameDescriptionSetting RangeFactory SettingChange during OperationControl MethodsDisplayV/f

Page 243 - Terminal A1 input voltage

6-100b5-10PID Output Gain SettingSets the output gain of the PID controller.0.0 to 25.01.0 NoAAAAAOutput Gainb5-11PID Output Reverse Selection0: Zero

Page 244

Individual Functions6-101Multi-Function Contact Inputs (H1-01 to H1-10)Multi-Function Analog Input (H3-05, H3-09)Parameter NumberNameDescriptionOutput

Page 245

6-102PID Control MethodsThere are four PID control methods. Select the method by setting parameter b5-01.PID Input MethodsEnable PID control using p

Page 246

WiringThis chapter describes wiring terminals, main circuit terminal connections, main circuit termi-nal wiring specifications, control circuit termin

Page 247 - Function)

Individual Functions6-103PID Adjustment MethodsUse the following procedure to adjust PID while performing PID control and measuring the response wave

Page 248 - Limiting Minimum Frequency

6-104Suppressing Short Cycle VibrationIf vibration occurs when the vibration cycle is short, and the cycle is almost identical to the derivative time

Page 249 - Improved Operating Efficiency

Individual Functions6-105PID Control BlockThe following diagram shows the PID control block in the Drive.Fig 6.60 PID Control BlockOption CardSerial

Page 250

6-106PID Feedback Loss DetectionWhen performing PID control, be sure to use the PID feedback loss detection function. If PID feedback is lost,the Dri

Page 251 - E1-06: Base frequency

Individual Functions6-107 Energy-savingTo perform energy saving, set b8-01 (Energy Saving Mode Selection) to 1. Energy-saving control can be per-form

Page 252

6-108Adjusting Energy-saving ControlThe method of adjustment during energy-saving control operations differs depending on the control method.Refer to

Page 253

Individual Functions6-109* 1. Initial/Default settings vary based on drive capacity. Values shown here are for 200-240V class 0.4kW drives.* 2. The s

Page 254 -  Hunting-prevention Function

6-110Manual Motor Parameter Setting MethodsThe motor parameter settings methods are given below. Make (enter) settings referring to the motor testrep

Page 255

Individual Functions6-111 Setting the V/f PatternIn V/f control method, you can set the Drive input voltage and the V/f pattern as the need arises.R

Page 256 - Machine Protection

6-112* 1. These are values for a 200-240V Class Drive. Values for a 380-480V Class Drive are double.* 2. The factory setting will change when the cont

Page 257 - 5.0 kHz > C6-03: K=1

2-2Connection DiagramThe connection diagram of the Drive is shown in Fig 2.1.When using the Digital Operator, the motor can be operated by wiring only

Page 258 - 200-240 V, 30 to 75 kW

Individual Functions6-113Setting Drive Input Voltage E1-01Setting Range: 155.0V to 255.0V (200-240V Models)310.0V to 510.0V (380-480V Models)Factory

Page 259

6-114 E1-04 Maximum Output FrequencySetting Range: 0.0 to 400.0HzFactory Default: 60.0Hz E1-05 Maximum Output VoltageSetting Range: 0.0 to 255.0V (2

Page 260

Individual Functions6-115Fig.38 Custom V/f Pattern Programming CurveIncreasing the voltage in the V/f pattern increases the available motor torque. Ho

Page 261

6-116Table 9 V/f Pattern Default Settings for Drive Capacity 0.4~1.5kW for 240V Class (Continued)Parameter No.Name Unit Factory SettingE1-03 V/f Patte

Page 262 -  Detecting Motor Torque

Individual Functions6-117Table 10 V/f Pattern Default Settings for Drive Capacity 2.2~45kW for 240V Class (Continued)Parameter No.Name Unit Factory Se

Page 263

6-118Table 11 V/f Pattern Default Settings for Drive Capacity 55~300kW for 240V Class (Continued)Parameter No.Name Unit Factory SettingE1-03 V/f Patte

Page 264

Individual Functions6-119Fig 6.63 User-Set V/f PatternIf one of the custom V/f patterns is selected, then parameters E1-04 through E1-13 will determi

Page 265

6-120 Torque ControlWith flux vector control or open-loop vector control 2, the motor's output torque can be controlled by a torquereference fro

Page 266

Individual Functions6-121d5-05Speed Limit BiasSets the speed limit bias as a percentage of the maximum output frequency (E1-04). Bias is given to the

Page 267 - Function Contents (100%)

6-122* Factory setting will change according to the control mode (factory settings for Flux Vector Control are shown here).Multi-function Contact Inpu

Page 268 -  Motor Overload Protection

Connection Diagram2-3IMPORTANT1. Control circuit terminals are arranged as shown below.2. The output current capacity of the +V terminal is 20 mA.3.

