Installing and Wiring Option Cards
2-31
Wiring the PG-X2
Wiring examples for the PG-X2 are provided in the following illustrations.
• Shielded twisted-pair wires must be used for signal lines.
• Do not use the pulse generator power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.
• The length of the pulse generator wiring must not be more than 100 meters.
• The direction of rotation of the PG can be set in parameter F1-05 (PG Rotation). The factory preset is
Phase A leads with a forward run command.
Fig 2.27 PG-X2 Wiring
Be sure that the ground terminal is properly grounded using a wire of the recommended size.
200 V class: Ground to 100 Ω or less 400 V class: Ground to 10 Ω
or less