Parameters A - 36
Key Selections
o2-01
Local/Remote Key
Function
Selection
Local/Remote Key
Determines if the Digital Operator Local/Remote key is
functional.
0: Disabled
1: Enabled
0 to 1 1 A A A A
o2-02
STOP Key Function
Selection
Oper STOP Key
Determines if the STOP key on the Digital Operator will stop the
Drive when Drive is operating from external terminals or serial
communication.
0: Disabled
1: Enabled
0 to 1 1 A A A A
o2-03
User Parameter Default Value
User Defaults
Allows storing of parameter settings as a User Initialization
Selection.
0: No Change
1: Set Defaults - Saves current parameter settings as user
initialization. A1-03 now allows selecting <1110> for user
initialization and returns o2-03 to zero.
2: Clear All - Clears the currently saved user initialization. A1-03
no longer allows selecting <1110> and returns o2-03 to zero.
0 to 2 0 A A A A
o2-04
Drive/kVA Selection
Inverter Model #
Sets the kVA of the Drive. Enter the number based on Drive model
number. Use the last four digits of the model number.
CIMR-F7U.
This parameter only needs to be set when installing a new control
board. Do not change for any other reason. Refer to Table B.1.
0 to FF
Va ri es
by
kVA
AA A A
o2-05
Frequency Reference
Setting Method Selection
Operator M.O.P.
Determines if the Data/Enter key must be used to input a frequency
reference from the Digital Operator.
0: Disabled - Data/Enter key must be pressed to enter a frequency
reference.
1: Enabled - Data/Enter key is not required. The frequency
reference is adjusted by the up and down arrow keys on the
Digital Operator without having to press the data/enter key.
0 to 1 0 A A A A
o2-06
Operation Selection when
Digital Operator is
Disconnected
Oper Detection
Determines if the Drive will stop when the Digital Operator is
removed when in LOCAL mode or b1-02=0.
0: Disabled - The Drive will not stop when the Digital Operator is
removed.
1: Enabled - The Drive will fault (OPR) and coast to stop when the
Digital Operator is removed.
0 to 1 1 A A A A
o2-07
Cumulative Operation Time
Setting
Elapsed Time Set
Sets the initial value of the elapsed operation timer U1-13.
0 to
65535
0H A A A A
o2-08
Cumulative Operation Time
Selection
Elapsed Time Run
Sets how time is accumulated for the elapsed operation timer
U1-13.
0: Power-On Time - Time accumulates when the Drive is
powered.
1: Running Time - Time accumulates only when the Drive is
running.
0 to 1 0 A A A A
o2-09
Initialization Specification
Selection
Init Mode Sel
Determines parameter default values after a Drive initialization
(A1-03) is executed. This should always be set to "1" for North
American installations.
1: American spec
Possible damage to equipment or injury may occur if this setting is
changed from “1: American Spec.” O2-09 is a macro parameter that
can change the default values of terminal I/O and many other
parameters in the drive. Consult the Yaskawa factory for details if
adjustment is required.
11AAAA
o2-10
Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Set
Sets the initial value of the heatsink fan operation time monitor
U1-40.
0 to
65535
0H A A A A
o2-12
Fault Trace/Fault History
Clear Function
FLT Trace Init
Clears the fault memory contained in the U2 and U3 monitors.
0: Disabled - no effect
1: Enabled - resets U2 and U3 monitors, and returns o2-12 to zero.
0 to 1 0 A A A A
o2-14
kWh User Monitor
Initialization
kWH MonitorClear
Used to reset the kilowatt-hour monitor U1-29 to zero.
0: Disabled - no change
1: Enabled - Resets U1-29 to zero and returns o2-14 to zero.
0 to 1 0 A A A A
Denotes that parameter can be changed when the Drive is running.
Table A.1 F7 Parameter List (Continued)
Parameter
No.
Parameter Name
Digital Operator Display
Description
Setting
Range
Factory
Setting
Control Method
V/F
V/F
w/PG
Open
Loop
Vector
Flux
Vector
WARNING