6. Operating with DeviceNet Communications
119
MEMOBUS Register Tables
Reference Data (Read/Write Registers)
Write zeroes in the unused bits. Do not write any data in the reserved
registers.
Register
Number
Contents
0000H Reserved
0001H Operation signals
Bit 0 RUN command
1: RUN
0: STOP
1 Reverse RUN command
1: Reverse run
0: Stop
2 Multi-function input reference 3
(Function selected by n052.)
3 Multi-function input reference 4
(Function selected by n053.)
4 Multi-function input reference 5*
(Function selected by n054.)
5 Multi-function input reference 6*
(Function selected by n055.)
6 Multi-function input reference 7*
(Function selected by n056.)
7 Not used.
8 External fault
1: Fault (EF0)
9 Fault reset
1: RESET command
A Not used.
B to
F
Not used.
0002H Frequency reference (Units set in n035.)
0003H V/f gain (1000/100%)
Setting range: 2.0 to 200.0%
0004H to
0008H
Reserved