Specifications for Options and Peripheral Devices
9-5
Specifications for Options and Peripheral Devices
The following options and peripheral devices can be used for the MxC. Select them according to the
application.
* 1. Use an earth leakage breaker that has harmonics protection and a minimum current of 30 mA per MxC. Otherwise, the harmonic leakage current may cause a mal-
function. If a malfunction occurs in an earth leakage breaker without harmonic protection, lower the carrier frequency of MxC, replace the earth leakage breaker
with one that has harmonic protection, or raise the current of the earth leakage breaker to 200 mA or more per MxC.
* 2. The FINEMET zero-phase reactor is manufactured by Hitachi Metals.
Table 9.4 Options and Peripheral Devices
Purpose Name Model (Code) Descriptions
Protect MxC
wiring
MCCB or
Ground Fault
Interrupter
*1
NF
Always connect a breaker to the power supply line to
protect MxC wiring. Use a ground fault interrupter
suitable for high frequencies.
Prevents burning
of the MxC.
Magnetic Con-
tactor
SC series
Install to prevent the MxC from burning out when
faults occur at the input terminal side of the MxC.
Always attach a surge absorber to the coil.
Contains switch-
ing surge
Surge Absorber DCR2-
Absorbs surge from the magnetic contactor and con-
trol relays. Connect surge absorbers to all magnetic
contactors and relays near the MxC.
Isolates I/O
signals
Isolator DGP
Isolates the I/O signals of the MxC and is enabled
against inductive noise.
Reduces the
affects of radio
and
control device
noise
Input Noise
Filter
LNFD-
FN-
Reduces noise coming into the MxC from the power
supply line and to reduce noise flowing from the
MxC into the power supply line. Connect as close to
the MxC as possible.
FINEMET
zero-phase
reactor to reduce
radio noise
*2
F6045GB
(FIL001098)
F11080GB
(FIL001097)
F200160BP
(300-001-041)
Reduces noise from the line that sneaks into the MxC
input power system. Insert as close to the MxC as
possible.
Can be use on both the input side and output side.
Output Noise
Filter
LF-
Reduces noise generated by the MxC. Connect as
close to the MxC as possible.
Operates the MxC
externally
VS Operator
(small plastic
Operator)
JVOP-95•
(73041-0905X-)
Allows frequency reference settings and on/OFF
operation control to be performed by analog refer-
ences from a remote location (50 m max).
Frequency counter specifications: 60/120 Hz, 90/
180Hz
VS Operator
(Standard
steel-plate
Operator)
JVOP-96•
(73041-0906X-)
Allows frequency reference settings and on/OFF
operation control to be performed by analog refer-
ences from a remote location (50 m max).
Frequency counter specifications: 75 Hz, 150 Hz,
220 Hz
Digital Operator
Connection
Cable
1 m cable:
(72606-WV001)
3 m cable:
(72606-WV003)
Extension cable to use a digital operator remotely.
Cable length: 1 m or 3 m
Controls an MxC
system
VS System
Module
JGSM-
A system controller that can be match to the auto-
matic control system to produce an optimum system
configuration.
Saves the momen-
tary power loss
compensation
time of MxC
Momentary
power loss com-
pensation unit
P000
(73600-P000)
Safety measure taken to protect against momentary
power loss of the control power supply.
Set/monitor
frequencies and
voltages
externally.
Frequency Meter DCF-6A
Devices to set or monitor frequencies externally.
Frequency Setter
RV30YN20S
(2 kΩ)
Frequency Set-
ter Knob
CM-3S
Output Voltmeter SCF-12NH
Measures the output voltage externally and designed
for use with a PWM MxC.
Correct frequency
reference input,
frequency meter,
ammeter scales
Variable
Resistor Board
for Frequency
Reference
2 kΩ
(ETX003270)
20 kΩ
(ETX003120)
Connected to the control circuit terminals to input a
fr
equency reference.
Frequency Meter
Scale Correction
Resistor
(RH00085
0)
Calibrates the scale of frequency meters and amme-
ters.
Power
supply
Molded-case
circuit breaker
or ground fault
interrupter
Magnetic
contactor
(MC)
Moto
r
Ground
Input noise
filter
Output noise
filter
MxC
Ground
Zero phase
reactor
Zero phase
reactor