Page 269 - Setting Motor Rated Current

Individual Functions6-123Inputting Torque References and Torque Reference DirectionsThe torque reference can be changed according to an analog input

Page 270

6-124Speed Limiter and Priority Circuit (Speed Limit Function)If the external torque reference and load are not balanced during torque control, the m

Page 271

Individual Functions6-125Fig 6.65 Speed Limit Bias SettingTorque Limit Operation ExamplesOperation examples will be described separately for winding

Page 272 - Error Code Details

6-126Torque Reference AdjustmentConsider the following information when adjusting the torque.Torque Reference Delay Time: d5-02The time constant of t

Page 273

Individual Functions6-127Speed/Torque Control Switching FunctionIt is possible to switch between speed control and torque control when one of the mul

Page 274 - Continuing Operation

6-128A timing chart for switching between speed and torque control is shown in the following figure.Fig 6.66 Speed/Torque Control Switching Time Char

Page 275 - Setting Precautions

Individual Functions6-129Related Parameters* 1. Factory settings will change depending on the control mode.* 2. The setting range becomes 1.00 to 300

Page 276 -  Speed Search

6-130Multi-function Contact Input Functions (H1-01 to H1-10)Speed Control (ASR) Gain Adjustment for Vector ControlUse the following procedure to adju

Page 277

Individual Functions6-131Fine AdjustmentsWhen you want even finer gain adjustment, adjust the gain while observing the speed waveform. Parametersettin

Page 278

6-132Adjusting ASR Integral Time 1 (C5-02)This parameter sets the speed control (ASR) integral time.Lengthening the integral time lowers the responsiv

Page 279 - Estimated Speed Search

2-4Terminal Block ConfigurationThe terminal arrangement for 200-240 V Class Drives are shown in Fig 2.2 and Fig 2.3.Fig 2.2 Terminal Arrangement (200

Page 280

Individual Functions6-133High-speed Gain Adjustments (C5-01, C5-02)Adjust these parameters at normal operating speed. Increase C5-01 (ASR proportional

Page 281

6-134Gain Adjustments at Minimum Output FrequencyOperate the motor at the minimum output frequency. Increase C5-03 (ASR proportional gain 2) to a leve

Page 282

Individual Functions6-135Setting Precautions• Droop control is disabled if b7-01 is set to 0.0.• Set b7-01 to the amount of slip as the percentage of

Page 283 -  Application Precautions

6-136Related ParametersParameter NumberNameDescriptionSetting RangeFactory SettingChange during OperationControl MethodsDisplayV/fV/f with PGOpenLoop

Page 284 - Drive Protection

Individual Functions6-137Multi-function Contact Input Functions (H1-01 to H1-10)Multi-function Contact Output Functions (H2-01 to H2-03)To output the

Page 285

6-138Time ChartA time chart for the zero servo function is given in Fig 6.74 Time Chart for Zero Servo.Fig 6.74 Time Chart for Zero ServoApplicatio

Page 286 - Input Terminal Functions

Digital Operator Functions6-139Digital Operator FunctionsThis section explains the Digital Operator functions. Setting Digital Operator FunctionsYou

Page 287

6-140o2-01Local/Remote Key Function SelectionDetermines if the Digital Operator Local/Remote key is functional.0: Disabled1: Enabled 0 to 1 1 NoAAAA

Page 288 - Ramp Hold)

Digital Operator Functions6-141Changing Frequency Reference and Display UnitsSet the Digital Operator frequency reference and display units using par

Page 289 - Application Precautions

6-142Initializing Changed Parameter ValuesYou can save to the Drive parameter set values that you have changed as parameter initial values. Change th

Page 290 - Precautions

Wiring Main Circuit Terminals2-5Wiring Main Circuit Terminals Applicable Wire Sizes and Closed-loop ConnectorsSelect the appropriate wires and crim

Page 291

Digital Operator Functions6-143 Copying ParametersThe Digital Operator can perform the following three functions using the built-in EEPROM (non-volat

Page 292

6-144Storing Drive Set Values in the Digital Operator (READ)To store Drive set values in the Digital Operator, make the settings using the following

Page 293

Digital Operator Functions6-145Error displays and their meanings are shown below. (Refer to Chapter 7 Errors when Using the Digital Oper-ator Copy Fu

Page 294 - (FJOG/RJOG)

6-146During the copy operation, errors may occur. If an error is displayed, press any key to cancel the error displayand return to the 03-01 display.

