Parameter Tables
5-41
H4: Multi-Function Analog Outputs
* The FM output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify Mode while the motor is stopped.
The AM output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify Mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
H4-01
Terminal FM
Monitor Selection
Sets the number of the monitor item to be
output (U1-) from terminal FM.
Items that can be set differ in accordance
with the selected control modes.
For information on the parameters for
which analog output is possible, refer to
U: Monitors.
1 to 99 2 No A A A 41DH 6-79
Terminal FM Sel
H4-02
Terminal FM
Gain Setting
Sets the multi-function analog output 1
voltage level gain.
Sets whether the monitor item output will
be output in multiples of 10 V.
The maximum output from the terminal is
10 V.
A meter calibration function is available.
*
0.00 to
2.50
1.00 Yes Q Q Q 41EH
4-5
6-79
Terminal FM
Gain
H4-03
Terminal FM Bias
Setting
Sets the multi-function analog output 1
voltage level bias.
Sets output characteristic up/down paral-
lel movement as a percentage of 10 V.
The maximum output from the terminal is
10 V.
A meter calibration function is available.
*
-10.0 to
+10.0
0.0% Yes A A A 41FH 6-79
Terminal FM Bias
H4-04
Terminal AM
Monitor Selection
Sets the number of the monitor item to be
output (U1-) from terminal AM.
Items that can be set differ in accordance
with the selected control modes.
For information on the parameters for
which analog output is possible, refer to
U: Monitors.
1 to 99 3 No A A A 420H 6-79
Terminal AM Sel
H4-05
Terminal AM
Gain Setting
Set the voltage level gain for multi-func-
tion analog output 2.
Set the number of multiples of 10 V to be
output as the 100% output for the monitor
items. The maximum output from the ter-
minal is 10 V.
A meter calibration function is available.
*
0.00 to
2.50
0.50 Yes Q Q Q 421H
4-5
6-79
Terminal AM
Gain
H4-06
Terminal AM
Bias Setting
Sets the multi-function analog output 2
voltage level bias.
Sets output characteristic up/down paral-
lel movement as a percentage of 10 V.
The maximum output from the terminal is
10 V.
A meter calibration function is available.
*
-10.0 to
+10.0
0.0% Yes A A A 422H 6-79
Terminal AM
Bias
H4-07
Terminal FM Sig-
nal Level Selec-
tion
Sets the signal output level for multi-
function output 1 (terminal FM)
0: -10 to 10 VDC output
1: -10 to 10 VDC output
0 or 1 0 No A A A 423H 6-79
AO Level Select 1
H4-08
Terminal AM Sig-
nal Level Selec-
tion
Sets the signal output level for multi-
function output 2 (terminal AM)
0: 0 to +10 VDC output
1: 0 to ±10 VDC output
0 or 1 0 No A A A 424H -
AO Level Select 2