To connect a reactor between the Inverter and the motor, set n108 to the
sum of the initial value of n108 (Motor Leakage Inductance) and the
externally mounted reactor inductance. Unless a reactor is connected,
n108 (Motor Leakage Inductance) does not have to be set according to
the motor.
V/f Pattern during Vector Control
Set the V/f pattern as follows during vector control:
The following examples are for 200 V Class motors. When using 400 V
Class motors, double the voltage settings (n012, n015, and n017).
Standard V/F
[Motor Specification: 60 Hz]
(V)
(Hz)
[Motor Specification: 50 Hz]
(V)
(Hz)
[Motor Specification: 50 Hz]
(V)
(Hz)
High Starting Torque V/F
[Motor Specification: 60 Hz]
(V)
(Hz)