Page 295 - (External Fault Function)

Digital Operator Functions6-147Comparing Drive Parameters and Digital Operator Parameter Set Values (VERIFY)To compare Drive parameters and Digital O

Page 296 - Monitor Parameters

6-148An error may occur during the comparison. If an error is displayed, press any key to cancel the error displayand return to the o3-01 display. Err

Page 297

Digital Operator Functions6-149 Setting a PasswordWhen a password is set in A1-05, if the set values in A1-04 and A1-05 do not match, you cannot refe

Page 298

6-150Related ParametersParameter NumberName DescriptionSetting RangeFactory SettingChange during OperationControl MethodsV/f V/f with PGOpenLoopVecto

Page 299

Options6-151OptionsThis section explains the Drive option functions. Performing Speed Control with PGThis section explains functions with V/f control

Page 300 - External power supply

6-152F1-05PG Rotation Selection0: Fwd=C.C.W. - Phase A leads with forward run command. (Phase B leads with reverse run command.)1: Fwd=C.W. - Phase B

Page 301 - Individual Functions

2-6Table 2.1 200-240 V Class Wire SizesDrive ModelCIMR-Terminal SymbolTerminal ScrewsClamping Torq u elb•in(N•m)Terminal Block Acceptable Wire Range

Page 302

Options6-153* Factory setting will change according to the control mode (factory settings for Vector Control w/PG are shown here).Using PG Speed Cont

Page 303

6-154Fig 6.75 PG Rotation Direction SettingGenerally, PG is A-phase driven when rotation is clockwise (CW) see from the input axis. Also, motor rota-

Page 304

Options6-155Setting PG Pulse Monitor Output Dividing RatioThis function is enabled only when using PG speed control card PG-B2. Set the dividing rati

Page 305 - Message Format

6-156 Using Digital Output CardsThere are two types of Drive digital output cards:• DO-02CRelay contact output (DPDT contact)• DO-086 photocoupler ou

Page 306 - MODBUS Message Example

Options6-157Setting Output Items for the DO-02C Digital Output CardIf using DO-02C Digital Output Card, set the output items using F5-01 and F5-02.S

Page 307

6-158F5-09 Set to 0F5-09 Set to 1The following table shows the code outputs.F5-09 Set to 2Output depends on the settings in F5-01 to F5-08.Set ValueTe

Page 308 - Data Tables

Options6-159 Using an Analog Reference CardWhen using a AI-14B or A1-14U Analog Reference Card, set parameter b1-01 (Reference selection) to 3(Option

Page 309 - Monitor Data

6-160Related ParametersParameter NumberNameDescriptionSetting RangeFactory SettingChange during OperationControl MethodsDisplayV/f V/f with PGOpenLoo

Page 310

Options6-161Selecting Input Terminal Functions for the DI-16H2 Digital Reference CardThe frequency reference from the DI-16H2 Card is determined by t

Page 311 - ENTER Command

6-162Application PrecautionsThe DI-08 will not function if F3-01 is set to 6Selecting the Digital ReferenceThe range of the digital references is de

Page 312 - Slave Not Responding

Wiring Main Circuit Terminals2-7* The wire thickness is set for copper wires at 75°CG7U2037R/L1, S/L2, T/L3, , 1 U/T1, V/T2, W/T3, R1/L11, S1/L21,

Page 313 - Self-Diagnosis

Options6-163DI-08 Reference RangesWhen using the DI-08, the following ranges can be set depending on the settings of the parameters.o1-03 F3-01Switch

Page 315 -  Using PID Control

TroubleshootingThis chapter describes the fault displays and countermeasure for the Drive and motor problemsand countermeasures. Protective and Diagno

Page 316 - Adjustment

7-2Protective and Diagnostic FunctionsThis section describes the alarm functions of the Drive. The alarm functions include fault detection, alarmdetec

Page 317

Protective and Diagnostic Functions7-3UV1DC Bus UndervoltMain Circuit UndervoltageThe main circuit DC voltage is below the Undervoltage Detection Leve

Page 318

7-4OH4Motor Overheat 2Motor Overheating FaultThe Drive will stop according to the setting of L1-04.The motor has overheated.Check the size of the load

Page 319 - PID Input Methods

Protective and Diagnostic Functions7-5UL3Undertorq Det 1Undertorque Detected 1There has been a current less than the setting in L6-02 for longer than

Page 320 - PID Fine Adjustment Methods

7-6FBLFeedback LossPID Feedback Reference LostA PID feedback reference loss was detected (b5-12 = 2) and the PID feed-back input was less than b5-13 (

