A1-03: Initialize Parameters
Resets parameters to default values. After initialization, the setting for A1-03 automatically returns to 0.
No. Parameter Name Setting Range Default
A1-03 Initialize Parameters
0, 1110, 2220,
3330, 3410, 3420
0
Setting 0: No Initialize
Setting 1110: User Initialize
Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to
“1: Set defaults”.
Note: User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to
clear the user-defined default values.
Setting 2220: 2-Wire Initialization
Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.
Setting 3330: 3-Wire Initialization
Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse
respectively.
Setting 3410: HVAC Initialization
Resets parameters to default settings. The following parameters are not reset:
H1-03: b1 (Customer Safeties)
H1-04: b2 (BAS Interlock)
H1-05: AF (Emergency Override Forward Run)
H2-03: b2 (BAS Interlock Relay Contact)
Note: After performing an HVAC Initialization, H1-03 to H1-05 and H2-03 will be displayed in the Modified Parameters list.
Setting 3420: OEM Bypass Initialization
Resets parameters to default settings. The following parameters are not reset:
H1-03: A7 (BP Customer Safeties)
H1-04: A6 (BP BAS Interlock)
H1-05: A4 (BP Emergency Override)
H1-06: AE (BP Bypass Run)
H2-01: A4 (BP Drive Relay)
H2-02: A5 (BP Bypass Relay)
H2-03: A6 (BP BAS Interlock)
o1-16: 2 (Drive/Bypass)
Note: After performing an OEM Bypass Initialization, H1-03 to H1-05, H2-01 to H2-03, and o1-16 will be displayed in the Modified Parameters
list.
Notes on Parameter Initialization
The parameters shown in Table 4.24 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. Although
the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.
Table 4.24 Parameters Not Changed by Drive Initialization
No. Parameter Name
A1-00 Language Selection
A1-02 Control Method Selection
E1-03 V/f Pattern Selection
F6-08 Communication Parameter Reset
L8-35 Installation Selection
4.12 Advanced Drive Setup Adjustments
144
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual