This section describes how to read and understand the parameter tables.
Understanding Parameter Tables
Parameter tables are structured as shown below. Here, b1-01 (Frequency Reference Selection) is used as an
example.
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Display
V/f
Open
Loop
Vector
Flux
Vector
b1-01
Frequency Refer-
ence Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed U1-01 or d1-
01 to d1-17.
1: Terminals - Analog input terminal A1 (or
terminal A2 based on parameter H3-09).
2: Serial Com - Modbus RS-422/485 terminals
R+, R-, S+, and S-.
3: Option PCB - Option card connected on
2CN.
0 to 3 1 No Q Q Q 180H
Reference Source
• Parameter Number: The number of the parameter.
• Name: The name of the parameter.
• Description: Details on the function or settings of the parameter.
• Setting Range: The setting range for the parameter.
Default: The default (each control method has its own default. Therefore the default
changes when the control method is changed).
Refer to page 5-64 for defaults by control method.
Changes during Run: Indicates whether or not the parameter can be changed while the MxC is in
operation.
Yes: Parameter settings can be changed while the Run Command is present.
No: Settings cannot be changed while the Run Command is present.
• Control Methods: Indicates the control methods in which the parameter can be monitored or set.
Q: Items which can be monitored and set in either Quick Programming Mode
or Advanced Programming Mode.
A: Items which can be monitored and set only in Advanced Programming
Mode.
No: Items which cannot be monitored or set for the control method.
• MEMOBUS Register: The register number used for MEMOBUS communications.
• Page: Reference page for more detailed information on the parameter.