Page 321

Protective and Diagnostic Functions7-7OPROper Dis-connectDigital Operator Connection FaultThe connection to the Digital Operator was broken during ope

Page 322 - PID Control Block

7-8CPF04Internal A/D ErrCPU internal A/D converter error-Try turning the power supply off and on again.The control circuit is damaged. Replace the Dri

Page 323 - PID Sleep

2-8Table 2.2 380-480 V Class Wire SizesDrive ModelCIMR-Terminal SymbolTerminal ScrewsTightening Tor qu e(N•m)Possible Wire Sizesmm2 (AWG)Recommended

Page 324 -  Energy-saving

Protective and Diagnostic Functions7-9 Alarm DetectionAlarms are detected as a type of Drive protection function that do not operate the fault contac

Page 325 -  Setting Motor Parameters

7-10OL3(blinking)Over-torque Det 1Overtorque 1There has been a current greater than the setting in L6-02 for longer than the setting in L6-03.-• Make

Page 326

Protective and Diagnostic Functions7-11EF3(blinking)Ext Fault S3External fault (Input terminal S3)An external fault was input from a multi-function in

Page 327

7-12CE(blinking)modbus Com ErrMODBUS Communications ErrorNormal reception was not possible for 2 s or longer after received control data.-Check the co

Page 328 -  Setting the V/f Pattern

Protective and Diagnostic Functions7-13 Operation ErrorsAn operation error will occur if there is an invalid setting or a contradiction between two p

Page 329

7-14OPE10V/f Ptrn Set-tingV/f data setting errorParameters E1-04, E1-06, E1-07, and E1-09 do not satisfy the following conditions:• E1-04 (FMAX) ≥ E1-

Page 330 -  E1-03 V/f Pattern Selection

Protective and Diagnostic Functions7-15 Errors During AutotuningThe errors that can occur during autotuning are given in the following table. If an

Page 331

7-16* Displayed after autotuning has been completed.V/f Over SettingV/f settings exces-sive*The torque reference exceeded 100% and the no-load torque

Page 332

Protective and Diagnostic Functions7-17 Errors when Using the Digital Operator Copy FunctionThe errors that can occur when using the copy function fr

Page 333

7-18TroubleshootingDue to parameter setting errors, faulty wiring, and so on, the Drive and motor may not operate as expectedwhen the system is starte

Page 334

iiiSafety Precautions InstallationCAUTION• Always hold the case when carrying the Drive.If the Drive is held by the front cover, the main body of the

Page 335

Wiring Main Circuit Terminals2-9G7U4030R/L1, S/L2, T/L3, , 1, U/T1, V/T2, W/T3, R1/L11, S1/L21, T1/L31M879.2 to 88(9.0 to 10.0)8 to 1/0(8 to 60)2(

Page 336

Troubleshooting7-19 If the Motor Does Not OperateUse the following information if the motor does not operate.The motor does not operate when the RUN

Page 337 -  Torque Control

7-20The operation method selection is wrong.If parameter b1-02 (reference selection) is set to 0 (Digital Operator), the motor will not operate when a

Page 338

Troubleshooting7-21 If the Direction of the Motor Rotation is ReversedIf the motor operates in the wrong direction, the motor output wiring is faulty

Page 339 - Monitor Function

7-22 If the Motor Operates Higher Than the ReferenceUse the following information if the motor operates higher than the reference.The analog frequen

Page 340

Troubleshooting7-23 If Motor Deceleration is SlowUse the following information when the motor deceleration is slow.The deceleration time is long eve

Page 341

7-24 If the Motor OverheatsTake the following steps if the motor overheats.The load is too big.If the motor load is too heavy and the motor is used

Page 342

Troubleshooting7-25 If the Ground Fault Interrupter Operates When the Drive is RunThe Drive performs internal switching, so there is a certain amount

Page 343 - Torque Reference Adjustment

7-26Oscillation and hunting are occurring with V/f w/PG control.The gain adjustment may be insufficient. Adjust the various types of speed control lo

Page 344

Troubleshooting7-27 If Output Frequency Does Not Rise to Frequency ReferenceUse the following information if the output frequency does not rise to th

Page 346

2-10* The wire thickness is set for copper wires at 75°C.*1Wire size range provided for Drives using insulated screw-type terminal blocks with a singl

Page 347

Maintenance andInspectionThis chapter describes basic maintenance and inspection for the Drive. Maintenance and Inspection...

