MagneTekGPD 503Technical Manual
CONTENTS - ContinuedSUBJECT PAGE- ix -2.30 Thermal Motor Overload Protection ... 2-462.31 Torque Compensation ...
B. Drive Operation From Digital Operator (Using Factory Settings):ACTIONDESCRIPTION DISPLAYApply Power DRIVE lamp is on.The Frequency Reference (An-
C. Drive Operation (2-Wire Control) By External Input Signals:ACTIONDESCRIPTION DISPLAYApply Power DRIVE lamp is on.The Frequency Reference (An-01)
ACTION DESCRIPTION DISPLAYPressPRGMKeyDRIVE lamp lights. Display shows the DRIVE Frequency Reference value as set by to Return to input at terminal 1
Section 4. INITIAL START-UP (“LOCAL” CONTROL)4.1 PRE-POWER CHECKS• Verify wires are properly connectedand no erroneous grounds exist.• Remove all
OPERATING OPERATION ATPROCEDURE DIGITAL OPERATOR DIGITAL DISPLAY DESCRIPTIONPower On Red lamp at STOP key lights. When power is applied, the last (R
OPERATING OPERATION ATPROCEDURE DIGITAL OPERATOR DIGITAL DISPLAY DESCRIPTIONFrequency EXAMPLE: Set frequencySetting command to 15 Hz:(Continued)Move t
4.3 PRE-OPERATION CONSIDERATIONS• After completing the start-up, connect the motor to the load.• Additional control circuit wiring can be added, a
Section 5. OPERATION AT LOADAfter completing the start-up, and programming of constants, turn off the AC main circuitpower. Make additional wiring c
Section 6. FAILURE INDICATION AND DETAILS6.1 GENERALA failure in the GPD 503 can fall into one of two categories.A blinking "Alarm" indic
INDICATION(DISPLAY) FAILURE INDICATION ITEM DESCRIPTIONEFSimultaneous forward and Fwd Run and Rev Run commands are both closed for (blinking) reverse
INSTALLATION REFERENCE SHEET• Drive Information: • Motor Nameplate Information:Model Number ______________ Full Load Amps ______________Specificatio
INDICATION(DISPLAY) FAILURE INDICATION ITEM DESCRIPTIONouOvervoltage Internal monitor of DC Bus voltage indicates that input (blinking) AC power is ex
6.2 DISPLAYING FAULT SEQUENCEWhenever the Fault relay trips and shuts down the GPD 503, the display code of the faultthat caused the trip (except fo
6.2 DISPLAYING FAULT SEQUENCE ContinuedB. At Power-Up.In Table 6-3, digital display A occurs if there was a Fault trip (shutdown) before turning
Section 7. TROUBLESHOOTINGIf the GPD 503 malfunctions, locate the cause and take corrective action by following theflowcharts given in this section.
