YASKAWA Varispeed-606PC3 Instruction Manual Page 126

  • Download
  • Add to my manuals
  • Print
  • Page
    / 256
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 125
6. Operating with DeviceNet Communications
125
* The MA output signal can be used from DeviceNet communications only.
There is no corresponding external output terminal.
Constant Data
Inverter constants can be set or referenced. For the register numbers of
the constants, refer to the list of constants given on page 242.
Register
Number
Contents
002DH Output status
Bit 0
MA
*
(1: Closed)
1 P1 (1: Closed)
2 P2 (1: Closed)
3 Not used.
4 Not used.
5 Not used.
6 Not used.
7 Not used.
8 to F Not used.
002EH to
0030H
Reserved.
0031H Main circuit DC voltage (1/1 V)
0032H Torque monitor (1/1%; 100%/Rated motor torque; signed)
0033H to
0036H
Not used.
0037H Output power (100/1 KW; signed)
0038H PID feedback value (100(%)/Input corresponding to max. output
frequency;10/1%; unsigned)
0039H PID input value (±100(%)/±Max. output frequency; 10/1%; signed)
003AH PID output value (±100(%)/±Max. output frequency; 10/1%;
signed)
003BH Output current (10/1 A)
003CH to
00FFH
Reserved.
Page view 125
1 2 ... 121 122 123 124 125 126 127 128 129 130 131 ... 255 256

Comments to this Manuals

No comments