Page 348 - The proportional gain is low

8-2Maintenance and Inspection Outline of MaintenanceThe maintenance period of the Drive is as follows:Maintenance Period: Within 18 months of shippin

Page 349

Maintenance and Inspection8-3 Periodic Maintenance of PartsThe Drive is configured of many parts, and these parts must be operating properly in order

Page 350

8-4 Cooling Fan Replacement Outline200-240 V and 380-480 V Class Drives of 15 kW or LessA cooling fan is attached to the bottom of the Drive.If the

Page 351 -  Droop Control Function

Maintenance and Inspection8-5200-240 V and 380-480 V Class Drives of 18.5 kW or MoreA cooling fan is attached to the top panel inside the Drive.The c

Page 352 -  Zero-servo Function

8-6 Removing and Mounting the Control Circuit Terminal CardThe control circuit terminal card can be removed and mounted without disconnecting the cab

Page 353

SpecificationsThis chapter describes the basic specifications of the Drive and specifications for options andperipheral devices. Standard Drive Specif

Page 354

9-2Standard Drive SpecificationsThe standard Drive specifications are listed by capacity in the following tables. Specifications by ModelSpecificatio

Page 355

Standard Drive Specifications9-3380-480 V Class* 1. The maximum applicable motor output is given for a standard 4-pole Yaskawa motor. When selecting

Page 356 - Digital Operator Functions

9-4 Common SpecificationsThe following specifications apply to both 200-240 V and 380-480 V Class Drives.* 1. Rotational autotuning must be performed

Page 357

Wiring Main Circuit Terminals2-11Table 2.3 Closed-loop Connector Sizes (JIS C2805) (200-240 V Class and 380-480 V Class)Wire Size * Terminal ScrewR

Page 358 - Disabling the STOP Key

Specifications of Options and Peripheral Devices9-5Specifications of Options and Peripheral DevicesThe following options and peripheral devices can be

Page 359 - Enter Key

9-6The following Option Cards are availableTable 9.5 Option Cards Type NameCode NumberFunctionDocument NumberBuilt-in (con-nect to con-nector)Speed (

Page 360 -  Copying Parameters

Specifications of Options and Peripheral Devices9-7Built-in (con-nect to con-nector)PG Speed Con-trol CardsPG-A273600-A012XUsed for V/f with PG contro

Page 361 - A1 - 00=1

9-8* Under development.Built-in (con-nected to con-nector)Com-muni-cations Option CardsDeviceNet Communica-tions Inter-face Card SI-N73600-C021XUsed t

Page 362

AppendixThis chapter provides precautions for the Drive, motor, and peripheral devices and also provides lists of parameters. Varispeed G7 Control Mod

Page 363 - Copy Function.)

10-2Varispeed G7 Control ModesDetails of the Varispeed G7-Series Drive control modes and their features are provided in this section. Control Modes a

Page 364 - DATA VERIFYING

Varispeed G7 Control Modes10-3* 1. The variable speed control range. (For continuous operation, the motor's temperature rise must be considered.)

Page 365 - VERIFY ERROR

10-4Application Function PrecautionsObserve the following precautions when using the application functions.• Perform rotational autotuning during tri

Page 366 - Operation

Varispeed G7 Control Modes10-5With torque control, operate within a speed control range of 1:10 on the regenerative side.Precautions on Setting Parame

Page 367

10-6V/f Control without PG (A1-02 = 0)V/f control without a PG is suitable for applications where multiple motors are operated with a single Drive, s

Page 368

2-124/0 100M10 100 - 10M12 100 - 12M16 100 - 16250 / 300MCM 125 / 150M10 150 - 10M12 150 - 12M16 150 - 16400MCM 200 M12 200 - 12650MCM 325M12 x 2 325

Page 369

Drive Application Precautions10-7Drive Application PrecautionsThis section provides precautions for selecting, installing, setting, and handling Drive

Page 370 - Setting Number of PG Pulses

10-8 InstallationObserve the following precautions when installing Drive.Installation in EnclosuresEither install the Drive in a clean location not

Page 371

Drive Application Precautions10-9 HandlingObserve the following precautions when wiring or performing maintenance for Drive.Wiring CheckThe Drive wi

Page 372 - Detecting Motor Overspeed

10-10Motor Application PrecautionsThis section provides precautions for motor application. Using the Drive for an Existing Standard MotorWhen a stand

Page 373 -  Using Digital Output Cards

Motor Application Precautions10-11 Using the Drive for Special MotorsObserve the following precautions when using a special motor.Pole-changing Moto

Page 374

10-12Conformance to UL and CE MarkingsInformation regarding conformance to UL and CE markings is provided in this section. CE MarkingsCE markings ind

