6-126
Changing Frequency Reference and Display Units
Set the digital operator frequency reference and display units using parameter o1-03. You can change the units
for the following parameters using o1-03.
U1-01 (shows the frequency reference)
U1-02 (shows the output frequency)
U1-05 (shows the motor speed)
U1-20 (shows the output frequency after Soft Start)
d1-01 to d1-17 (frequency reference parameters)
Switching between Monitors when the Power Supply is On
Using parameter o1-02, select the monitor item (U1- [status monitor]) to be displayed on the digital oper-
ator when the power supply is turned on. For information on monitors that may be displayed, refer to U1-
in Chapter 5 Parameters and Settings.
Setting Precautions
If selecting monitor parameters other than U1-01 (shows the frequency reference), U1-02 (shows the output
frequency), and U1-03 (shows the output current), first select the monitor items to be displayed in o1-01, and
then set o1-02 to 4.
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control Methods
Display
V/f
Open
Loop
Vector
Flux
Vector
o2-03
User Parameter
Default Value
Allows storing of parameter settings as a User
Initialization Selection.
0: No Change
1: Set Defaults - Saves current parameter set-
tings as user initialization. A1-03 now
allows selecting <1110> for user initial-
ization and returns o2-03 to zero.
2: Clear All - Clears the currently saved user
initialization. A1-03 no longer allows
selecting <1110> and returns o2-03 to
zero.
0 to 2 0 No A A A
User Defaults
o2-05
Frequency Refer-
ence Setting
Method Selection
Determines if the DATA/ENTER key must be
used to input a frequency reference from the
digital operator.
0: Disabled. - DATA/ENTER key must be
pressed to enter a frequency reference.
1: Enabled. - DATA/ENTER key is not
required. The frequency reference is
adjusted by the up and down arrow keys
on the digital operator without having to
press the DATA/ENTER key.
0 or 1 0 No A A A
Operator M.O.P.
o2-07
Cumulative Opera-
tion Time Setting
Sets the initial value of the elapsed operation
timer U1-13.
0 to
65535
0 hr No A A A
Elapsed Time Set
o2-10
Cumulative Cool-
ing Fan Operation
Time Setting
Set the initial value of the fan operation time
using time units.
The operation time accumulates from the set
value.
0 to
65535
0 hr No A A A
Fan ON Time Set