* Terminal MA can be used only from DeviceNet communications. There is
no corresponding external output terminal.
Acceleration/Deceleration Time Control I/O Instances
Acceleration/Deceleration Time Control I/O Instances are for
DeviceNet-compatible Inverters only. They support the functions of the
V7 standard control I/O instances and also allow the acceleration/decel-
eration time to be set and the motor speed (estimated value) to be moni-
tored. Eight bytes are used for input data and eight bytes are used for
output data.
Byte 1,
bit 5
Te r min al
P2
Indicates the output status of Inverter
multi-function output terminal P2.
0: Terminal P2 OFF
1: Terminal P2 ON
Bytes
2 and 3
Speed Ac-
tual
Indicates the Inverter’s speed.
The units depend on the setting in Invert-
er constant n035. The units are not af-
fected by the speed scale (SS) setting.
Bytes
6 and 7
Output
Current
Indicates the Inverter’s output current.
The units are fixed at 0.1 A. The units
are not affected by the current scale
(CS) setting.
Data Name Contents