Page 375 - F5-09 Set to 2

Conformance to UL and CE Markings10-13Input FusesIn order to conform to the Low Voltage Directive or UL, fuses must be provided for inputs. Use UL-com

Page 376

10-14380-480 V class40P4 480 5 16 to 660 CR6L-20/UL FUJI600 V20 A2640P7 480 10 19 to 660 CR6L-20/UL FUJI600 V20 A2641P5 480 10 46 to 660 CR6L-30/UL FU

Page 377

Conformance to UL and CE Markings10-15EMC DirectiveVarispeed G7-Series Drives satisfy testing for conformance to the EMC Directive under the conditio

Page 378

10-16Fig 10.7 Installation Method for Filter and Drive (CIMR-G7U2022 to 2110, 4022 to 4300)Table 10.3 EMC Noise FiltersVoltage ClassDrive Model Numb

Page 379

Wiring Main Circuit Terminals2-13 Main Circuit Terminal FunctionsMain circuit terminal functions are summarized according to terminal symbols in Ta

Page 380 - DI-08 Reference Ranges

Conformance to UL and CE Markings10-17380-480 V class40P4Under development --- --- ---40P741P5Under development --- --- ---42P243P744P045P547P5Under d

Page 381

10-18 UL MarkingsThe G7 is UL listed to UL Standard 508C, UL FILE No.: E13145. Conformance to UL StandardTo comply with UL standard, follow the appr

Page 382 - Troubleshooting

Conformance to UL and CE Markings10-19Control Circuit TerminalA UL Listed, Class 2 power supply must be used for the control circuits. See Table 10.6

Page 383 -  Fault Detection

10-20User ParametersFactory settings are given in the following table. These setting are for a 200-240 V Class Drive of 0.4 kWset to factory set contr

Page 384

User Parameters10-21C3-01 Slip compensation gain1.0*3d3-01 Jump frequency 1 0.0C3-02Slip compensation primary delay time200*2d3-02 Jump frequency 2 0.

Page 385

10-22E3-05Motor 2 mid. output frequency 1 (FB)3.0 *2F4-08Analog output signal level for channel 20E3-06Motor 2 mid. output frequency voltage 1 (VC)12.

Page 386

User Parameters10-23H3-05Multi-function analog input (termi-nal A3)2 L2-04 Voltage recovery time 0.3H3-06 Gain (terminal A3) 100.0 L2-05 Undervoltage

Page 387

10-24* 1. Not initialized. (Japanese standard specifications: A1-01 = 1, A1-02 = 2)* 2. The factory setting will change if the control method is chang

Page 388

IndexIndex-1Symbols+/- speed, 6-75Numerics2-wire sequence, 6-73-wire sequence, 6-8AAC reactor, 2-17acceleration and deceleration times, 6-15advanced p

Page 389

Index-2IndexFFBL Feedback Loss, 7-6, 7-11FJOG, 6-77forward/reverse run commands input together, 7-9frequency reference, 6-2, 6-25fuse blown, 7-2Ggroun

Page 390 -  Alarm Detection

2-14 Main Circuit ConfigurationsThe main circuit configurations of the Drive are shown in Table 2.5.Table 2.5 Drive Main Circuit ConfigurationsNote

Page 391

IndexIndex-3OPE09, 7-13OPE10 V/f Ptrn Setting, 7-14open chassis type, 1-4open-loop vector control, 4-9operation errors, 7-13OPR Oper Disconnect, 7-7op

Page 392

VV/f control, 4-8V/f control with PG, 4-8V/f pattern, 6-111, 6-113verify mode, 3-5, 3-13Wwatchdog timer fault, 7-8wire size, 2-22wiring, 2-1, 2-36

Page 393 - (blinking)

Drives Technical Support in USA and CanadaTechnical Support for Drives and Drives is available by phone as follows:Normal: Monday through Friday durin

Page 395

G7 DriveYASKAWA ELECTRIC AMERICA, INC.Drives Division 16555 W. Ryerson Rd., New Berlin, WI 53151, U.S.A.Phone: (800) YASKAWA (800-927-5292) Fax: (

Page 396 -  Errors During Autotuning

Wiring Main Circuit Terminals2-15 Standard Connection DiagramsStandard Drive connection diagrams are shown in Fig 2.4. These are the same for both

Page 397

2-16 Wiring the Main CircuitsThis section describes wiring connections for the main circuit inputs and outputs.Wiring Main Circuit InputsObserve the

Page 398

Wiring Main Circuit Terminals2-17Installing a Magnetic ContactorIf the power supply for the main circuit is to be shut off during a sequence, a magn