TROUBLESHOOTING CHART 7.1MOTOR WILL NOT RUN"CHARGE" LAMPON MAIN PC BOARDLIT?CHECK CIRCUITBREAKER, MAGNETICCONTACTOR ANDINPUT POWER.NONONONON
TROUBLESHOOTING CHART 7.1 (Continued)AFROMPRECEDINGPAGEPROPER FREQUENCYREFERENCE INPUT?(TERMINAL 17(-) TO 13,14 OR 16)NONONONONOCHECK EXTERNALCIRCUITS
TROUBLESHOOTING CHART 7.2MOTOR STALLS DURING ACCELERATIONACCELERATION TIMETOO SHORT?YESYESYESYESYESWITH GPD 503 INSTOPPED CONDITION,EXTEND ACCELER-ATI
TROUBLESHOOTING CHART 7.3OVERVOLTAGE ( ou) FAULT INDICATIONIS INPUT AC SUPPLYVOLTAGE CORRECT?NONONONODECREASE TOPROPER VOLTAGERANGE.YESYESYESYESYESDOE
TROUBLESHOOTING CHART 7.4BLOWN FUSE ( FU) FAULT INDICATIONCAUTIONDo not replace DC Bus fuse without first checking output transistors.DISCONNECT LEADS
TROUBLESHOOTING CHART 7.5OVERCURRENT ( oC) FAULT INDICATIONDOES OUTPUTCURRENT EXCEED200% OF RATING?WITH GPD 503 IN STOPPED CON-DITION, INCREASE ACCELE
TROUBLESHOOTING / MAINTENANCE REFERENCE SHEET• Fault Code History:Date Fault Cause Solution_______ _________ ____________________ ______
TROUBLESHOOTING CHART 7.6OVERLOAD ( oL) FAULT INDICATIONLOAD TOO LARGE(MOTOR OVERHEATED)?YESYESYESYESYESYESDECREASE LOADWITHIN RATING.CHECK MOTORAND L
TROUBLESHOOTING CHART 7.7UNDERVOLTAGE ( Uu) FAULT INDICATIONIS INPUT ACSUPPLYCORRECT?NONOYESYESNOYESIS THEREAT LEAST 450VDC(FOR 460V GPD 503) OR225VDC
TROUBLESHOOTING CHART 7.8INVERTER OVERHEATED ( oH) FAULT INDICATIONIS AMBIENTTEMPERATURE45°C (113°F)OR GREATER?REDUCE AMBIENTTEMPERATURE.HEAT SINKTHER
TROUBLESHOOTING CHART 7.9CONTROL FUNCTION ERROR ( CPF) FAULT INDICATION1. CHECK THAT ALL GPD 503HARNESS CONNECTORSARE FIRMLY SEATED.2. CHECK THAT CPU
TROUBLESHOOTING CHART 7.10EXTERNAL FAULT ( EF) INDICATIONIS AN EXTERNAL FAULT SIGNALPRESENT (OPEN OR CLOSED ✱✱CIRCUIT BETWEEN TERMINAL 3 AND 11; OR OP
Appendix 1. LISTING OF CONSTANTSThe GPD 503 control circuits use five types of constants to select functions and character-istics of the GPD 503. Ch
CONSTANT INCRE- SETTING FACTORY USER PARA.NUMBER DATA NAME MENT RANGE SETTING SETTING REF.bn-01 Accel Time 1 0.1 s 0.0 - 6000.0 10
CONSTANT SET FACTORY USER PARA.NUMBER DATA NAME DIGIT DATA FUNCTION SETTING SETTING REF.Sn-01 kVA (HP) Select – – GPD 503 capacity selection See A
CONSTANT SET FACTORY USER PARA.NUMBER DATA NAME DIGIT DATA FUNCTION SETTING SETTING REF.Sn-06 Operation Mode XXXX 00 = S-curve at Accel/Decel, 0
CONSTANT SET FACTORY USER PARA.NUMBER DATA NAME DIGIT DATA FUNCTION SETTING SETTING REF.Sn-08 (Continued) XXXX Condition when CommunicationInterface C
Section 1. INSTALLATION1.1 GENERALThe GPD 503 is a high performance sine-coded pulse width modulated AC motor drivewhich generates an adjustable vo
CONSTANT SET FACTORY USER PARA.NUMBER DATA NAME DIGIT DATA FUNCTION SETTING SETTING REF.Sn-11 Protective XXXX 0 Braking resistor (heat sink 0000 S
CONSTANT SET FACTORY USER PARA.NUMBER DATA NAME DIGIT DATA FUNCTION SETTING SETTING REF.Sn-13 Protective XXXX — Not Used 0100 – – Character-istic
