  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 137
5-38
* Applicable for the Varispeed AC with software versions PRG:1050 or later.
E
Fault (ON: Digital operator communications error or fault other than CPF00 and
CPF01 has occurred).
Yes Yes Ye s -
F Not used (Set when the terminals are not used). - - - -
10 Minor fault (ON: Alarm displayed) Yes Yes Yes -
11 Fault Reset Command active Yes Yes Yes -
12 Timer function output Yes Yes Yes 6-93
13 Frequency agree 2 (L4-04 used) Yes Yes Yes 6-45
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and during
frequency agree)
Yes Yes Ye s 6-4 5
15 Frequency detection 3 (ON: Output frequency -L4-03, L4-04 used) Yes Yes Yes 6-45
16 Frequency detection 4 (ON: Output frequency -L4-03, L4-04 used) Yes Yes Yes 6-45
17 Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at off) Yes Yes Yes 6-49
18 Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at on) Yes Yes Yes 6-49
19 Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at off) Yes Yes Yes 6-49
1A During reverse run (ON: During reverse run) Yes Yes Yes -
1B During baseblock 2 (OFF: During baseblock) Yes Yes Yes -
1C Motor selection (Motor 2 selected) Yes Yes Yes -
1D During regeneration (ON: During regeneration) No No Yes -
1E Restart enabled (ON: Restart enabled.) Yes Yes Yes 6-65
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection
level)
Yes Yes Ye s
6-51
6-78
20 MxC overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting) Yes Yes Yes 6-78
2F
*
Maintenance Time
ON: The operation time of either the capacitors on the PCB board or the cooling fan
have reached the specified maintenance time.
Yes Yes Ye s 6- 155
30 During torque limit (current limit) (ON: During torque limit) No Yes Yes -
31 During speed limit (ON: During speed limit) No No Yes 6-78
32
Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected (internal
torque reference < external torque reference).
Output when the motor is rotating at the speed limit.
No No Yes 6-109
33 Zero-Servo Complete (ON: Zero-servo function completed) No No Yes
6-78
6-123
36
Frequency (FOUT) detection 5 (ON: Output frequency is equal to or greater than the
set value of +L4-01 or equal to or less than the set value of L4-01 and L4-02 is used,
off during base blocked)
Yes Yes Ye s 6-4 4
37
During Run 2 (ON: Frequency output, off: Baseblock, DC Injection Braking, initial
excitation, operation stop)
Yes Yes Ye s 6-7 7
Set
Value
Function
Control
Methods
Page
V/f
Open
Loop
Vector
Flux
Vector