Page 399

2-18• Incorrect Noise Filter InstallationFig 2.7 Incorrect Power supply Noise Filter InstallationWiring the Output Side of Main CircuitObserve the f

Page 400

ivWarning Information and PositionThere is warning information on the Drive in the position shown in the following illustration.Always heed the warnin

Page 401

Wiring Main Circuit Terminals2-19Do Not Use an Electromagnetic SwitchNever connect an electromagnetic switch (MC) between the Drive and motor and tu

Page 402

2-20Countermeasures Against Radio InterferenceRadio noise is generated from the Drive as well as from the input and output lines. To reduce radio nois

Page 403

Wiring Main Circuit Terminals2-21Connecting the Braking Resistor (ERF)A Braking Resistor that mounts to the Drive can be used with 200-240 V and 38

Page 404 - If Motor Deceleration is Slow

2-22Wiring Control Circuit Terminals Wire Sizes and Closed-loop ConnectorsFor remote operation using analog signals, keep the control line length bet

Page 405 -  If the Motor Overheats

Wiring Control Circuit Terminals2-23 Control Circuit Terminal FunctionsThe functions of the control circuit terminals are shown in Table 2.10. Use

Page 406

2-24Analog input signals+V +15 V power output+15 V power supply for analog inputor transmitters+15 V (Max. current: 20 mA)-V -15 V power output-15 V p

Page 407

Wiring Control Circuit Terminals2-25Relay outputsMAFault output signal (NO contact)MA / MC: Closed during fault conditionMB / MC: Open during fault

Page 408

2-26* 1. For a 3-wire sequence, the default settings are a 3-wire sequence for S5, multi-step speed setting 1 for S6 and multi-step speed setting 2 fo

Page 409

Wiring Control Circuit Terminals2-27The functions of DIP switch S1 are shown in the following table.The functions and positions of CN15 are shown in

Page 410 - Inspection

2-28 Sinking/Sourcing ModeThe multi-function input terminal logic can be switched between sinking mode (0 Vdc common) and sourcingmode (+24 Vdc commo

Page 412 - Periodic Maintenance of Parts

Wiring Control Circuit Terminals2-29 Control Circuit Terminal ConnectionsConnections to Drive control circuit terminals are shown in Fig 2.16.Fig 2

Page 413 - Fan cover

2-30 Control Circuit Wiring PrecautionsObserve the following precautions when wiring control circuits. • Separate control circuit wiring from main ci

Page 414

Installing and Wiring Option Cards2-31Installing and Wiring Option Cards Option Card Models and SpecificationsUp to three Option Cards can be mount

Page 415 - Control Circuit Terminal Card

2-32 InstallationBefore mounting an Option Board, remove power from the Drive and wait for the CHARGE LED to go out. Remove the Digital Operator, fro

Page 416 - Specifications

Installing and Wiring Option Cards2-33 PG Speed Control Card Terminals and SpecificationsThe terminal specifications for the PG Speed Control Cards

Page 417 - Standard Drive Specifications

2-34PG-B2The terminal specifications for the PG-B2 are given in the following table.PG-D2The terminal specifications for the PG-D2 are given in the

Page 418 - 4132 4160 4185 4220 4300

Installing and Wiring Option Cards2-35PG-X2The terminal specifications for the PG-X2 are given in the following table.* 5 Vdc and 12 Vdc cannot be

Page 419 -  Common Specifications

2-36 Wiring Wiring examples are provided in the following illustrations for the Control Cards. Wiring the PG-A2Wiring examples are provided in the f

Page 420

Installing and Wiring Option Cards2-37Fig 2.21 I/O Circuit Configuration of the PG-A2PG powersupply+12 VdcShort for open-collector inputPulseinputP

Page 421

2-38 Wiring the PG-B2 Wiring examples are provided in the following illustrations for the PG-B2.• Shielded twisted-pair wires must be used for signal

Page 422

viRegistered TrademarksThe following registered trademarks are used in this manual.• DeviceNet is a registered trademark of the ODVA (Open DeviceNet V

Page 423 - * Under development

Installing and Wiring Option Cards2-39Wiring the PG-D2 Wiring examples are provided in the following illustrations for the PG-D2.• Shielded twisted

Page 424 - Appendix

2-40 Wiring Terminal BlocksUse no more than 100 meters (328 ft) of wiring for PG (encoder) signal lines, and keep them separate frompower lines.Use s

Page 425 - Varispeed G7 Control Modes

Installing and Wiring Option Cards2-41 Selecting the Number of PG (Encoder) PulsesThe setting for the number of PG pulses depends on the model of P

