Data Name Contents
Byte 0,
bit 0
Running Indicates the Inverter’s operating status.
0: Stopped.
1: Operating forward, operating in
reverse, or applying DC injection
braking.
Byte 0,
bit 1
ZSP Indicates the Inverter’s operating status.
0: Operating forward or in reverse.
1: Stopped or applying DC injection
braking.
Byte 0,
bit 2
Rev Run-
ning
Indicates the Inverter’s operating status.
0: Operating forward, stopped (Reverse
RUN command OFF), or applying DC
injection braking (Reverse RUN com-
mand OFF).
1: Operating in reverse, stopped
(Reverse RUN command ON), or
applying DC injection braking
(Reverse RUN command ON).
Byte 0,
bit 3
Reset Indicates the input status of the
Inverter’s RESET signal.
0: ---
1: RESET signal being input.
Byte 0,
bit 4
At Refer-
ence
Indicates that the Inverter’s frequency
match was detected.
0: Stopped, accelerating, or decelerat-
ing.
1: Frequency matches.
Byte 0,
bit 5
Ready Indicates the Inverter’s preparation sta-
tus.
0: Fault detected or initializing.
1: Preparations for operation completed.