CONSTANT SET FACTORY USER PARA.NUMBER DATA NAME DIGIT DATA FUNCTION SETTING SETTING REF.Sn-15 Terminal 5 – – 00 – Selects terminal 5 function 03 2.1
CONSTANT SET FACTORY USER PARA.NUMBER DATA NAME DIGIT DATA FUNCTION SETTING SETTING REF.Sn-26 Digital Speed XXXX 0000 = BCD input, 1% accuracy 0000 Se
A1-10(THIS PAGE INTENTIONALLY BLANK)
CONSTANT INCRE- SETTING FACTORY USER PARA.NUMBER DATA NAME MENT RANGE SETTING SETTING REF.Cn-01 Output Voltage Regulator 0.1 V 0.0 - 255.0 230
CONSTANT INCRE- SETTING FACTORY USER PARA.NUMBER DATA NAME MENT RANGE SETTING SETTING REF.Cn-14 Frequency Command 1 % 0 - 109 100 2.14Upper L
CONSTANT INCRE- SETTING FACTORY USER PARA.NUMBER DATA NAME MENT RANGE SETTING SETTING REF.Cn-37 Momentary Power Failure 0.1 s 0.0 - 2.0 – –Rid
CONSTANT NO. MONITOR ITEM DISPLAY EXAMPLE PARA. REF.Un-01 Frequency reference (Hz)60.002.17Un-02 Output frequency (Hz)60.002.17Un-03 Output current
Appendix 2. SPECIFICATIONS230V ClassInput Power Voltage : 3 Phase 200 / 208 / 220 / 230 VAC +/– 10%Frequency : 50 / 60 Hz +/– 5%Output Power V
1.4 ELECTRICAL INSTALLATION All basic interconnections (using the Digital Operator) are shown in Figures 1-3through 1-6.1.4.1 Main Circuit Input
SECTION C. ALL GPD 503sControl Method Sine Wave PWMDigital command: 0.01% (-10 to 40oC)(+14 to 104oF)Frequency AccuracyAnalog command: 0.1% (15 to
SECTION C. ALL GPD 503s (CONTINUED)Control Braking Torque Approximately 20%Characteristics(continued) V/F Pattern Selection 15 Standard Patterns:4 f
Appendix 3. GPD 503 CAPACITYSystem Constant Sn-01 (GPD 503 Capacity) is factory preset per the voltage and horse-power ratings of the GPD 503. Tabl
HP Motor Rated Current Reference Current ForSn-01 Rating Max Motor Output Current (Amps) (Cn-09) Setting Constants (Amps)Set Value (CT) HP
Appendix 4. DIODE AND TRANSISTOR MODULE RESISTANCE TESTDIODE MODULEMeasure the resistance across the module terminals with a volt-ohm meter. Set the
IGBT TRANSISTOR MODULEMeasure the resistance across the module terminals with a volt-ohm meter. Set the meterto the X1 range. Measured resistance sh
RATING PHYSICAL DIMENSIONS MOUNTING ENCLOSURE (IN.) DIM. (IN.) WEIGHTVOLTS HPTYPE (LB)CT VT H W D H1 W11 1 NEMA 1 11.9
RATING PHYSICAL DIMENSIONS MOUNTING ENCLOSURE (IN.) DIM. (IN.) WEIGHTVOLTS HP TYPE (LB)H W D H1 W12 3 NEMA 1 13.94 8.05 6.50 13.19 7
Appendix 6. SPARESA6-16611DS305DS302DS306DS307DS308DS309DS310DS311DS322DS323Part No.502078__501848__501739__Model No.DC Bus Fuse11DS313DS304DS314DS3
A6-2Part No.502079__502078__501739__Model No.DC Bus Fuse1DS075DS100DS150DS200Diode ModuleGate Driver PCBControl PCB9873727119Fan586360 61 621514090807
HP TERMINAL WIRE SIZERATING TERMINAL SYMBOL SCREW AWG MM2DS305 L1 (R), L2 (S), L3 (T), –, B1/+, B2, T1 (U), T2 (V), T3 (W),
Appendix 7. DYNAMIC BRAKING CONNECTIONSGENERAL. Dynamic braking (DB) enables the motor to be brought to a smooth and rapidstop. This is achieved by
