Errors Indicated by the DeviceNet Communications
Indicators
The following table shows the errors indicated by the MS and NS indi-
cators on the Inverter, the likely causes of the errors, and the recom-
mended corrective actions.
Indicator Status Meaning Cause Corrective Action
MS NS
Power
supply
OFF
Power is not being
supplied to the
Inverter.
Check the Inverter’s
main circuit wiring and
turn ON the power.
- Initializing
communi-
cations
There is an incor-
rect baud rate set-
ting or there is a
MAC ID duplication.
Correct the baud rate or
MAC ID setting and turn
ON the Inverter’s power
again. Replace the
Inverter if the problem
recurs.
- Recover-
able (non-
fatal) error
There was a non-fa-
tal error.
Replace the Inverter if
the problem recurs.
Irrecover-
able (fatal)
error
A fatal error related
to communications
occurred.
Turn ON the Inverter’s
power again. Replace
the Inverter if the prob-
lem recurs.
Communi-
cations
timeout
A communications
timeout occurred
with the Master.
Check that the termi-
nators are properly
connected to the
communications
line.
Check that the com-
munications lines
are properly con-
nected. (Check for
cable damage and
bad connections.)
Check that the com-
munications lines
are separated from
the main circuit wir-
ing.
Green
Red
Red
Green
or
Red
Red