Basic Programming 5 - 15
E1-04 Maximum Output Frequency
Setting Range: 40.0 to 400.0Hz
Factory Default: 60.0Hz
E1-05 Maximum Output Voltage
Setting Range: 0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 230.0V (240V Models)
460.0V (480V Models)
E1-06 Base Frequency
Setting Range: 0.0 to 400.0Hz
Factory Default: 60.0Hz
E1-09 Minimum Output Frequency
Setting Range: 0.0 to 400.0Hz (Normal Duty)
0.0 to 300.0Hz (Heavy Duty)
Factory Default: 1.5Hz
E1-13 Base Voltage
Setting Range: 0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 0.0V (240V Models)
0.0V (480V Models)
To set up a custom V/F pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be
sure that the following condition is true:
E1-09 ≤ Ε1−07 < Ε1−06 ≤ Ε1−11 ≤ Ε1−04
Fig 5.9 V/F Pattern Parameters
Parameters E1-07, E1-08, E1-10, E1-11, and E1-12 are accessible through the Programming Menu.
Frequency
Voltage
E1-09 E1-07
E1-06
E1-04
E1-11
Max Voltage E1-05
Mid Voltage B E1-12
Mid Voltage A E1-08
Base Voltage E1-13
Min Voltage E1-10
Min
Freq
Max
Fre
q
Base
Freq
Mid
Freq
A
Mid
Freq B
Mid
Freq A
Page view 115