INSTALLATIONThis option must be installed by a TECHNICALLY QUALIFIED INDIVIDUAL who is familiarwith this type of equipment and the hazards involved.WA
Braking Resistor (Heat Sink Mount) Installation1. Remove the drive from its mounting for access to the rear of the heat sink.2. Mount the Braking Resi
Braking Resistor Unit Installation (for 230V 1-10HP(CT), 460V 1-20HP(CT), 575V 2-25HP(CT) drives)IMPORTANTSince the Braking Resistor Unit generates he
Braking Unit(s) and Braking Resistor Unit(s) Installation (for 230V 15HP(CT) andabove, 460V 25HP(CT) and above, 575V 30HP(CT) and above)IMPORTANTSince
6. The Braking Unit and Braking Resistor Unit MUST BE GROUNDED. Observe thefollowing precautions:• Use grounding leads conforming to your National E
A7-7Figure A7-5. Wiring Multiple Braking Units and Braking Resistor Units to Drive(230V 40-100HP(CT), 460V 75-400HP(CT), 575V 60-200HP(CT))T1T2T3RSTU
8. IMPORTANT: After wiring, test insulation resistance of each Braking Unit/BrakingResistor Unit with a 900V megger as follows:a. Disconnect leads bet
Please send information on the following:❑ DDM™ DriveDataManagerA program to create and edit configuration files for MagneTek AC drives.A program to u
Free set of plastic coated pocket sizedcards which provide to the user a rapidreference for programming GPD 503constants. For your free set, complete
DRIVE TERMINAL WIRE SIZEMODEL NO. TERMINAL SYMBOL SCREW AWG mm2DS313, DS304,L1 (R), L2 (S), L3 (T), –, B1/+, B2, T1 (U), T2 (V), T3
MagneTekData subject to change without notice. GPD and DDM are trademarks of MagneTek, Inc.MagneTekDrives & Systems16555 West Ryerson RoadNew Berl
1-2.3DRIVE TERMINAL WIRE SIZEMODEL NO. TERMINAL SYMBOL SCREW AWG mm2DS5003, L1 (R), L2 (S), L3 (T), –, B1/+, B2, T1 (U), T2 (V), T3
1-2.4SECTION A. 230V TERMINAL FUNCTION1 HP 3 TO 40 HPL1 (R)Three phase Main circuit input power supplyL2 (S)200 / 208 / 220V at 50 Hz; 200 / 208 / 22
1-3SECTION C. 575V TERMINAL FUNCTION 1 HP 3 TO 40 HPL1 (R) Three phase Main circuitL2 (S) input power supplyL3 (T) 500 / 575 / 600V at 50/60 HzT1 (U)
- i -GPD 503 SIMPLIFIED START-UP PROCEDURE This procedure will quickly get you up and running by Digital Operator keypad or user suppliedremote opera
1.4 ELECTRICAL INSTALLATION Continued1.4.2 Control CircuitAll basic control circuit (signal) interconnections are shown in the appropriate diag
TERMINAL FUNCTIONS LEVELS1 2-WIRE CONTROL: Forward Run / Stop signal Run at closed, stop at open (See NOTE 2)(See NOTE 1)3-WIRE CONTROL: Run signal Ru
•• •••• ••• •CORRECT CORRECT NOTACCEPTABLETERMINAL FUNCTIONS LEVELS21 Multi-function analog monitor (+) Output current or Type of analog signal (o
1.4 ELECTRICAL INSTALLATION Continued1.4.4 Auxiliary Input and Output Power Option DevicesFigure 1-2 is a factory guideline for proper wiring p
NOTES FOR FIGURE 1-3✱ – Indicates components not supplied. – Indicates customer connection terminal. Wire only to terminals shown. ( ) – Indica
