Yaskawa Matrix Converter User Manual Page 134

  • Download
  • Add to my manuals
  • Print
  • Page
    / 398
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 133
5-34
H: Terminal Function
The following settings are made with the terminal function parameters (H parameters): Settings for external
terminal functions.
H1: Multi-Function Contact Inputs
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
H1-01
Multi-Function
Digital Input Ter-
minal S3 Function
Selection
Multi-function contact input 1 0 to 78 24 No A A A 400H -
Terminal S3 Sel
H1-02
Multi-Function
Digital Input Ter-
minal S4 Function
Selection
Multi-function contact input 2 0 to 78 14 No A A A 401H -
Terminal S4 Sel
H1-03
Multi-Function
Digital Input Ter-
minal S5 Function
Selection
Multi-function contact input 3 0 to 78
3 (0)
*
No A A A 402H -
Terminal S5 Sel
H1-04
Multi-Function
Digital Input Ter-
minal S6 Function
Selection
Multi-function contact input 4 0 to 78
4 (3)
*
No A A A 403H -
Terminal S6 Sel
H1-05
Multi-Function
Digital Input Ter-
minal S7 Function
Selection
Multi-function contact input 5 0 to 78
6 (4)
*
No A A A 404H -
Terminal S7 Sel
H1-06
Multi-Function
Digital Input Ter-
minal S8 Function
Selection
Multi-function contact input 6 0 to 78 8 No A A A 405H -
Terminal S8 Sel
H1-07
Multi-Function
Digital Input Ter-
minal S9 Function
Selection
Multi-function contact input 7 0 to 78 5 No A A A 406H -
Terminal S9 Sel
H1-08
Multi-Function
Digital Input Ter-
minal S10 Func-
tion Selection
Multi-function contact input 8 0 to 78 32 No A A A 407H -
Terminal S10 Sel
Page view 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 397 398