4. The carrier frequency is automatically reduced to 2.5 kHz
when the Reducing Carrier Frequency Selection at Low
Speed (n175) is set to 1 and the following conditions are
satisfied:
Output frequency 5 Hz
Output current 110%
Factory setting: 0 (Disabled)
5. When repeatedly starting and stopping a load that is more
than 120% of the Inverters rated current with a period of
less than 10 minutes, set the Reducing Carrier Frequency
Selection at Low Speed (n175) to 1.
Operator Stop Key Selection (n007)
The Digital Operator stop button can be disabled by a
setting in the Inverter. Install a separate emergency
stop switch.
Failure to observe this warning may result in injury.
Set the processing when the STOP key is “pressed” during operation
either from a multi-function input terminal or communications.
Setting Description
0 The STOP key is effective either from a multi-
function input terminal or communications. When
the STOP key is pressed, the Inverter stops ac-
cording to the setting of constant n005. At this
time, the Digital Operator displays a alarm
(flashing). This STOP command is held in the
Inverter until both forward and reverse RUN com-
mands are open, or until the RUN command from
communications goes to zero.
1 The STOP key is ineffective either from multi-
function input terminals or communications.
WARNING