1-93ø POWER SUPPLY (SEE NAMEPLATE DATA)1CB ✱GPD 503 L1 L2 L3151617121413V/HZ PROFILE+15Vdc(20mA MAX)MAN REF. IN(0 TO 10Vdc)FWD▲▲▲▲▲
NOTES FOR FIGURE 1-4✱ – Indicates components not supplied. – Indicates customer connection terminal. Wire only to terminals shown. ( ) – Indicat
1-113ø POWER SUPPLY (SEE NAMEPLATE DATA)1CB ✱GPD 503 L1 L2 L3151617121413V/HZ PROFILE+15Vdc(20mA MAX)MAN REF. IN(0 TO 10Vdc)RUN▲▲▲▲
1-12NOTES FOR FIGURE 1-5✱ – Indicates components not supplied. – Indicates customer connection terminal. Wire only to terminals shown. ( ) – In
1-133ø POWER SUPPLY (SEE NAMEPLATE DATA)1CB ✱GPD 503 L1 L2 L3151617121413V/HZ PROFILE+15Vdc(20mA MAX)MAN REF. IN(0 TO 10Vdc)FWD▲▲▲▲
INSTALLATION OF EXTERNAL RUN/STOP SWITCH AND SPEED POTENTIOMETERSIMPORTANT: Complete the INSTALLATION and KEYPAD OPERATION instructions before attemp
1-14NOTES FOR FIGURE 1-6✱ – Indicates components not supplied. – Indicates customer connection terminal. Wire only to terminals shown. ( ) – Ind
1-153ø POWER SUPPLY (SEE NAMEPLATE DATA)1CB ✱GPD 503 L1 L2 L3151617121413V/HZ PROFILE+15Vdc(20mA MAX)MAN REF. IN(0 TO 10Vdc)RUN▲▲▲▲
Section 2. PROGRAMMABLE FEATURES2.1 GENERALThis section describes features of the GPD 503 which are defined by programmed settingsin the various co
RUNNINGCritical Frequency Rejection 2.7 Cn-16 thru Cn-19Speed Coincidence 2.23 Cn-21, Cn-22Carrier Frequency 2.37 Cn-23, -24, -25Speed Search 2.28 Sn-
2.2 ACCEL/DECEL TIMEA. bn-01: Accel Time 1 Factory setting (each): 10.0secondsbn-02: Decel Time 1Range (each): 0.0 to 6000.0 secondsbn-03: Accel T
2.3 AUTO REFERENCE CHARACTERISTICSSn-06: Operation Mode Digit 3 [ X X X X ] : Auto ReferenceSelect 3 CharacteristicsFactory setting: X 0X X (0 - 1
2.4 AUTO REFERENCE - LOSS DETECTIONSn-06: Operation Mode Digit 4 [ X X X X ] : Auto Reference Select 3 Loss DetectionFactory setting: 0X X X (disa
2-6(THIS PAGE INTENTIONALLY BLANK)
2-72.5 AUTO-RESTARTA. Cn-36: Number of Auto-Restart Attempts Factory setting: 00Range: 00 - 10When a fault occurs during operation, the GPD 503 ca
2.7 CRITICAL FREQUENCY REJECTIONA. Cn-16: Prohibited Frequency 1Factory setting (each): 0.0Cn-17: Prohibited Frequency 2Cn-18: Prohibited Frequency
IMPORTANT: Programming is required to set up the drive for operation from external terminals.6. Replace cover, make sure remote switch S1 is in “Stop”
2.8 DC INJECTION BRAKINGA. Sn-04: Operation Mode Select 1 Digits 3 & 4 [ X X X X ] : MotorStopping Method SelectionFactory setting: 0 0X XCn-1
2.8 DC INJECTION BRAKING ContinuedB. Cn-10: DC Inj. Braking Start Frequency Range: 0.0 to 10.0 HzCn-11: DC Inj.Braking Current Factory settin
2.8 DC INJECTION BRAKING ContinuedC. Sn-19: Multi-function Analog Data07: DC Injection BrakingInput (Term. 16) Current AdjustThe multi-functio
2.9 DIGITAL DISPLAY SELECTIONCn-20: Operator Display Mode Factory setting: 0Reference and IndicationRange: 0 to 39999This constant designates what
