5-24
d6: Field Weakening
Parameter
Number
Name
Description
Setting
Range
Default
Change
during
Run
Control
Methods
MEMO-
BUS
Register
Page
Display
V/f
Open
Loop
Vector
Flux
Vector
d6-01
Magnetic Field
Weakening Level
Set the MxC output voltage when the
field weakening command is input.
It is enabled when the field weakening
command is set for a multi-function
input.
Set the level as a percentage taking the
voltage set in the V/f pattern as 100%.
0 to 100 80% No A No No 2A0H -
Field-Weak Lvl
d6-02
Magnetic Field
Frequency
Set the lower limit in hertz of the fre-
quency range where field control is valid.
The field weakening command is valid
only at frequencies above this setting and
only when the speed is in agreement with
the current speed reference.
0.0 to
120.0
0.0 Hz No A No No 2A1H -
Field-Weak Freq
d6-03
Magnetic Field
Forcing Function
Selection
Set the field forcing function.
0: Disabled
1: Enabled
0 or 1 0 No No A A 2A2H -
Field Force Sel
d6-06
Magnetic Field
Forcing Limit
Set the excitation current reference’s
upper limit for field forcing. Set the limit
as a percentage, taking the motors no-
load current as 100%. Enabled for opera-
tion other than DC excitation.
Usually, there is no need to change this
setting.
100 to
400
400% No No No A 2A5H -
FieldForce Limit