Page 426

2-42PG-D2/PG-X2There are 5 Vdc and 12 Vdc PG power supplies.Check the PG power supply specifications before connecting.The maximum response frequency

Page 427

Digital Operator and ModesThis chapter describes Digital Operator displays and functions, and provides an overview ofoperating modes and switching bet

Page 428 - Regenerative torque

3-2Digital OperatorThe Digital Operator is used for programming, operating, monitoring, and copying the Drive’s parame-ters. To copy parameters, G7 Dr

Page 429 - Fig 10.4

Digital Operator3-3 Digital Operator KeysThe names and functions of the Digital Operator Keys are described in Table 3.1.Note Except in diagrams, Key

Page 430 -  Selection

3-4Drive Mode IndicatorsThe definition of the Drive mode indicators are shown in Table 3.2. REMOTE Sequence (SEQ) IndicatorThe status of the “REMOTE”

Page 431 -  Settings

Drive Mode Indicators3-5 Run IndicatorThe status of the “RUN” indicator is shown in Table 3.5 when the Drive is in either the “LOCAL” or “REMOTE” mod

Page 432 -  Handling

3-6 Switching ModesThe mode selection display will appear when the MENU Key is pressed from a monitor or setting display.Press the MENU Key from the

Page 433 - Motor Application Precautions

viiContents1 Handling Drives ... 1-1Varispeed G7 Introduction ...

Page 434

Drive Mode Indicators3-7 Drive ModeDrive mode is the mode in which the Drive can be operated. The following monitor displays are possible indrive mod

Page 435 -  CE Markings

3-8Example Operations Key operations in drive mode are shown in the following figure.Fig 3.2 Operations in Drive ModeNote When changing the display

Page 436 - Input Fuses

Drive Mode Indicators3-9 Quick Programming ModeIn quick programming mode, the parameters required for Drive trial operation can be monitored and set.

Page 437

3-10 Advanced Programming ModeIn advanced programming mode, all Drive parameters can be monitored and set. Parameters can be changed from the setting

Page 438 - L1L2L3PE

Drive Mode Indicators3-11Setting User ParametersHere, the procedure is shown to change C1-01 (Acceleration Time 1) from 10 s to 20 s.Table 3.8 Setti

Page 439 - L1L2L3 T1 T3T2

3-12External Fault Setting ProcedureExamples of the Digital Operator displays that appear when setting an eternal fault for a multi-functioncontact i

Page 440

Drive Mode Indicators3-13 Verify ModeVerify mode is used to display any parameters that have been changed from their default settings in aprogramming

Page 441 -  Conformance to UL Standard

3-14 Autotuning ModeAutotuning automatically tunes and sets the required motor parameters when operating in the vector controlmodes. Always perform a

Page 442 -  Motor Overheat Protection

Drive Mode Indicators3-15* TUn10 will be displayed during rotational autotuning and TUn11 will be displayed during stationary autotuning. The DRIVE in

Page 444

viii Control Circuit Wiring Precautions ... 2-30 Control Circuit Wire Si

Page 445

Trial OperationThis chapter describes the procedures for trial operation of the Drive and provides an exampleof trial operation. Trial Operation Proce

Page 446

4-2Trial Operation ProcedurePerform trial operation according to the following flowchart.Fig 4.1 Trial Operation FlowchartV/f with PG(A1-02 = 1)START

Page 447

Trial Operation Procedures4-3Trial Operation ProceduresThe procedure for the trial operate is described in order in this section. Setting the Power S

Page 448

4-4 Checking the Display StatusIf the Digital Operator's display at the time the power is connected is normal, it will read as follows:When an f

Page 449

Trial Operation Procedures4-5 Basic SettingsSwitch to the quick programming mode (“QUICK” will be displayed on the LCD screen) and then set the fol-l

Page 450

4-6Table 4.2 Parameters that Are Set as RequiredParameter NumberName DescriptionSetting RangeFactory Settingb1-03Stopping method selectionSelect stop

Page 451

Trial Operation Procedures4-7 Settings for the Control MethodsAutotuning methods depend on the control method set for the Drive. Make the settings re

Page 452

4-8Setting the Control MethodAny of the following five control methods can be set.Note With vector control, the motor and Drive must be connected 1:1

Page 453

Trial Operation Procedures4-9• Set the number of rotations per pulse in F1-01 (PG Constant). If there is a reduction gear between themotor and PG, set

Page 454

4-10Stationary Autotuning for Line-to-Line Resistance Only (T1-01 = 2)Stationary autotuning for line-to-line resistance only can be used in any contro

Comments to this Manuals

No comments