2.9 DIGITAL DISPLAY SELECTION ContinuedCAUTIONWhen setting a 5 digit value in Cn-20, the decimal pointposition selected will also automatically
2.11 ENERGY SAVING OPERATIONbn-09: Energy Saving Gain Factory setting: 80%Range: 0 to 200 %This constant sets, in increments of 1%, the level to
2.12 EXTERNAL FAULT INPUTSA. Sn-12: External Fault Signal Input Factory setting: 0100(Terminal 3)This constant determines how the GPD 503responds
2.12 EXTERNAL FAULT INPUTS ContinuedB. Sn-15 thru Sn-18: Multi-function Data 20 - 2F: External Fault 1 (terminal 5)Inputs (Term. 5 thru 8) Dat
2.13 FREQUENCY (AUTO) COMMAND BIAS/GAINbn-05: Frequency Command Gain Factory setting: 100.0%Range: 0.0 to 1000.0 %Sets the auto-speed frequency c
2.14 FREQUENCY COMMAND UPPER & LOWER LIMITSCn-14: Frequency Command Upper Limit Factory setting: 100%Range: 0 to 109 %Cn-15: Frequency Comman
- iv -Cn-29 50Cn-30 160Cn-31(4)Cn-32(4)Cn-33(4)Cn-34 30 (3)Cn-35 2.0Cn-36 0Cn-37(4)Cn-38 150Cn-39 2.0 (4)Cn-40(4)Cn-41 100Cn-42 0.3Un-01 N/A N/AUn-02
2.15 JOG REFERENCEAn-09: Jog Reference Factory setting: 6.00HzRange: 0.00 to 400.00 HzWhen jog operation is selected (either by the Digital Operat
2.15 JOG REFERENCE ContinuedEXAMPLES: (Continued)OPERATION BY REMOTE SIGNAL INPUT (RUN & JOG)JOG2 – 2-WIRE CONFIGURATIONSn-04 = 0000(Remot
2.15 JOG REFERENCE ContinuedEXAMPLES: (Continued)JOG2 – 3-WIRE CONFIGURATIONSn-04 = 0000(Remote Control)2-20.1NOTES:1. Use of external Jog inp
2.16 MOMENTARY POWER LOSS RIDE-THRUSn-11: Protective Characteristics Digit 3 [ X X X X ] : Power Loss Select 2 Ride-thru ProtectionX 0X X = Disabl
2.17 MONITOR DISPLAY (DIGITAL OPERATOR)While in the Drive mode, different information will appear on the Digital Operator display when each of the U
2.18 MULTI-FUNCTION ANALOG INPUT (Term. 16)Sn-19: Multi-function Analog Input (Term. 16)Programming Sn-19 per the chart below con-figures terminal 1
Sn-19 = 00100%FREQUENCYREF.0%0V 10VMULTI-FUNCTION ANALOG INPUTSn-19 = 012.00FGAINE 1.000V 5V 10VMULTI-FUNCTION ANALOG INPUTSn-19 = 0210%FBIAS10%0V 10V
2.19 MULTI-FUNCTION INPUT TERMINALS (Term. 5-8)Sn-15: Terminal 5 Function Factory settings (for 2-wire control):Sn-16: Terminal 6 Function Sn-15 = 0
2.19 MULTI-FUNCTION INPUT TERMINALS (Term. 5-8) ContinuedDESCRIPTIONDATA FUNCTION Signal Levels: 0 = state; 1 = pulse00FWD/REV selection (for
2.19 MULTI-FUNCTION INPUT TERMINALS (Term. 5-8) ContinuedData 01: Remote/LocalSet digits of Sn-04 to X X 0 0 to select external inputs as the sou
-v-Horsepower RangeRATEDHORSEPOWERMODELINPUTCT (150% OL) VT (125% OL) NO.1 1 DS3052 2 DS3023 3 DS3065 5 DS3077.5 7.5/10 DS3082 10 15 DS3093 15 20 DS31
2.19 MULTI-FUNCTION INPUT TERMINALS (Term. 5-8) ContinuedData 08: External Base Block by N.O. Contact• When either the Forward Run command or Rev
2-282.19 MULTI-FUNCTION INPUT TERMINALS (Term. 5-8) ContinuedData 0A: Accel/Decel Speed Prohibit (HOLD Command)As long as the HOLD command is presen
