Machine Protection
6-43
Stall Prevention during Run
Stall Prevention during Run prevents the motor from stalling by automatically lowering the MxC's output fre-
quency when a transient overload occurs while the motor is operating at a constant speed.
Stall Prevention during Run is enabled only during V/f Control. If the MxC output current continues to exceed
the setting in parameter L3-06 for 100 ms or longer, the motor speed is reduced. Set whether to enable or dis-
able deceleration time using parameter L3-05. Set the deceleration time using C1-02 (Deceleration Time 1) or
C1-04 (Deceleration Time 2).
If the MxC output current reaches the set value in L3-06 - 2% (MxC Rated Output Current), the motor will
accelerate again at the frequency set or the acceleration time set.
Related Parameters
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control Methods
Display
V/f
Open
Loop
Vector
Flux
Vector
L3-05
Stall Prevention
Selection During
Running
Selects the stall prevention method to use to
prevent MxC faults during run.
0: Disabled.- MxC runs a set frequency. A
heavy load may cause the MxC to trip on
an OC or OL fault.
1: Decel Time 1 - In order to avoid stalling
during heavy loading, the MxC will decel-
erate at Decel time 1 (C1-02) if the output
current exceeds the level set by L3-06.
Once the current level drops below the
L3-06 level, the MxC will accelerate back
to its frequency reference at the active
acceleration rate.
2: Decel Time 2 - Same as setting 1 except
the MxC decelerates at Decel Time 2 (C1-
04).
When output frequency is 6 Hz or less,
Stall Prevention during Run is disabled
regardless of the setting in L3-05.
0 to 2 1 No A No No
StallP Run Sel
L3-06
Stall Prevention
Level During Run-
ning
This parameter is enabled when L3-05 is set
to “1” or “2”. MxC rated current is set as
100%.
Decrease the set value if stalling or excessive
current occurs with the defaults.
30 to
200
160% No A No No
StallP Run Level