1.Servo-related nc alarm
NO.0713 READY ON
2-
0713
READY ON ERROR
V-READY is still ON (diagnosis “0007 bit2 = 1”) even though the P-READY is
OFF (diagnosis “0007 PRD”).
To release the alarm, make the reset key ON by eliminating the cause.
When the parameter “1815 VOC = 1,” the alarm will be cancelled.
This alarm rarely occurs; however if it is the case, the cause may be the
troubles of the magnet contactor or the relay.
0714
ENCODER DISCONNECT
Disconnection of the encoder signal, phase A and phase B, and the ZERO
signal line
To release the alarm, make the reset key ON by eliminating the cause.
The encoder signal can be seen in a general diagnosis.
Diagnosis No. 0006 ENA: Phase A signal
ENB: Phase B signal
ENZ: ZERO signal 1: ON
Items Cause of Trouble How to Verify Measures
1
Improper cable
connection
Verify the connection and wiring of
the encoder return cables.
Correct the cable
connection and
wiring.
2
Inferior EPS3
board
Replace the EPS3
board.
3
Inferior encoder
of the servo
motor
Replace the motor
or the encoder.