2.20 MULTI-FUNCTION ANALOG MONITOR OUTPUT (Term. 21 & 22)Sn-05: Operation Mode Select 2 Digit 4 [ X X X X ] : Multi-function Analog OutputFactor
2.21 MULTI-FUNCTION OUTPUT TERMINALS (Term. 9 & 10; 25-27)Sn-20: Contact Output (external terminals 9 & 10)Sn-21: Open Collector Output (ext
2.22 OVERTORQUE DETECTIONOvertorque detection is used to compare GPD 503 rated output current with theovertorque detection level. When the output c
2.22 OVERTORQUE DETECTION ContinuedSn-19: Multi-function Analog Data 04: External Overtorque Input (Term. 16) Detection Level AdjustmentThe mul
2.22 OVERTORQUE DETECTION ContinuedEXAMPLE OF OVERTORQUE DETECTIONSn-07 setting: 0101— Overtorque enabled, and only at set frequencySn-19 sett
2.23 SPEED COINCIDENCECn-21: Speed Coincidence Frequency Factory setting: 0.0HzRange: 0.0 to 400.0 HzCn-22: Speed Coincidence Bandwidth Factory s
2.24 REMOTE/LOCAL AND REFERENCE SELECTIONAn-01: Memory 1 An-02: Memory 2 An-03: Memory 3An-04: Memory 4 An-05: Memory 5 An-06: Memory 6An-07: Memory
2-362.24 REMOTE/LOCAL AND REFERENCE SELECTION Continued2.24.2 Multiple Speed Reference Configuration [Multi-step Speed Operation]In a multiple
-vi-WARNINGDo not touch circuit components until main input power has been turned off and“CHARGE” lamp is extinguished. The capacitors are still char
2-36.12.24 REMOTE/LOCAL AND REFERENCE SELECTION ContinuedMode 1 (Memory Data Only) uses only memory locations An-01 thru An-09.The input commands
2.24 REMOTE/LOCAL AND REFERENCE SELECTION ContinuedMode 2 (Memory, Auto, Manual) uses Auto, Manual and An-03 thru An-09.The input commands at ter
2.24 REMOTE/LOCAL AND REFERENCE SELECTION ContinuedMode 3 (An-01, Manual, An-03 thru An-09) uses An-01, Manual and An-03 thruAn-09.The input comm
2.24 REMOTE/LOCAL AND REFERENCE SELECTION ContinuedMode 4 uses An-01 thru An-08 and Analog Manual.The input commands at terminals 5 thru 8 arebin
2.24 REMOTE/LOCAL AND REFERENCE SELECTION ContinuedMode 5The final consideration for multiple frequency command configuration modes is that anyco
2.25 RESET CODES: 2-WIRE, 3-WIRE INITIALIZATIONSn-03: Operator Status Data: 1110= Factory 2-Wire Control Initialization1111= Factory 3-Wire Contro
2.26 SLIP COMPENSATIONbn-08: Slip Compensation Gain Factory setting: 0.0%Range: 0.0 to 9.9 %This constant sets the slip compensation gain, in inc
2.27 SOFT START (S-CURVE) CHARACTERISTICSSn-06: Operation Mode Digits 1 & 2 [ X X X X ] : Soft Start Select 3 CharacteristicsSetting of these tw
2.28 SPEED SEARCH ContinuedRUNSIGNALSPEED SEARCHMAX FREQ., OR FREQ.REF. WHEN SPEED SEARCH IS INPUTTEDOUTPUT FREQUENCYVOLTAGE ATSPEED SEARCHOUTPUT VO
2.28 SPEED SEARCH ContinuedB. Cn-38: Speed Search Deactivation Current Level Factory setting: 150%Range: 0 to 200 %After power recovery, if the G
CONTENTSSUBJECT PAGEGPD 503 SIMPLIFIED START-UP PROCEDURE ... iHORSEPOWER RANGE ...
2.28 SPEED SEARCH ContinuedE. Cn-41: V/f During Speed Search Factory setting: 100%Range: 0 to 100 %To prevent a fault such as OC from occurring d
2.29 STALL PREVENTIONSn-10: Protective Characteristics Data:— X X X 0= Stall prevention enabled Select 1 (Stall Prevention) during acceleration—
2.29 STALL PREVENTION ContinuedSn-19: Multi-function Analog Data 09: Stall Prevention Level Input (Term. 16) During RunningThe multi-function a
2.30 THERMAL MOTOR OVERLOAD PROTECTIONSn-14: Protective Characteristics Select 5 Factory Setting : 0000(Motor Protection)The GPD 503 Electronic Th
2.30 THERMAL MOTOR OVERLOAD PROTECTION Continued2-46.105010015020020010050201052TIME (MIN.)40 Hz60 Hz40 Hz60 Hz IMIM100(%)Sn-14 = 0000 Upper
2.31 TORQUE COMPENSATIONbn-07: Torque Compensation Gain (KT) Factory setting: 1.0Range: 0.0 to 2.0 Sets the torque compensation, in increments of0
APPLI- Sn-02 V/f PATTERN APPLI- Sn-02 V/f PATTERNCATION SPECIFICATION DATA (NOTE 3) CATION SPECIFICATION DATA (NOTE 3)Starting50Hz 0
2.33 V/f PATTERN - CUSTOMA. Cn-01: Output Voltage Regulator Factory Setting: 230/460/575VRange: 0.0 to 255.0 (230V)0.0 to 510.0 (460V)0.0 to 733
2.33 V/f PATTERN - CUSTOM Continued Initial Voltage Values *When Sn-02 = 01 When Sn-02 = 0FB. Cn-02: Frequency – Max. (Fmax)Cn-03: Voltage
2.34 UP/DOWN FREQUENCY SETTING Sn-15 thru Sn-18: Multi-function Input Data 10: UP functionTerminals (Term. 5-8) Data 11: DOWN functionProgrammin
-viii-(THIS PAGE INTENTIONALLY BLANK)
2.34 UP/DOWN FREQUENCY SETTING Continued 2.35 SLIP COMPENSATION DELAY TIME Cn-35: Slip Compensation Delay Time Factory Setting: 2.0secondsRa
2.36 CARRIER FREQUENCY Cn-23: Carrier Frequency Upper Limit Factory Setting: See Table 2-5Cn-24: Carrier Frequency Lower LimitRange (Each): 0.4
2.36 CARRIER FREQUENCY Continued2-532 3 0 V1 DS305 15.0 15.0 0 40 DS2040 2.0 0.4 362 DS302 15.0 15.0 0 40/50GPD503-2L4010.0 10.0 03 DS306 15.0 15
Section 3. DIGITAL OPERATOR3.1 GENERALThe Digital Operator enables the GPD 503 to beoperated in either the Drive (DRIVE) mode or theProgram (PRGM)
B. KEYPAD KEYSLABEL FUNCTIONPRGM Pressing this key toggles between the Drive and Program modes of DRIVE operation. Active only when the GPD 503 is i
B. KEYPAD KEYS - ContinuedLABEL FUNCTION>IN DRIVE MODE OR PROGRAM MODE: When a changeable constant RESET setting value is being displayed, pressi
3.3 COMPARISON OF PROGRAM MODE AND DRIVE MODEDisplays that appear on the Digital Operator differ according to the selected mode ofoperation. The PR
3.4 PROGRAM MODE OPERATIONA. Changing Display With DSPL Key:ACTIONDESCRIPTION DISPLAYApply Power DRIVE lamp is on.— If the GPD 503 fault circuit d
B. Procedure For Changing a Setting:ACTIONDESCRIPTION DISPLAYPress ^and Value of bn-XXdigits scrolls up or v Keys as down by 1 each time one of t
3.5 DRIVE MODE OPERATIONA. Changing Display With DSPL Key:ACTIONDESCRIPTION DISPLAYApply Power DRIVE lamp is on.— If the GPD 503 fault circuit det
Comments to this Manuals